Laserfiche WebLink
CCSM Office <br /> From: "Kerry Banter <kbamett@fire.zephyrhills.fl.us> <br /> To: "CCSM Office" <ccsm @tampabay.rr.c:om> <br /> Sent: Wednesday, June 02, 2010 2:51 PM <br /> Subject RE: Fung Garden Chinese Restaurant <br /> Steve, <br /> Thanks for getting with me. You would be correct for the most part. I believe everything should be scheduled to keep her <br /> from being down long. The fire barrier /enclosure that surrounds the duct needs to be taken out. Then everything should <br /> be cleaned by the hood cleaner. Any tiles that need to be replaced also should be done. I want to make sure we get rid of <br /> the grease build up in, around and behind the duct in the ceiling area. Once that is complete the pan can be installed on <br /> the curb to route the grease in the right direction. The duct then can be wrapped versus a new barrier being installed. As <br /> for the fan unit, some new hinges and a proper grease cup shall be installed. Please be advised a permit will be required to <br /> complete this work. Submit a plan showing scope of work. If you have any questions, please let me know. <br /> Kerry Barnett <br /> Fire Marshal <br /> 6907 Dairy Rd <br /> Zephyrhills, FL. 33545 <br /> (813) 780-0041 <br /> CELL: (813) 813-714-6326 <br />