My WebLink
|
Help
|
About
|
Sign Out
Browse
Search
07-6953
Zephyrhills
>
Building Department
>
Permits
>
2007
>
07-6953
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/6/2009 4:33:32 PM
Creation date
1/10/2008 11:01:51 AM
Metadata
Fields
Template:
Building Department
Building Department - Doc Type
Permit
Permit #
07-6953
Building Department - Name
ZEPHYR PALMS
Address
4645 AIRPORT RD
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
31
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
<br />HD-600 SERIES TESTING METHODS <br /> <br />-Models HD-601/HD-621 and HD-602lHD-622 can be tested by the application of quick heat from any convenient <br />source. A portable hair dryer is recommended. However, do not apply heat that exceeds the fixed-temperature rating <br />of the detector.'. <br /> <br />_ Models HD-603/HD-623 and HD-604/HD-624 cannot be tested. However, the fusible alloy element is gene~al/y con- <br />sidered so reliable that testing is not necessary. <br /> <br />SPECIFICATIONS <br /> <br />S075n.tbl, S075doti.wm', 5075dot2.wmf, 5075dot3.wrnf. 5075dot4.wmf <br /> <br />HD-601 & HD-621 HD-602 & HD-622 HD-603& HD-623 H0-604 & HD-624 <br />No marking. 0 Gray ring. 0 Gray spot 8 Black dot on white. ~ <br />Model HD-601 (one circuit) Model HD-602 (one circuit) Model HD-603 (one circuit) Model HC-604 (one circuit) <br />Model HD-621 (dual circuit) Model HC-622 (dual circuit) Model HD-623 (dual circuit) Model HD-624 (dual circuit) <br />RatEH)f -rise and Rate-of -rise and Fixed-temperature only Fixed-temperature only <br />fixed-temperature fixed-temperature 135.F (57.C). 200.F (94.C). <br />135"F (57.C). 200.F (94.C). <br />Application: nonnal Application: nonnal Application: unusually violent Application: unusually violent <br />temperature fluctuations and temperature fluctuations and temperature fluctuations and temperature fluctuations and <br />ceiHng temperatures not ceiling temperatures ceiling temperatures not ceiting temperatures <br />exceeding 100.F (3S.C). exceeding 100.F (3S"C) but exceeding 100"F (3S"C). exceeding 100.F (3e"C) but <br /> not 150"F (66.C). not 150"F (66"C). <br />Maximum spacing allowance" Maximum spacing allowance" , Maximum spacing allowance" Maximum spacing allowance" <br />UL: 50 ft. x 50 ft. UL: 50 ft. x 50 ft. UL: 25 ft. x 25 ft. UL & FM: 15 ft. x 15 ft <br />(1524 x 15.24 meters). (15.24 x 15.24 meters). (7.62 x 7.62 meters). (4.572 x 4.572 meters). <br />FM: 30 ft. x 30 ft. FM: 30 ft. x 30 ft. FM: 20 ft. x 20 fl <br />(9.144 x 9.144 meters). (9.144 x 9.144 meters). (6.096 x6.096 meters). <br />*Refer1o NFPA for application requirements. <br /> <br />SCREW TERMINALS <br /> <br />Standard <br />Single-Circuit <br />Detector <br /> <br />Dual-circuit <br />Detector <br />Used to send two <br />independent signals. <br /> <br />Wire from <br />alarm panel <br />or previous <br />detector. <br />\~ <br /> <br />Wire connected to <br />next detector or <br />end-of-line resistor. <br />/ <br /> <br /> <br /> <br />Wire from <br />alarm panel <br />or previous <br />detector. \.. <br /> <br />1/ <br /> <br />Wire connected to <br />next detector or <br />end-of-line resistor. <br /> <br />Wire connected to <br />next detector or <br />end-of-Iine resistor. <br /> <br />NOTE: All single-circuit <br />models come with one (1) <br />normally open dry contact. <br /> <br />NOTE: All dual-circuit <br />models come with two (2) <br />normally open dry contacts. <br /> <br />50751er1.wmf <br /> <br />S075ter2.wmf <br /> <br />Page 2 of 2 - DF-51375 <br /> <br />NOTES <br /> <br />Application: Heat detectors should be <br />used for property protection. Reliance <br />should not be placed solely on heat de- <br />tectors forUfe safety. When life safety is <br />involved, smoke detectors MUST also be <br />used. Detectors must cHOT be painted. <br /> <br />Batterybaclcup: Heatdetectors should <br />be electronically supervised with battery <br />backup at the panel. <br /> <br />Rate-ot-rise mechanism: The rate-of- <br />rise mechanism may be subject to re- <br />duced sensitivity over time. Annual test- <br />ing of the rate-of-riseoperation is recom- <br />mended. <br /> <br />ELECTRICAL RATINGS <br />. 6-125 Volts AC, 3.0 Amp. <br />. 6-28 Volts DC, 1.0 Amp. <br />" 125 Volts DC, 0.3 Amp. <br />. 250 Volts DC, 0.1 Amp. <br />
The URL can be used to link to this page
Your browser does not support the video tag.