Wiring Diagrams (for all models)
<br /> MT SIGNAL AUDIBLE SIGNAL AND STROBE AUDIBLE SIGNAL AND STROBE OPERATE
<br /> • •
<br /> OPERATE INDEPENDENTLY IN UNISON. RED AND BLACK SHUNT-WIRES
<br /> ARE SUPPLIED.
<br /> racer '`' +p ro ■ ,,
<br /> carJ '"' - - + :i%�c momo
<br /> APOLSTZGE•C gm LOW .
<br /> °c v�urx¢r.: n n Tax MscM:�o PRECEDING.: ` += TO NEXT:. NEXT:. aa- ivs� -■a. Ii / A MGC.� II MUG ■ ..c. -�. �C F +•� APPI IANGE� _ R EO '
<br /> pi:c; .0 n.un, -eN ' - C 119.1111 ' OR RAMC
<br /> .oc I
<br /> SXCMnLC ° *:
<br /> dfnkti'
<br /> STROBE: AOOXELLJ ■rb.ru a,wi,
<br /> Specifications and Ordering Information
<br /> Model Order Input Rated . Mounting Agency Approvals
<br /> Number Code Voltage .Candela Options*" UL MEA CSFM FM BFP
<br /> MT 12/24 -R 5023 12/24 - D,E,F,L,M,O,P,R X X X X X
<br /> MT 12/24 -W 5024 12/24 - D,E,F,L,M,O,P,R X X • X X X
<br /> MT 241575W -FR° 8422 24 15 (75 on AXIS) D,E,F L,M,O,P,R X X X X *
<br /> MT 24MCW -FR 3301 :24 15/30/75/110 D,E,F,L,M,O,P,R X * X * *
<br /> MT24MCW -FW 3303 24 15/30/75/110 D,E,F,L,M,O,P,R X X *
<br /> MT 121575W FR" 8421 12 15 (75 on AXIS) D,E,F,L,M,O,P,R X X X X *
<br /> MT- 121575W -NW 9747 12 15 (75 on AXIS) D,E,F,L,M,O,P,R X X _ X X
<br /> MTWP- 2475W --FR— 8420 24 180 Qa 77 °F (25 °C) M X X X X *
<br /> MTNP- 2475W -NW'* 9744 24 180 0 77°F (25 °C) M X X X X
<br /> MT4 -115 -R 6223 120 VAC - D,E,J,K,N.O,R X X X X X
<br /> MT4 -115 -S 6142 120 VAC - D.E,J,K.N,O,R X X X X X
<br /> MT4- 115- WH -VFR@ 6224. 120 VAC 15 D,E,J,K,N,O,R X X X X X
<br /> MT4- 12/24 -R 5308 12/24 - D,E,J,K,N 0 R X * * * *
<br /> MT4- 12/24 -5 7997 12/24 - D,E,J.K,N,O,R X * • * *
<br /> NOTE: **MTWP -2475W ie Weatherproof and rated for 180 cd la 77 °F (25 °C): See Data Sheet S9004 or Installation Instruction P84150.
<br /> ***For additional information on mounting please refer to Data Sheet S7000.
<br /> # 1575 strobes are UL Listed for 15cd with 75cd on AXIS. *Pending
<br /> ## Series WH Strobe is listed for UL Standard 1638 only. See Instruction Sheet P83160.
<br /> •
<br /> 41ARNINO: CONTACT WHEELOCK FOR THE CURRENT "INSTALLATION INSTRUCTIONS" P82467 MT- 12124, P84155 MT w/Strobe
<br /> P84150 MTWP WEATHERPROOF "GENERAL INFORMATION" SHEET (P82380) ON THESE PRODUCTS. THESE DOCUMENTS DO
<br /> UNDERGO PERIODIC CHANGES :IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE
<br /> MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE
<br /> PRODUCTS, INCLUDING:
<br /> • TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES.
<br /> • FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON
<br /> THOSE CIRCUITS.
<br /> • COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW.
<br /> • THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR RATED INPUT VOLTAGE RANGE.
<br /> • INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES.
<br /> • USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBE ON
<br /> CODED OR INTERRUPTED CIRCUITS IN WHICH THE APPUED VOLTAGE IS CYCLED ON AND OFF AS THE STROBE MAY
<br /> NOT FLASH. 7
<br /> • FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT
<br /> IN IMPROPER INSTALLATION, APPLICATION, AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY
<br /> SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS.
<br /> • CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND
<br /> INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS.
<br /> Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated,
<br /> maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a
<br /> year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation,
<br /> operation. maintenance and testing must be performed by qualified personnel for proper operation In accordance with all of the Latest
<br /> National Fire Protection Association (NFPA), Underwriters' Laboratories (UL), National Electrical Code (NEC), Occupational Safety and
<br /> Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines,
<br /> regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority
<br /> having jurisdiction (AHJ).
<br />
|