My WebLink
|
Help
|
About
|
Sign Out
Browse
Search
11-11453
Zephyrhills
>
Building Department
>
Permits
>
2011
>
11-11453
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
10/19/2011 9:52:11 AM
Creation date
10/19/2011 9:52:06 AM
Metadata
Fields
Template:
Building Department
Building Department - Doc Type
Permit
Permit #
11-11453
Building Department - Name
GALL BOULEVARD LAND TRUST
Address
6020 GALL BLVD
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
36
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
• <br /> 2 <br /> shall remain on when system is silenced. Tamper switches on backflow preventor <br /> shall be tied into panel, if applicable. Install weatherproof horn/strobe outside main <br /> entrance. <br /> 10. Ensure address is located on front and rear doors. Mimi mum 6 inches. <br /> 11. A Knox box will be required. Application can be obtained from this agency. Box <br /> will be located outside main entrance at a height of 6 feet. <br /> 12. Building shall be evaluated for lightweight truss in accordance to F.S. 633.027 <br /> and/or Florida Administrative Code 69A- 60.008. This sign shall be to the left of the <br /> main door at a height of 6 feet. <br /> 13. Additional fees will be assessed with the additional plan review for the fire alarm <br /> and fire sprinkler systems. <br /> Inspection Required: <br /> 1. Firewall Inspection. <br /> 2. Final <br /> KERRY BARNETT, FI ° ; ' SHAL <br /> ** *Please be advised this review of plans submitted is a cursory review to assist the contractor in <br /> compliance with applicable fire safety codes. This review is not intended to be a final approval of the <br /> submitted plans. It is the contractor's sole responsibility to ensure that the plans are in complete compliance <br /> with all applicable NFPA codes and local ordinances. In the event that further examination or site <br /> inspection reveals areas of non - compliance, it shall be the contractor's sole responsibility, at their sole <br /> expense to bring those areas in compliance. The City assumes no responsibility for the contractor's failure <br /> to be in compliance with all applicable NFPA codes and local ordinances. <br />
The URL can be used to link to this page
Your browser does not support the video tag.