Laserfiche WebLink
<br />Specifications <br /> <br />POWER REQUIREMENTS 12 VDC nominal, 5501IA Alarm and Standby. Power supplied from the Multiplex <br /> bus. <br />INPUTS Single Action. <br />ALARM OUTPUT Reports Alarm and Point Number to the FACP. <br />TROUBLE OUTPUT Reports Trouble and Point Number 10 the FACP. <br />RADIO FREQUENCY INTERFERENCE No alarm on critical frequencies in the range from 26 10 950 Megahertz <br />(RFI) IMMUNITY at 30 vim. <br />STORAGE & OPERATING +320 to +120oF 1 00 to +490C. non-condensing RH. <br />TEMPERATURE <br />ADDRESS PROGRAMMING Addresses are set by 3 rotary switches. <br />ENCLOSURE DESIGN Diecast Zinc Alloy and steel enclosure. <br /> 07045 Measures: 4.75 in. H., ~ 3.75 in. W., by 3.25 in. D. (12 cm H., 9.5 em W., <br /> 8.2 em D). Weighs 1 lb. 8 oz. ( 0 g). <br />WIRING Terminal block accepts up to 12 AWG (2.3 mm) wire. <br />MOUNnNG The D7045mounts 10 a 3 in. x 2 in. x 3~ device box gilre a Steel Citt CXW) or a <br /> 4 in. x 2118 square box with a 518 in. mud ring (like t e Steel City 5 171 box and <br /> 52-G-14-518 mud ring) with the two provided screws. <br />OPTIONS 0463 Double Action Cover. <br /> 0464 Red Back Box for manual PuU Stations, Deep. <br /> 0465 Replacement Glass Break Rod. <br />LISTINGS Ullisting Ul864 <br />ORDERING INFORMATION 07045 Single Action Pull Station <br /> <br /> <br />07045 Rear View <br /> <br />ISO 9002 C!i) <br /> <br />CERT1F1CATE NO. A5137 <br /> <br />508916 <br />Specifications <br /> <br />5/02 <br />07045 <br />Page 2 of 2 <br /> <br />@ 2002 Radionics, a division of Detection Systems, Inc. <br />PO Box 80012, Salinas, CA 93912-0012 USA <br />Customer Service: (800) 538-5807 <br />