<br />TIME DELAY WIRING INSTRUCTION <br /> <br />*NOTE: <br /> <br />TO MEET NEC AND U,L. LISTING YOU MUST USE CLASS 1 WIRE TO <br />MAKE CONNECTIONS IN THE JUNCTION BOX. <br /> <br />THE RED AND BLUE WIRES MUST BE CONNECTED TO THE 24 <br />VOLT FIRE ALARM SYSTEM, OR THE 110 VOLTS MUST BE RAN TO <br />THE RELAY AT THE ALARM PANEL. EITHER WAY, THE TIME <br />DELAY MUST DROP OUT WHEN THE FIRE ALARM SOUNDS. <br /> <br />JUNCTION BOX <br /> <br />BLUE TO - 24V DC <br />RED TO + 24V DC <br />WHITE TO IIOV <br />BLACK TO IIOV <br />GREEN TO GROUND <br /> <br />-, <br /> <br />**Junction Box is located on top of the White Control Box** <br /> <br />**Onlv when Red and Blue wires are connected to 24-volt rU'e alarm system. Once the two <br />wires are connected you MUST remove the two pull jumpers on the PC Board inside the Control <br />Box. (R47 & R48 above and below the relay), This allows the 15 second delay to drop out when <br />the fire alann sounds. If the resisters are not removed the delay will not drop out which is <br />against all Fire Codes. ** <br /> <br />~ <br /> <br />I <br />~ <br />