Laserfiche WebLink
Chapter 3 - System Design <br /> Page 3 -11 <br /> REV. 3 <br /> Detector Placement <br /> Thermal detectors are required in all hazard areas protect- A temperature survey must be performed to determine the <br /> ed by the PYRO -CHEM Open Face Paint Spray Booth ■ maximum ambient temperature of the hazard survey. See <br /> Industrial Fire Suppression System if automatic system Temperature Chart in Chapter 2 - Components. <br /> operation is required. Either mechanical or electrical ther- <br /> mal detectors can be used for automatic system operation. TOTAL FLOODING (DETECTOR SPACING) - FUSIBLE <br /> Mechanical detectors (fusible links) are used in conjunction LINKS <br /> with the PYRO -CHEM Models MCH3 and NMCH3 control Ceiling Height Spacing <br /> devices. Electrical detectors are used in conjunction with Up to 14 ft. (4.2 m) 10 ft. (3.0 m) maximum <br /> the PYRO -CHEM Models ECH3 -24 and ECH3 -120 Control Height detectors <br /> Heads. <br /> 5 ft. (1.5 m) max. from a wall* <br /> 100 sq. ft. (9.2 sq. m) max. coverage <br /> TOTAL FLOODING (DETECTOR SPACING) - THERMAL per detector <br /> Ceiling Height Spacing Greater than 8 ft. (2.4 m) max. between detectors <br /> Up to 14 ft. (4.2 m) 15 ft. (4.5 m) maximum 14 ft. (4.2 m) up to <br /> Height between detectors 20 ft. (6.1 m) height 4 ft. (1.2 m) max. from wall <br /> 7 ft. 6 in. (2.3 m) max. from wall 64 sq. ft. (5.9 sq. m) max. coverage <br /> 225 sq. ft. (20.9 sq. m) max. per detector <br /> coverage per detector NOTE: For sloped ceiling (peaked type or shed type) <br /> Greater than 13 ft. (3.9 m) maximum installations, refer to NFPA -72, "National Fire Alarm Code" <br /> 14 ft. (4.2 m) between detectors for detailed spacing requirements. <br /> up to 20 ft. 6 ft. 6 in. (1.9 m) max. from wall LOCAL APPLICATION - OVERHEAD (DETECTOR SPAC- <br /> (6.1 m) height 169 sq. ft. (15.7 sq. m) max. ING) - Maximum spacing per fusible link detector is 36 ft. <br /> coverage per detector (3.3 m or 3 ft. (.9 m) from edge of hazard and 6 ft. (1.8 m) <br /> Greater than 11 ft. (3.4 m) max. between fusible link detectors. <br /> 20 ft. (6.9 m) between detectors When a detector(s) is mounted more than 1 ft. (.3 m) below <br /> up to 24 ft. (7.3 m) 5 ft. 6 in. (1.7 m) max. from wall ceiling or in an open area, heat trap(s) is recommended. <br /> 121 sq. ft. (11.2 sq. m) max. Detectors should be mounted overhead at nozzle height or <br /> coverage per detector as close to the hazard as possible without interference, not <br /> Greater than 9 ft. (2.7 m) max. to exceed 10 ft. (3 m). <br /> 24 ft. (7.3 m) between detectors Detectors should not be located where they will be suscep- <br /> up to 30 ft. (9.1 m) 4 ft. 6 in. (1.4 m) max. from wall tible to damage during the normal work operation. <br /> 81 sq. ft. (7.5 sq. m) max. LOCAL APPLICATION - TANKSIDE (DETECTOR SPAC- <br /> coverage per detector ING) - Detectors can be located either near the inner tank <br /> NOTE: For sloped ceiling (peaked type or shed type) wall and flammable liquid surface or above the tank. If locat- <br /> installations, refer to NFPA -72, "National Fire Alarm Code" ed above the tank, the rules for local application overhead <br /> for detailed spacing requirements. would apply. If located on the tank wall, the detectors can be <br /> LOCAL APPLICATION - OVERHEAD (DETECTOR mounted horizontally or vertically in the freeboard area but <br /> SPACING) - Maximum spacing per detector is 100 ft.2 must be protected from damage during normal working <br /> (9.3 m or 5 ft. (1.5 m) from edge of hazard and 10 ft. operation. Detectors should be located at a maximum spac- <br /> (3.1 m) between detectors. When detectors are mounted ing per detector of 3 ft. (.9 m) from edge of hazard and 6 ft. <br /> below the ceiling in an open area, heat traps are recom- (1.8 m) between detectors on the long side of the tank. <br /> mended. *For 14 ft. (4.3 m) wide booths with maximum height of 12 ft. (3.7 m), the <br /> LOCAL APPLICATION - TANKSIDE (DETECTOR SPAC- detector location off the side wall can be a maximum of 7 ft. (2.1 m). <br /> ING) - Detectors can be located either near the inner tank <br /> wall and flammable liquid surface or above the tank. If locat- <br /> ed above the tank, the rules for local application overhead <br /> would apply. If located on the tank wall, the detectors can be <br /> mounted horizontally or vertically in the freeboard area, but <br /> must be protected from damage during normal working <br /> operations. The maximum spacing per detector is 5 ft. <br /> (1.5 m) from edge of hazard and 10 ft. (3.1 m) between <br /> detectors. <br /> ULEX 3437 CEx732 <br /> September 1, 2006 <br />