My WebLink
|
Help
|
About
|
Sign Out
Browse
Search
09-9948
Zephyrhills
>
Building Department
>
Permits
>
2009
>
09-9948
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
1/11/2011 11:10:32 AM
Creation date
1/11/2011 11:10:29 AM
Metadata
Fields
Template:
Building Department
Company Name
DRIFTWOOD
Building Department - Doc Type
Permit
Permit #
09-9948
Building Department - Name
BLISS,GLENDA
Address
38336 COTTONWOOD PL
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
22
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
DEC -16 -2009 16:19 P.07 <br /> 4 <br /> 70448.01- 1o9 -a7 <br /> • <br /> Architectural Testing Page 5 of9 • <br /> ` S <br /> Test Results: The results are tabulatedas follows: <br /> Paragraph Title of Test - Test Method Results Allowed <br /> Test Specimen #1: H -R30 1219 x 2286 (48 x 90) (Flange) <br /> 5.3.1 OperatingForoe per ASTM E 2068 <br /> Initiate motion 76 N (17 lbf) report Only , • <br /> Maintain motion 89 N (20 lbf) 133 N (30 lbf) <br /> 5.3.2.1 Air Leakage Resistance per ASTM E 283 <br /> 75, Pa (1.6 psf) 0.86 L/s /m '1.5 L /s/m <br /> (0,17 cfm/ft (0.3'afrra/ft max.) <br /> Note #x: The tested specimen meets (or exceeds) the performance levels specified in <br /> AAMA/✓< DMA /OSA 101a 5.2/4440 -05 for air leakage resistance. , <br /> 5.3.3 Water Penetration Resistance per ASTM E 547 See Note #2 <br /> 5.3.4.2 Uniform Load Deflection per ASTM E 330 See Note #2 <br /> 5.3.4.3 Uniform Load Stractiaral per ASTM E 330 See Note #2 <br /> Note #2: The client opted to start at a pressure higher than the minimum' required. Those <br /> results are listed under "Optional' Performance". <br /> 5.3.5 Forced Entry E esistazwe per ASTIvl F 588 <br /> • <br /> Type: A Grade: 10 <br /> Disassembly Test No entry No entry , <br /> Test Al through A7' No entry s No entry <br /> Lock Hardware Manipulation Test No entry No entry <br /> Sash Manipulation Test No entry No entry <br /> 5.3.6.3 Daglazing Test <br /> 1n,operating direction - 320 N (70 lbs) <br /> Interior meeting rail 3.8 mm (0.15 ") 11.4 RIM (0.45") <br /> Bottom rail 3.6 mm (0.14 ") 114 mm (0.45 ") • <br /> • <br />
The URL can be used to link to this page
Your browser does not support the video tag.