Laserfiche WebLink
SECTION IV — SYSTEM DESIGN <br /> UL EX. 3470 ULC CEx747 Page 4-1 <br /> 3 -1 -07 REV.7 <br /> SYSTEM DESIGN GENERAL INFORMATION <br /> The ANSUL R -102 Restaurant Fire Suppression System may be 1. Nozzles must be located 2 -8 in. (5 -20 cm) into the center of the <br /> used on a number of different types of restaurant cooking appii- duct opening, discharging up. See Figure 1. <br /> ances and hood and duct configurations. The design information <br /> listed in this section deals with the limitations and parameters of <br /> this pre - engineered system. Those individuals responsible for the <br /> design of the R -102 system must be trained and hold a current <br /> ANSUL certificate in an R -102 training program. <br /> 111141111 <br /> The R -102 and the PIRANHA systems use compatible agents and <br /> components, therefore, they may be used together for cooking <br /> appliance, hood, and duct protection. The primary ANSUL <br /> AUTOMAN Release can be either an R -102 or a PIRANHA <br /> ANSUL AUTOMAN Release and can actuate up to two additional R -102 or PIRANHA Regulated Actuators. In systems utilizing a � <br /> 101 remote release, any combination of the maximum number of <br /> regulated actuators can be used. 2 — e IN <br /> (5 — 20 cm) t <br /> • Both systems must actuate simultaneously. <br /> • Each system must be designed and installed per its appropri- FIGURE 1 <br /> ate manual. 000173 <br /> • Adjacent appliances requiring protection must be protected 2. In installations where a UL listed damper assembly is <br /> with the same type of system, either R -102 or PIRANHA, employed, the duct nozzle can be installed beyond the 8 in. <br /> unless the center -to- center spacing between the adjacent (20 cm) maximum, to a point just beyond the damper assem- <br /> R -102 and PIRANHA nozzles is no less than 36 inches. bly that will not interfere with the damper. Exceeding the maxi- <br /> • When appliances are protected with R -102 nozzles, the hood mum of 8 in. (20 cm) in this way will not void the UL listing of <br /> and connecting duct above those appliances cannot be pro- the system. <br /> tected with PIRANHA nozzles. 3. Previously listed 3 flow number and 5 flow number duct pro- <br /> • Mixing systems in a common plenum is not allowed. tection detailed in earlier published manual, Part No. 418087 - <br /> One of the key elements for restaurant fire protection is a correct 06, can also still by utilized. <br /> system design. This section is divided into ten sub - sections: Noz- DUCT SIZES UP TO 50 IN. (127 cm) <br /> zle Placement Requirements, Tank Quantity Requirements, Actu- PERIMETER/ 16 IN. (41 cm) DIAMETER <br /> ation and Expellant Gas Line Requirements, Distribution Piping <br /> Requirements, Detection System Requirements, Manual Pull Sta- • One 1W nozzle (Part No. 419336) = one flow number <br /> tion Requirements, Mechanical Gas Valve Requirements, Electri- 50 in. (127 cm) perimeter maximum <br /> cal Gas Valve Requirements, Electrical Switch Requirements, and <br /> Pressure Switch Requirements. Each of these sections must be • 16 in. (41 cm) diameter maximum <br /> completed before attempting any installation, System design <br /> sketches should be made of all aspects of design for reference DUCT SIZES UP TO 100 IN. (254 cm) <br /> during installation. PERIMETER/ 32 IN. (81.3 cm) DIAMETER <br /> NOZZLE PLACEMENT REQUIREMENTS • One 2W Nozzle (Part No. 419337) = two flow numbers <br /> This section gives guidelines for nozzle type, positioning, and • 100 in. (254 cm) perimeter maximum <br /> quantity for duct, plenum, and individual appliance protection. This • 32 in. (81.3 cm) diameter maximum <br /> section must be completed before determining tank quantity and The chart below shows the maximum rotection available from <br /> piping requirements. each duct nozzle. p <br /> Duct Protection — Single Nozzle Part 3.0 Gallon 1.5 Gallon <br /> All duct protection is UL listed without limitation of maximum duct Description No. System System <br /> length (unlimited length). This includes all varieties of ductworks 2W Nozzle 419337 Maximum Maximum <br /> both horizontal and vertical including ducts that run at angles to 100 in. (254 cm) 100 in. (254 cm) <br /> the horizontal and ducts with directional bends. Perimeter Perimeter <br /> The R -102 system uses different duct nozzles depending on the 1W Nozzle 419336 Maximum Maximum <br /> size of duct being protected. 50 in. (127 cm) 50 in. (127 cm) <br /> Perimeter Perimeter <br />