Laserfiche WebLink
<br />SECTION IV - SYSTEM DESIGN <br />UL EX. 3470 ULC CEx747 Page 4-52 <br />REV. 1 10-1-02 <br /> <br />MANUAL PULL STATION REQUIREMENTS <br /> <br />A remote manual pull station allows the R-102 system to be man- <br />ually operated at some point distant from the regulated release <br />assembly. The pull station should be installed at a maximum height <br />of 60 in. (152 cm) and located in the path of exit. The pull station <br />is the only source of manual actuation of the regulated release <br />assembly. <br /> <br />The totalleng1h of the cable used for each manual pull station with- <br />in a system must not exceed 150 ft. (46 m). <br /> <br />The maximum number of pulley elbows that may be used per pull <br />station is 20. <br /> <br />One pulley tee, Part No. 427929, is allowed per system. <br /> <br />The maximum length of cable from the AllTOMAN to a pull station <br />is 150 ft. (45.7 m) with a maximum of 20 pulley elbows used per <br />side of the tee. As the tee is located far1her from the AUTOMAN, <br />the 150 ft. (45.7 m) maximum must be observed but as pulley <br />elbows are placed between the AUTOMAN and the tee, they must <br />be deducted from the available pulley ebows (20) allowed on each <br />side. <br /> <br />Example: If 10 pulley elbows are placed between the AUTOMAN <br />and the pulley tee, the maximum available pulley elbows left for <br />~ use on each side of the tee is 10 per side. See Figure 94 for three <br />I different examples. (Note: Both must be gas valves or both must <br />. be pull stations. Mixing is not allowed.) <br /> <br />TEE CLOSE TO AUTOMAN (EXAMPLE) <br />PULLEY TEE <br /> <br />12 IN. <br />(305 mm) <br /> <br />AUTOMAN <br />GAS VALVE OR GAS VALVE OR <br />MANUAL PULL MANUAL PULL <br /> <br />149 FT. (45.4 m) AND 20 PULLEY BBOWS MAXIMUM <br />PER EACH SIDE OF TEE <br /> <br />TEE CLOSE TO GAS VALVES OR MANUAL PULL (EXAllPLE) <br /> <br />12 IN. <br />(305 mrn) <br /> <br />12 IN. <br />(305 mm) <br /> <br /> <br />AUTOMAN <br />149 FT. (45.4 m) AND 20 PULLEY ELBOWS BETWEEN <br />AUTOMAN AND TEE <br /> <br />TEE HALFWAY BETWEEN AUTOMAN AND GAS VALVES OR MANUAL PULL (EXAMPLE) <br />75 FT. (22.9 m) AND 10 PULLEY B.Jl(JNS <br /> <br />75 FT. (22.9 m) AKJ 75 FT. (22.9 m) AND <br />10 PULLEY ELBOWS 10 PULLEY ELBOWS <br /> <br />PUU.EYTEE <br /> <br />AUTOMAN <br /> <br />GAS VI'J..VE OR <br />MANUAL PULL <br /> <br />GAS VALVE OR <br />MANUAL PULL <br /> <br />. <br /> <br />FIGURE 94 <br />004007 <br /> <br />Metal SWnped Style - Part No. 4835 or 54011 <br />Parts that may be used for installation of a metal stamped remote <br />manual pull station are: <br /> <br />DescriDtion <br />Remote Manual Pull Station Assembly* <br />Remote Manual Pull Station Assembly <br />Pulley Elbow <br />Pulley Elbow <br />Pulley Tee <br />'AssemIlly includes parts listed below: <br /> <br />1/16" Stainless Steel Cable 50 ft. (15 m) <br />Oval Press-To-Crimp Sleeves <br />Glass Break Rod (1) <br /> <br />~ <br />54011 <br />4835 <br />423250 <br />415670 <br />427929 <br /> <br />15821 <br />4596 <br />4834 <br /> <br />MECHANCAL GAS VALVE REQUIREMENlS <br /> <br />An Ansul or Ansul approved mechanical gas shut-off valve system <br />can be attached to the R-102 system. The system works both <br />mechanically and pneumatically by use of an air cylinder located <br />inside the regulated release assembly. Upon actuation of the fire <br />suppression system, a pneumatically-operated air cylinder assem- <br />bly will mechanically close the gas shut-off vaMl. <br /> <br />The totalleng1h of the cable for each mechanical gas valve must <br />not exceed 150 ft. (46 m). The maximum number of pulley elbows <br />that may be used is 20 for each valve. <br /> <br />One pulley tee (Part No. 427929) is allowed per system. <br /> <br />The maximum leng1h of cable from the AUTOMAN to a gas valve is <br />150 ft. (45.7 m) with a maximum of 20 pulley elbows used per side <br />of the tee. As the tee is located farther from the NJTOMAN, the 150 <br />ft. (45.7 m) maximum must be observed but as pulley elbows are <br />placed between the AUTOMAN and the tee, they must be deduct- <br />ed from the available pulley elbows (20) allowed on each side. <br /> <br />Example: If 10 pulley elbows are placed between the AUTOMAN <br />and the pulley tee, the maximum available puley elbows left for <br />~ use on each side of the tee is 10 per side. See Figure 94 for three <br />different examples. <br /> <br />Parts that may be used for installation of a Mechanical Gas Shut- <br />off Valve are: <br /> <br />Description <br />Gas Valve/Actuator 3/4 in. Assembly (Ansul)* <br />Gas Valve/Actuator 1 in. Assembly (Ansul)* <br />Gas Valve/Actuator 1 1/4 in. Assembly (Ansul)* <br />Gas Valve/Actuator 1 1/2 in. Assembly (Ansul)* <br />Gas Valve/Actuator 2 in. Assembly (Ansul)* <br />Gas Valve/Actuator 2 1/2 in. Assembly (ASCO)* <br />Gas Valve/Actuator 3 in. Assembly (ASCO)* <br />Pulley Ellow <br />Pulley Elbow <br />Pulley Tee <br />1/16" Stainless Steel Cable <br />50 ft. (15 m) or 500 ft. (152 m) roll <br />Oval Press-To-Crimp Sleeve <br />Stop Sleeve (2) <br />. Assembly includes parts listed below: <br />Air Cylinder Assembly <br />Air Cylinder <br />Tubing Assembly <br />Copper Tubing, 1/8 in. <br />Male Elbow <br />Male Connector <br />Machine Screw (2) <br />Hex Nut (2) <br />Lockwasher (2) <br />Visual Inspection Seal (2) <br /> <br />Ew:1.l& <br />55598 <br />55601 <br />55604 <br />55607 <br />55610 <br />25937 <br />25938 <br />423250 <br />415670 <br />427929 <br />15821 or <br />79653 <br />4596 <br />26317 <br /> <br />15733 <br />15521 <br />15529 <br />15525 <br />15523 <br />15522 <br />15421 <br />15527 <br />4141 <br />197 <br />