Laserfiche WebLink
Chapter 3 - System Design <br /> Page 3 -17 <br /> REV. 1 <br /> Step No. 4 Total all pipe lengths. Refer to the Volume Refer to Volume Chart. The pipe size chosen is <br /> Chart. Chose a given pipe size and multiply the 3/8 inch. The volume per foot of 3/8 in. pipe is <br /> ml per foot by the total length of all the pipe. If 37.5 ml. Multiply 37.5 by the total pipe length of <br /> the sum falls within the acceptable range noted 47.5 ft. <br /> in Tank Chart, that pipe size Is acceptable. If <br /> the calculated volume is too large, recalculate 37.5 ml x 47.5 ft. = 1781 ml total volume <br /> the volume using the ml per foot of a smaller The maximum volume allowed for a PCL -300 is <br /> pipe size. See Figure 3 -21. 1910 ml, therefore, 3/8 in. pipe is acceptable for <br /> Add section A -B = 0' -6" + 5' + 14' + 2' + 0' -6" = this system. <br /> 22' (.2 +1.5 +4.3 +.6 +.2 = 6.8 m) <br /> Add section B -C = 1' -6" (.5 m) <br /> Add section C -D = 1' (.3 m) <br /> Add section D -E = 2' (.6 m) <br /> Add section E -F = 0' -6" (.2 m) <br /> Add section F -L = 3' + 2' + 2" = 7' (2.1 m) <br /> Add section B -G = 0' -6" (.2 m) <br /> Add section C-H = 2' + 2' = 4' (.6 +.6 = 1.2 m) <br /> Add section D -I = 2' + 2' = 4' (.6 + .6 = 1.2 m) <br /> Add section E -J = 0' -6" + 0' -6" = 1' (.3 m) <br /> Add section F -K = 2' + 2' = 4' (.6 + .6 = 1.2 m) <br /> Total length of all pipe = 47' -6" (14.5 m) <br /> 6' <br /> a D 110. <br /> C 1 \ <br /> 1,01 1-6 2 ' E <br /> 2' <br /> 14' <br /> 2 <br /> G <br /> 6 <br /> 0 <br /> A 0 <br /> 0 <br /> 1 <br /> • OOfi19]PC <br /> Figure 3 -21. <br /> ULEX 3830 <br /> PN551274(2) April 1, 2004 <br />