Laserfiche WebLink
Wendle Sheet Metal Inc. Jobsite: /EB6-�Phlia i4rrrs� E <br /> #CSCO56662 � 335 N Buena Vista Drive 5963 Gall Blvd <br /> Lake Alfred, FL 33850 Zephyrhills FI <br /> Phone 863-956-2217 - Fax 863-956-5102 Contact: John <br /> 863-521-8807 <br /> �UBMITTED PLAN(S) HAVE BEEN REVIEW� <br /> SY ZEPHYRHILLS FIR MA HAL'S O ICE <br /> Datc: <br /> �vieww <br /> MininuM 10 �t clearance 10' x 12' <br /> 16 ga <br /> Two 2000 cfM externally I <br /> upblast welded <br /> xhaust fan stnck <br /> 3400 CFM grease QiZM for 40' 3/12 <br /> fittered cu 1500 f r, � pitched <br /> repinceroe t duct p veloci y 18' roof <br /> alr fan support Inged <br /> flange m�neral curb <br /> wool <br /> duct <br /> ase <br /> per NFPA <br /> 96-4,2.3.2 <br /> 9ft 4' lay in ceiUng <br /> baffle <br /> skirting <br /> grease <br /> Supply ftex filters <br /> front supply <br /> plenuM <br /> grease <br /> cup fire extingulshing system by <br /> 42' others <br /> 4 ft stainless 16ft stainless steel, t <br /> steel backirn�. I ype i <br /> Cooler 6. hood wlth front supply plenuM <br /> 78' <br /> Cooking <br /> equipMent Exhaust flow based on <br /> bY MediuM teroperature coaking <br /> others equipment per FBC 507.13.2 <br /> Note� Hood, grease reMOVaI devices, exhaut fan, and duct shall have a clenrance of 18' to coMbustible <br /> Materlats, 3' to liMited combustible Mnterinl nnd 0' to non coMbustible Material per NFPA 96-4,2.1. Where not <br /> possibte a clearance reduction systeM of 22 gage on 1' Mineral wool batts relnforced with wire Mesh spaced <br /> out i' on non coMbustibte spncers is provided for a 3' clearance to coMbust(ble Mnterial per NFPA 96-4.2.3.2 <br />