Page 2 of 6 TFP161
<br /> SPRINKLER FINISH (See Note 10)
<br /> K TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD WAX WAX OVER
<br /> LIQUID BRASS PLATED POLYESTER COATED COATED LEAD COATED
<br /> 135 °F /57 °C Orange
<br /> HORIZ. 155 °F /68 °C Red
<br /> SIDEWALL 1, 2, 3, 4, 9 1, 2, 3, 9 1, 2, 3, 9 1, 2, 3, 9 1, 2, 3, 9
<br /> (TY3351) 175 °F /79 °C Yellow
<br /> 200 °F /93 °C Green
<br /> 5.6 286 °F /141 °C Blue 1**, 2 ** 3 ** 9 ** 1**, 2 ** 3 ** 9 **
<br /> 1/2"
<br /> NPT 360F/182°C Mauve 1, 2, 4, 9 1, 2, 9 N/A
<br /> RECESSED 135FI57°C Orange
<br /> HORIZ. 155 °F /68 °C Red
<br /> SIDEWALL 1, 2, 3, 9
<br /> N/A
<br /> (TY3351)* 175 °F /79 °C Yellow
<br /> Figure 3 200F/93°C Green
<br /> 135 °F /57 °C Orange
<br /> VERTICAL 155FI68°C Red
<br /> 5.6 SIDEWALL 4,5,6,7,8,9 5,6,7,9 5,6,7,9 5,6,7,9
<br /> 1/2" (TY3451) 175 °F /79 °C Yellow
<br /> NPT Installed 200 °F /93 °C Green
<br /> Pendent -
<br /> or 286 °F /141 °C Blue 5 ** 6 ** 7 ** 9 ** 5 ** 6 ** 7 ** 9 **
<br /> Upright 360F/182°C Mauve 4, 5, 6, 8, 9 N/A
<br /> NOTES:
<br /> 1. Listed by Underwriters Laboratories, Inc. (UL) for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm)
<br /> top of deflector to ceiling distance.
<br /> 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) for use in Light and Ordinary Hazard Occupancies at a 4 to 12
<br /> inch (100 to 300 mm) top of deflector to ceiling distance.
<br /> 3. Approved by Factory Mutual Research Corporation (FM) for use in Light Hazard Occupancies at a 4 to 12 inch (100 to 300 mm)
<br /> top of deflector to ceiling distance.
<br /> 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05 & 007k/03) at a 4 to.6 inch (100 to 150 mm) deflector
<br /> to ceiling distance.
<br /> 5. Listed by Underwriters Laboratories, Inc. (UL) for use in Light and Ordinary Hazard Occupancies.
<br /> 6. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL:) for use in Light and Ordinary Hazard Occupancies.
<br /> 7. Approved by Factory Mutual Research Corporation (FM) for use in Light Hazard Occupancies.
<br /> 8. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05 & 007k/03).
<br /> 9. Approved by the City of New York under MEA 354 -01 -E.
<br /> 10. Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C -UL Listed,
<br /> the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead
<br /> Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers.
<br /> * Installed with Style 10 (1/2" NPT) 3/4" Total Adjustment Recessed Escutcheon.
<br /> ** 150 °F /66 °C Maximum Ceiling Temperature.
<br /> * ** Frame and deflector only. Listings and approvals apply to color (Special Order).
<br /> TABLE A
<br /> LABORATORY LISTINGS AND APPROVALS
<br /> Physical Characteristics
<br /> Frame Bronze Operation Design
<br /> Button Brass /Copper
<br /> Sealing Assembly The glass Bulb contains a fluid which Criteria
<br /> Beryllium Nickel w/Teflont expands when exposed to heat. When
<br /> Bulb Glass the rated temperature is reached, the The Series TY -B Horizontal and Verti-
<br /> Compression Screw Bronze fluid expands sufficiently to shatter the cal Sidewall Sprinklers are intended
<br /> HSW Deflector Bronze glass Bulb, allowing the sprinkler to for fire protection systems designed in o
<br /> VSW Deflector Copper activate and water to flow. accordance with the standard installa- '
<br /> tion rules recognized by the applicable a
<br /> Patents Listing or Approval agency (e.g., UL -'
<br /> U.S.A. 5,810,263 Listing is based on the requirements of
<br /> NFPA 13, and FM Approval is based o:
<br /> on the requirements of FM's Loss Pre- o
<br /> vention Data Sheets). Only the Style a
<br /> 10 Recessed Escutcheon is to be used o
<br /> for recessed horizontal installations.