<br />SECTION IV - SYSTEM DESIGN <br />UL EX. 3470 ULC CEx747 Page 4-40 <br />REV. 2 10-1-02 <br /> <br />TANK AND CARTRIDGE REQUIREMENTS <br /> <br />Once the hazard analysis is eompleted and the total nozzle flow <br />numbers are established, the quantity and size of agent tanks and <br />cartridges needed to supply the nozzles with the proper volumes <br />of agent at the proper flow rates can be determined. For cartridges <br />used in the regulated release mechanism, flow capacities, tank <br />quantities and sizes, and regulated release cartridge options are <br />given in the table below. <br /> <br />Total Quantity and <br />Flow Size of <br />Numbers* Thnk(s} <br /> <br />.. 1 - 5 (1) 1.5 Gallon <br /> <br />6 -11 (1) 3.0 Gallon <br /> <br />11 -16 (1) 1.5 Gallon <br />(1) 3.0 Gallon <br /> <br />.. 16 - 22 (2) 3.0 Gallon Double 101-30** <br /> <br />When one or more regulated actuators are used, the following <br />tank and cartridge combinations apply for each regulated actuator: <br /> <br />Regulated Actuator Regulated Actuator <br />Tank(s) Cartridge <br /> <br />(1) 1.5 Gallon LT-20-R or 101-10 <br />(1) 3.0 Gallon LT-3O-R or 101.20 <br />(1) 1.5 Gallon and LT-A-101-3O or 101-30** or <br />.. (1) 3.0 Gallon double tank <br />(2) 3.0 Gallon LT-A-101-3O or 101-30** or <br />.. double tank <br /> <br />Regulated Release <br />Cartridge Options <br />Nitrooen Carbon Dioxide <br /> <br />LT-20-R 101-10 <br /> <br />LT-3O-R 101-20 <br /> <br />Double 101-30 <br /> <br />. For exceptions to maxItrom flow numbers, see Distribution Piping Requirements for 1.5 gal- <br />lon and 3.0 gallon systems in this Section. <br />.. .. The 101-30 cartridge can not be used when (2) two 3.0 gallOn tanks are manifolded together.) <br /> <br />For higher total flow numbers (23 to 110), multiple cartridges and <br />regulated actuators are required as shown in the System Selection <br />Guide in Section IX - Appendix. <br /> <br />.. <br />.. <br /> <br />ACTUATION AND EXPELLANT GAS LINE REQUIREMENTS <br /> <br />This section contains the guidelines for installing the actuation and <br />expellant gas lines between the regulated release mechanism reg- <br />ulator, each regulated actuator regulator, and each agent tank. <br />These limitations should be considered when selecting the com- <br />ponent mounting locations. <br /> <br />Aetuatlon Gas Line - 6 to 8* Tanks Maximum <br />. 8 Tank maximum reflects the utilization of 3 tank regulated actuators. <br /> <br />1. Use only 1/4 in. Schedule 40 black iron, hot-dipped galva- <br />nized, chrome-plated, or stainless steel pipe and fittings. <br /> <br />2. The actuation gas line piping is installed from the regulated <br />release mechanism to each regulated actuator connected <br />within the system. The total leng1h of the actuation gas line <br />from the regulated release assembly to the regulated actuator <br />assembly(ies) must not exceed 20 ft. (6 m) when using an <br />L T-2Q-R, an LT-3Q-R nitrogen cartridge, or a 101-10 or a 101- <br />20 carbon dioxide cartridge. See Figure 71. <br /> <br />.. <br /> <br />REGULATED ACTUATOR ASSEMBLY <br />EXPELLANT GAS LINES <br />NOT INCLUDED IN ACTUATION <br />GAS LINE LENGTH TOTALS <br /> <br /> <br />ACTUATION GAS LINE WITH AN LT.20-R. <br />LT.30-R. 101-10 OR 101-20 CARTRIDGE <br />MAXIMUM LENGTH OF 20 FT. (6 m), <br />MAXIMUM NO. OF FITTINGS 9 <br /> <br />.. <br /> <br />FIGURE 71 <br />000776 <br />