Page 4 of 8 TFP312
<br /> TABLE A -1
<br /> RACK STORAGE
<br /> (See Design Criteria Section)
<br /> Commodity Maximum Maximum Minimum Flow Pressure, PSI (BAR)
<br /> Building Storage -
<br /> Height, Height, Comparison to Other TFP ESFR Sprinklers
<br /> Feet Feet ESFR -25 ESFR -1 ESFR -17 ESFR -17
<br /> (m) (m) PENDENT PENDENT PENDENT UPRIGHT
<br /> K = 25.2 K = 14.0 K = 16.8 K = 16.8
<br /> See Data Sheet See Data Sheet See Data Sheet
<br /> TFP318 TFP315 TFP316
<br /> NFPA FM NFPA FM NFPA FM NFPA FM
<br /> Class I, 45 40 40 50 90* 90* 63* 63* _ _
<br /> Class II, (13,7) (12,2) (2,8) (3,4) (6,2) (6,2) (4,3) (4,3)
<br /> Class 111, and 40 35 25 40 75 75 52 52 - _
<br /> Class IV (12,2) (10,7) (1,7) (2,8) (5,2) (5,2) (3,6) (3,6)
<br /> Encapsulated or 35 30 20 30 75 75 52 52 _ 52
<br /> U nenca psulated (10,7) (9,1) (1,4) (2,1) (5,2) (5,2) (3,6) (3,6) (3,6)
<br /> -and- 32 25 20 30 60 60 42 42 42
<br /> -
<br /> Cartoned (9,7) (7,6) (1,4) (2,1) (4,1) (4,1) (2,9) (2,9) (2,9)
<br /> Unexpanded 30 25 15 20 50 50 35 35 35
<br /> Plastics -
<br /> (9,1) (7,6) (1,0) (1,4) (3,4) (3,4) (2,4) (2,4) (2,4)
<br /> Uncartoned 45 40 _ _ 90* 90* 63* 63*
<br /> - _
<br /> (Exposed) (13,7) (12,2) (6,2) (6,2) (4,3) (4,3)
<br /> Unexpanded 40 35 _ 50 75 75 52 52 - -
<br /> Plastics (12,2) (10,7) (3,4) (5,2) (5,2) (3,6) (3,6)
<br /> 32 25 _ 50 60 60 42 42
<br /> (9,7) (7,6) (3,4) (4,1) (4,1) (2,9) (2,9) - -
<br /> 30 25 _ 50 50 50 35 35 _ _
<br /> (9,1) (7,6) (3,4) (3,4) (3,4) (2,4) (2,4)
<br /> Cartoned 32 25 _ _ 60 60 42 42 _ 42
<br /> Expanded Plastics (9,7) (7,6) (4,1) (4,1) (2,9) (2,9) (2,9)
<br /> 30 25 _ _ 50 50 35 35 _ 35
<br /> (9,1) (7,6) (3,4) (3,4) (2,4) (2,4) (2,4)
<br /> Uncartoned 30 25 _ - 100
<br /> (Exposed) ( (7,6) - (6,8)
<br /> - - - -
<br /> Expanded Plastics 25 20 75
<br /> ( (6,1) - - - (5,2) - - - -
<br /> *One level of in -rack sprinklers is required.
<br />
|