Laserfiche WebLink
ONLY HAND OPERATED COMPACTION EQUIPMENT SHALL BE ALLOWED <br /> WITHIN 5 FEET OF THE BACK SURFACE OF THE ANCHOR UNITS. HEAVY <br /> CONSTRUCTION EQUIPMENT SHALL NOT BE ALLOWED WITHIN THIS <br /> DISTANCE. <br /> BACKFILL SHALL BE PLACED FROM THE WALL REARWARD INTO THE <br /> EMBANKMENT TO INSURE THAT THE GEOGRID REMAINS TAUT. <br /> TRACK MOUNTED CONSTRUCTION EQUIPMENT SHALL NOT BE OPERATED <br /> DIRECTLY ON THE GEOGRID. A MINIMUM BACKFILL THICKNESS OF 6 INCHES IS <br /> REQUIRED PRIOR TO OPERATION OF TRACK MOUNTED VEHICLES OVER THE <br /> GEOGRID. TURNING OF TRACK MOUNTED VEHICLES SHOULD BE KEPT TO A <br /> MINIMUM TO PREVENT TRACKS FROM DISPLACING THE FILL AND DAMAGING THE <br /> GEOGRID. <br /> RUBBER TIRED EQUIPMENT MAY PASS OVER THE GEOGRID AT SLOW SPEED, LESS <br /> THAN 10 MPH. SUDDEN BRAKING AND SHARP TURNING SHALL BE AVOIDED. <br /> CAP UNIT: <br /> DIAMOND -PRO CAPS TO BE ATTACHED USING ADHESIVE. <br /> CONSTRUCTION TOLERANCES: <br /> VERTICAL CONTROL: <br /> + 1.25 INCHES OVER A 10 FOOT DISTANCE <br /> HORIZONTAL LOCATION CONTROL: <br /> STRAIGHT LINES: + 1.25 INCHES OVER A 10 -FOOT DISTANCE <br /> STRAIGHT AND RADIUS CORNER LOCATION: + 1.0 FOOT <br /> CURVES AND SERPENTINE RADIUS: + 2.0 FOOT <br /> ROTATION: <br /> FROM ESTABLISHED PLAN WALL BATTER: 2.0 DEGREES <br /> MAXIMUM, + 10 % FROM TOTAL ESTABLISHED HORIZONTAL SETBACK <br /> BULGING: <br /> 1.25 INCH OVER A 10 FOOT DISTANCE <br /> TREE PLANTING: <br /> CONTACT WALL INSTALLER PRIOR TO PLANTING ANY LANDSCAPING ADJACENT <br /> TO WALL, TO AVOID DAMAGE TO THE GEOGRID. <br /> WALL LAYOUT: <br /> WALL SHALL BE LAID OUT BY GENERAL CONTRACTOR PRIOR TO START OF <br /> INSTALLATION. <br /> w: \bpatel \let- notes \p - 6425 -note. doc <br />