<br /> SPRINKLER FINISH (See Note 7)
<br />K TYPE TEMP, BULB NATURAL I CHROME II WHITE'"
<br /> LIQUID BRASS PLATED POLYESTER
<br /> 135DF/57OC Orange
<br /> PENDENT 155OF/68DC Red
<br /> (TY1231) 1,2,3,5
<br /> and 175OFn9OC Yellow
<br /> UPRIGHT 200oF/93OC Green
<br />2.8 (TY1131) 286OF/141OC Blue
<br />1/2'
<br />NPT 135DF/57OC Orange
<br /> RECESSED 155OF/68DC Red
<br /> PENDENT
<br /> (TY1231)* 175OFn9DC Yellow
<br /> Figure 5 200DF/93OC Green 1,2,5
<br /> 135OF/57OC Orange
<br /> RECESSED 155DF/68OC Red
<br /> PENDENT
<br /> (TY1231)- 175OFn9OC Yellow
<br /> Figure 6 200oF/93OC Green
<br /> 135OF/57OC Orange
<br /> PENDENT 155OF/68OC Red
<br /> (TY2231 )
<br /> and 175OFn9OC Yellow
<br /> UPRIGHT 200oF/93OC Green
<br />4.2 (TY2131) 286OF/141OC Blue
<br />1/2' 1,2
<br />NPT 135OF/57OC Orange
<br /> RECESSED 155OF/68OC Red
<br /> PENDENT
<br /> (TY2231 )* 175OFn9OC Yellow
<br /> Figure 7 200oF/93OC Green
<br /> 135OF/57OC Orange
<br /> RECESSED 155OF/68OC Red
<br /> PENDENT
<br /> (TY2231)- 175OFn9OC Yellow
<br /> Figure 8 200oF/93OC Green
<br />
<br />NOTES:
<br />1, Listed by Underwriters Laboratories. Inc, (UL) as Quick Response Sprinklers.
<br />2, Listed by Underwriters Laboratories, Inc, for use in Canada (C-UL) as Quick Response
<br />Sprinklers.
<br />3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
<br />klers,
<br />5, Approved by the City of New York under MEA 354-01-E.
<br />7, Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
<br />klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
<br />* Installed with Style 10 (1/2* NPT) or Style 40 (3/4' NPT) 3/4' Total Adjustment
<br />Recessed Escutcheon, as applicable.
<br />.. Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2' Total Adjustment
<br />Recessed Escutcheon, as applicable.
<br />... Frame and Deflector only. Listings and approvals apply to color (Special Order),
<br />N/A: Not Available
<br />
<br />TABLE A
<br />LABORA TORY LISTINGS AND APPROVALS
<br />2.8 AND 4,2 K-FACTOR SPRINKLERS
<br />
<br />held horizontally, a small air bubble
<br />should be present. The diameter of the
<br />air bubble is approximately 1/16 inch
<br />(1.6 mm) for the 1350F/57"C to 3/32
<br />inch (2,4 mm) for the 2860F/1410C
<br />temperature ratings,
<br />
<br />A leak tight 1/2 inch NPT sprinkler joint
<br />should be obtained with a torque of 7
<br />to 14 ft.lbs. (9.5 to 19,0 Nm). A maxi-
<br />mum of 21 ft. Ibs. (28,5 Nm) of torque
<br />may be used to install sprinklers with
<br />1/2 NPT connections. A leak tight 3/4
<br />
<br />TFP17,1
<br />
<br />inch NPT sprinkler joint should'be ob-
<br />tained with a torque of 10 to 20 ft.lbs,
<br />(13,4 to 26,8 Nm). A maximum of 30
<br />fUbs. (40,7 Nm) of torque is to be used
<br />to install sprinklers with 3/4 NPT con-
<br />nections. Higher levels of torque may
<br />distort the sprinkler inlet and cause
<br />leakage or impairment of the sprinkler.
<br />
<br />Do not attempt to make-up for insuffi-
<br />cient adjustment in the escutcheon
<br />plate by under- or over-tightening the
<br />sprinkler. Readjust the position of the
<br />sprinkler fitting to suit,
<br />
<br />The Series TV -FRS Pendent and Up-
<br />right Sprinklers must be installed in
<br />accordance with the following instruc-
<br />tions.
<br />
<br />Step 1. Pendent sprinklers are to be
<br />installed in the pendent position, and
<br />upright sprinklers are to be installed in
<br />the upright position.
<br />
<br />Step 2. With pipe thread sealant ap-
<br />plied to the pipe threads, hand tighten
<br />the sprinkler into the sprinkler fitting.
<br />
<br />Step 3. Tighten the sprinkler into the
<br />sprinkler fitting using only the W- Type
<br />6 Sprinkler Wrench (Ref. Figure 13).
<br />With reference to Figures 1, 2, 3, and
<br />4, the W- Type 6 Sprinkler Wrench is to
<br />be applied to the sprinkler wrench
<br />flats.
<br />
<br />The Series TV-FRS Recessed Pen-
<br />dent Sprinklers must be installed in
<br />accordance with the following instruc-
<br />tions.
<br />
<br />Step A. After installing the Style 10.
<br />20, 30, or 40 Mounting Plate, as appli-
<br />cable, over the sprinkler threads and
<br />with pipe thread sealant applied to the
<br />pipe threads, hand tighten the sprin-
<br />kler into the sprinkler fitting.
<br />
<br />Step S. Tighten the sprinkler into the
<br />sprinkler fitting using only the W- Type
<br />7 Recessed Sprinkler Wrench (Ref.
<br />Figure 14). With reference to Figure 1,
<br />2, 3, and 4, the W-Type 7 Recessed
<br />Sprinkler Wrench is to be applied to
<br />the sprinkler wrench flats.
<br />
<br />Step C. After the ceiling has been in-
<br />stalled or the finish coat has been ap-
<br />plied, slide on the Style 10, 20, 30, or
<br />40 Closure over the Series TV-FRS
<br />Sprinkler and push the Closure over
<br />the Mounting Plate until its flange
<br />comes in contact with the ceiling,
<br />
|