Laserfiche WebLink
tqcci I Fire & Building <br /> Products <br /> Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 <br /> Model ESFR -25 <br /> Early Suppression Fast Response Pendent Sprinklers <br /> 25.2 K- factor <br /> General ing or eliminating the need for a sys- <br /> tem fire pump. Also, the Model ESFR - <br /> 25 permits use of a maximum deflec- <br /> Description for -to ceiling distance of 18 inches <br /> (460 mm) versus 14 inches (360 mm); <br /> The Model ESFR -25 Pendent Sprin- and a storage arrangement of 40 ft. <br /> klers (Ref. Figure 1) are "Early Sup- (12,2 m) with a ceiling height of 45 ft. v 9 <br /> pression Fast Response Sprinklers" (13,7 m) does not require in -rack sprin- <br /> having a nominal K- factor of 25.2. klers as do ESFR sprinklers having a <br /> They are suppression mode sprinklers nominal K- factor of 14.0.' <br /> that are especially advantageous as a <br /> means of eliminating the use of in -rack Applications for the Model ESFR -25 <br /> sprinklers, when protecting high -piled Sprinklers are expanding beyond the <br /> storage. current recognized installation stand- <br /> ards. For information regarding re- <br /> The Model ESFR -25 is primarily de- search fire tests which may be accept- <br /> signed for use with storage heights of able to an Authority Having <br /> most encapsulated or non- encapsu- Jurisdiction (e.g., flammable liquids, <br /> lated common materials including car- exposed plastics, and aerosols), <br /> toned unexpanded plastics to 40 ft. please contact the Technical Services," <br /> (12,2 m) high and with ceiling heights Department. ." <br /> to 45 ft. (13,7 m). In addition, the pro- <br /> tection of some storage arrangements WARNINGS <br /> of rubber tires, roll paper, flammable The Model ESFR -25 Sprinklers de- <br /> liquids, aerosols, and automotive com- scribed herein must be installed and <br /> ponents can be considered as well. maintained in compliance with this <br /> The ESFR -25 provides the system de- document, as well as with the applica- <br /> signer with hydraulic and sprinkler ble standards of the National Fire Pro - <br /> placement options not presently avail- tection Association, in addition to the <br /> able to the traditional ESFR sprinklers standards of any other authorities hav- <br /> having a nominal K- factor of 14.0. In ing jurisdiction (e.g., FM Global). Fail- <br /> particular, the Model ESFR -25 has ure to do so may impair the perform - <br /> been designed to operate at substan ance of these devices. <br /> tially lower end head pressures, as The owner is responsible for maintain- <br /> compared to ESFR sprinklers having a ing their fire protection system and de- <br /> nominal K- factor of 14.0. This feature vices in proper operating condition. <br /> offers flexibility when sizing the sys- The installing contractor or sprinkler <br /> tem piping, as well as possibly reduc- manufacturer should be contacted <br /> with any questions. <br /> IMPORTANT Sprinkler <br /> Always refer to Technical Data Identification <br /> Sheet TFP700 for the "INSTALLER <br /> WARNING" that provides cautions <br /> with respect to handling and instal- Numbers <br /> lation of sprinkler systems and com- <br /> ponents. Improper handling and in- IN TY9226 - (Pendent K =25.2) <br /> stallation can permanently damage TY9226 is a redesignation for C9226, <br /> a sprinkler system or its compo- G8441, and S8010. <br /> nents and cause the sprinkler to fail <br /> to operate in a fire situation or cause <br /> it to operate prematurely. <br /> Page 1 of 8 JUNE, 2007 TFP312 <br />