Laserfiche WebLink
G310A -A <br /> Page 6 Revised February 20, 2007 <br /> SENSOR ASSEMBLY (P /N G305) <br /> The sensor assembly, which is temperature activated, consists of two (2) metal housed detector assemblies with two <br /> (2) different wire lengths. Sensor one (1) is 30" long (PIN G305 -1) sensor two (2) is 54" long (P/N G305 -2). (See <br /> FIGURE 4) <br /> Temperature <br /> Temperature Sensor <br /> Sensor (P /N G305 -2) <br /> 0 (P /N G305 -1) <br /> ♦ ' <br /> t ' fi r 015,,,, �,..:� fib <br /> t �, �. Tee ( P ! N G304•E} L -1041I <br /> 4, 1 t (PIN (5304-D) t <br /> Oui ck Connect 'Olt _ Distribution Assy. Olt <br /> Nozzle (P /N 0304•F( <br /> FIGURE 4 <br /> DISTRIBUTION ASSEMBLY (P /N G304-A) <br /> The distribution assembly consist of two (2) Teflon lined Note: <br /> stainless steel braided hoses and two (2) magnetic based Magnetic base with tee assembly shall be on <br /> adjustable nozzle assemblies. The hose assembly from the the same side of the range hood as the <br /> extinguisher has a length variation of 22 "- 30 ". In addition, system enclosure, i.e., if the magnetic base <br /> the hose assembly between the nozzles ranges in length with "T" is installed on the left side of the <br /> from 27 " - 36 ". range hood, enclosure shall be mounted <br /> inside the cabinetry above the range hood on <br /> The assembly is installed on the underside of the range the far left side or vice versa for the right <br /> hood connecting to the hose from the cylinder extending side. (See FIGURE 4) <br /> through the 7/8" hole via the quick connect fitting to the <br /> tee. One magnetic base nozzle assembly is placed on each <br /> under portion of the range hood, left and right. <br />