<br />Operational Data <br /> <br />The D1256 and D1257 operate through the Serial Device <br />Interface buss of the controVcommunicators. The D1256 and <br />D1257 receive serial data and power through a four-wire cable. <br /> <br />Both devices continually show the status of the fire alarm <br />system. Changes in the normal panel condition such as alarm <br />or trouble events are displayed in alphanumeric English text <br />and the appropriate sounder response tone emitted. Resetting <br />the display and sounder can only be accomplished at the <br />D1256 Fire Command Center by authorized persons. <br /> <br />Specifications <br /> <br /> ,H :C'~' '~-- "I <br /> ~ ,-' , " f --.''''1''',,, ~l-~.'.' ~l!).f,:;~;'cl'-:;\ <br />" -,;. . ~l.;~ > 4 '_.....:;; _, " __ _ ~' , .. ~: ~~ ~;~:~:: :,~~~ :~i:fJ$~~ <br />Operating Vo.age Nominal 12 VDC <br />(supplied by controVcommunicator) <br />Operating Current 104 mA min.; 206 mA max. <br /> Wiring Four conductors supply: Serial data. <br /> +12 VDC and panel common <br /> Display 16-Character vacuum fluorescent <br />Operating Temperature +32OF to 122"F (OOC to +5O"C) <br />Non-condensing Relative Humidhy 5% to 85% at 860F (3QoC) <br />Base Dimensions (L x W x D) 8.3 in. x 4.5 in. 0.8 in. <br />(21 em x 11.4 em x 2 em) <br /> <br />Wire Information <br /> <br />":'ll'"4-''''":''~~'m!i''''il'1''''J,,",j'~',~''_~ <br />~~~ "~: h ~~ ~~'~~='_~_'~_H':~'~~~>~_lCi~I<~f1i~ <br />12 VDC 12 VDC (Red) <br />Data-Out Data-In (Yelow) <br />Data-In Data-Out (Green) <br />Common Common (Black) <br /> <br />Listings and Approvals <br /> <br />· UL Listed <br />· CSFM Listed <br />· FM Approved <br />Ordering Information <br /> <br /> <br />01256 Fire Command Center <br />01257 Remote FIR! AIann Annunciator <br />D54B Brass Faceplate <br />D54C Stainless Steel Faceplate <br />D55 Desk Stand <br />D56 Conduh Backbox <br /> <br />Specifications <br /> <br />The contractor shall furnish and install, where indicated on the <br />plans, Radionics D1256 Fire Command Center and D1257 <br />Remote Fire Alarm Annunciator. Each device shall have a 16 <br />character vacuum fluorescent display and show all fire system <br />events. Alarms shall be prioritized ahead of other system events <br />and displayed in sequence. The D1257 shall have no on <br />board system control function keys. <br /> <br />A built-in sounder shall indicate events with distinct tones for <br />fire alarm and system trouble. The D1256 and D1257 shall <br />connect to the fire controVcommunicator through a four-wire <br />cable. <br /> <br />The D1256 and 1257 shall be constructed of high impact red <br />plastic. The D1257 shall have the text "Fire Alarm Annunciator" <br />clearly printed in bold letters to the right of the event display. <br /> <br />The D9124, with the D9112LTB, D9112B1 and D7212B1, have <br />a 500 event non-volatile event memory log. The D9124 with <br />the D9112L TB-EX or D9412GL TB, 9000/7000 Series panels <br />have a 1000 event non-volatile memory log. All system events <br />are displayed on system annunciators, printed locally or <br />retrieved from oft premises via the Remote Account Manager <br />(RAM) software package. <br /> <br />.o~o <br /> <br />CERllFICATE NO. A5137 <br /> <br />@ 2001 Radionics, a division of Detection Systems, Inc. <br />@ The Radionics logo is a registered trademark of Radionics, <br />PO Box 80012, Salinas, CA 93912-0012 USA <br />Customer Service: (800) 538-5807 <br /> <br />75-06926-000-B <br />Specifications <br />L643 <br /> <br />01/01 <br />D1256/D1257 <br />Page 2 of 2 <br />