<br />Grinnell Grooved Fire Protection Products
<br />Figure 705
<br />Flexible Coupling
<br />General
<br />Description
<br />
<br />
<br />[LPC8]
<br />[VdS)
<br />
<br />
<br />I"fiL' ~ See Fire Protection
<br />\!.Y~~ Submittal Sheet for
<br />~ Pressure Rating and
<br />Listing/Approvallnformation
<br />
<br />The Figure 705 Flexible Coupling is capable of
<br />pressures up to 300 psig (2068 kPa) depending
<br />on pipe size and wall thickness when used in fire
<br />protection services, It provides a dependable
<br />method of joining pipe and is suitable for use in
<br />a variety of applications.
<br />Rigid Couplings are recommended lor dry pipe
<br />and freezer applications.
<br />WARNING
<br />The Figure 705 Aexible Coupling described herein
<br />must be installed and maintained in compliance
<br />with this document, as well as with the applicable
<br />standards of the National Fire Protection
<br />Association, in addition to the standards of any
<br />other authorities having jurisdiction. Failure to do
<br />so may impair the performance 01 this device.
<br />The owner is responsible for maintaining their
<br />fire protection system and devices in proper
<br />operating condition. The installing contractor or
<br />sprinkler manufacturer should be contacted with
<br />any questions.
<br />
<br />Technical
<br />Data
<br />
<br />Figure: 705
<br />Sizes: 1W' -12"
<br />Approvals: UL, FM, ULC, VdS, and LPCB;
<br />See Fire Protection Submittal Sheet for exact
<br />Listing / Approval information.
<br />Housing: Ductile iron conforming to
<br />ASTM A-536, Grade 65-45-12
<br />
<br />Page 1 of 2
<br />
<br />Protective Coatings:
<br />· Non-lead orange paint
<br />. Fire brigade red (optional) non-lead paint
<br />. Hot dipped galvanized conforming to ASTM
<br />A-153
<br />BolVNuts: Track Head Bolts - conforming to
<br />ASTM A-183, Zinc Plated, (Min. Tensile =
<br />110,000 psi/758,422 kPa)
<br />Metric - conforming to ASTM F568M
<br />Gasket: (specify when ordering)
<br />. Grade "An EPDMA violet color code
<br />ambientto + 1500F (+660C) for fire protection
<br />systems, Not recommended for hot water
<br />systems,
<br />· Tri-seal (Grade "E" EPDM), greencolorcode.
<br />. Prelubricated (Grade "An EPDMA)
<br />(See Data Sheet TFP1S9S for aid in selecting
<br />proper gasket)
<br />
<br />Ordering
<br />
<br />Procedure
<br />
<br />When placing an order, indicate the full product
<br />name, Please specify the quantity, figurenumber,
<br />type of gasket, Grade "A" EPDMA, Prelubricated
<br />(Grade "A" EPDMA) or Grade "En EPDM Tri-Seal,
<br />and size.
<br />Grinnell Grooved Piping Products, valves,
<br />accessories and other products are available
<br />throughoutthe U.S., Canada, and internationally,
<br />through a network of distribution centers. You
<br />may write directly or call 215-362-0700 for the
<br />distributor nearest you.
<br />
<br />Care and
<br />Maintenance
<br />
<br />The owner is responsible for the inspection,
<br />testing, and maintenance of their fire protection
<br />system and devices in accordance with the
<br />applicable standards ofthe National Fire Protection
<br />Association (e,g" NFPA 25), in addition to the
<br />standards of any authority having jurisdiction,
<br />The installing contractor or product manufacturer
<br />should be contacted relative to any questions.
<br />Any impairment must be immediately corrected.
<br />
<br />July 2004
<br />
<br />It is recommended that automatic sprinkler
<br />systems be inspected, tested, and maintained by
<br />a qualified Inspection Service.
<br />
<br />Limited
<br />
<br />Warranty
<br />
<br />Products manufactured by Tyeo Rre Products are
<br />warranted solely to the original Buyer for ten '(1 O)
<br />years against defects in material and workmanship
<br />when paid for and properly installed and maintained
<br />under normal use and service. This warranty will
<br />expire ten (1 O) years from date of shipment by Tyco
<br />Rre Products. No warranty is given for products or
<br />components manufactured by companies not
<br />affiliated by ownership with T yeo Rre Products orfor
<br />products and components which have been subject
<br />to misuse, improperinstaJlation, corrosion, orwhich
<br />have not been installed, maintained, modified or
<br />repaired in accordance with applicable Standards of
<br />the National Rre Protection Association (NFPA),
<br />and/or the standards of any other Authorities Having
<br />Jurisdiction. Materials found by Tyco Fire Products
<br />to be defective shaff be either repaired or replaced, at
<br />Tyco Rre Products' sole option. Tyco Rre Products
<br />neither assumes, nor authorizes any person to
<br />assumeforit,anyotherobligation in connection with
<br />the sale of products or parts of products. Tyco Rre
<br />Products shall notbe responsibleforsprinkfersystem
<br />design errors or inaccurate or incomplete information
<br />supplied by Buyer or Buyer's representatives.
<br />IN NO EVENT SHALL TYCO FIRE PRODUCTS BE
<br />LIABLE, IN CONTRACT, TORT. STRICT LIABILITY
<br />OR UNDER ANY OTHER LEGAL THEORY, FOR
<br />INCIDENTAL, INDIRECT, SPECIAL OR
<br />CONSEQUENTIAL DAMAGES, INCLUDINGBlJfNOT
<br />LIMITED TO LABOR CHARGES, REGARDLESS OF
<br />WHETHERTYCOAREPRODUCTSWASINFORMED
<br />ABOUT THE POSSIBILITY OF SUCH DAMAGES
<br />AND IN NO EVENT SHALL TYCO FIRE PRODUCTS:
<br />LIABILITY EXCEED AN AMOUNT EQUAL TO THE
<br />SALES PRICE.
<br />THE FOREGOING WARRANTY IS MADE IN liEU OF
<br />ANY AND AU O77IER WARRANTIES EXPRESS OR
<br />IMPLIED. INCLUDING WARRANTIES OF
<br />MERCHANTABILITY AND FITNESS FOR A
<br />PARTICUlAR PURPOSE.
<br />
<br />TFP1820
<br />
|