<br />D343 <br /> <br />Air Duct Smoke Detector Housing <br /> <br />. Specifications <br /> <br />Features <br /> <br />. D343 for Multiplex Bus loops <br />. Ph'?toelectric Models <br />. Alarm and Auxiliary Relay Contacts <br />. For Ducts 12 in. (30.5 em) to 10 ft. (3 m) <br />. 300 to 4000 ftJmin (1.52 to 20.3 m1sec) Air Velocity <br />. Easy Duct tube installation through the housing, cuts <br />installation time. <br />. Detector Test and Reset wit!:lQut removing covers <br />. Clear cover allows quick visual inspection <br />. Tube Filters and dust immune smoke detector reduce <br />maintenance <br />. Easy Disassembly for Cleaning <br />. UL, ULC, CSFM Listed <br /> <br />Description <br /> <br />The D343 Air Duct Smoke Detector Housing is designed to <br />mount to the ducts of HVAC systems to monitor the presence <br />of smoke in the conditioned air. It is designed to work with the <br />Radionics D7024 24 VAC Fire Alarm Control/Communicator <br />with the D7039 Multiplexer Expansion Module installed. <br />The efficient housing design samples the air passing through <br />a duct and allows the detection of a potentially hazardous <br />condition. When smoke is detected, the detector sends an <br />alarm signal to the control panel and/or HVAC control <br />equipment which will initiate the necessary action to control <br />air handling systems. <br /> <br />Application <br /> <br />The D343 Air Duct Smoke Detector Housing is designed to <br />operate on a Multiplex Bus loop. <br />The D343 Air Duct Smoke Detector Housing is designed to be <br />used in air handling systems with ducts between 1 foot (30.5 <br />em) and 10 ft. (3.05 m) wide having air velocities between 300 <br />and 4000 ft. per minute (1.52 to 20.3 m/s). <br />System testing may be accomplished by placing an extemal <br />magnet on the detector housing or by switching a signal from <br />a remote test station.(Requires an extemal 24 V supply). <br />The system may be reset by pushing rest at the panel, if using <br />smoke power, or by power down, if using a listed external <br />supply. <br /> <br /> <br />,~~" .i!'~ ~>--:'"''' <br /> <br />"."...,':"'~,: .':':;;;;''i''7''"',%''!!!'"Y..:'lffllillf <br /> <br />II <br /> <br /> <br />o <br /> <br />00 <br /> <br />0. <br /> <br />0343 Air Duct Smoke Detector Housing <br /> <br />Installation <br /> <br />A mounting template, two #10-24 jack nuts, two #10-24 x 1 in. <br />(2.54 em) machine screws, two foam gaskets and two tube <br />damps are provided in the hardware package. The mounting <br />template is affixed to the duct at the desired place and holes <br />are drilled (or punched) and cleaned. The Sampling and <br />Exhaust tubes are inserted into the duct with the Sampling <br />Tube facing into the airflow and the Exhaust Tube downwind <br />from the Sampling Tube. <br />Sample tubes should extend across the width of the duct. <br />Radionics offers sample tubes in three different sizes which <br />may be combined or cut to make other lengths. Sample tubes <br />over 3 ft. (91.4 em) must be supported at the end opposite the <br />duct detector. Sample tubes are provided with an end plug <br />which must be installed in the open end. <br />This detector housing and associated detector head should <br />be installed in accordance with NFPA 9OA: Standard for the <br />Installation d Air Conditioning and Ventilating Systems, NFPA <br />72: National Fire Alann Code", NFPA 101: Life Safety Code", <br />any applicable local and state codes and your local Authority <br />Having Jurisdiction (AHJ). <br /> <br />$ radionics <br /> <br />A member of the <br />Bosch Group <br />