<br /> �; Tot /a B iu ldi� Summary Loads � __�
<br /> � � -� �� � '��
<br /> . � ��� �--, -�' `�
<br /> Z CHURCH: Glazing-CHURCH 3X5 WINDOW, u-value 105 1,106 0 2,906 2,906
<br /> 0.35, SHGC 0.32
<br /> Z CHURCH: Door-Wood - Panel 40 192 0 172 172
<br /> 13A-4fcb: Wall-Biock, board insulation only, R-4 board 415 1,494 0 811 811 �
<br /> insulation, filled core, brick finish �
<br /> 16C-30: Roof/Ceiling-Under Attic with Insulation on Attic 600 576 0 787 787 'i
<br /> Floor (also use for Knee Walls and PartRion ;
<br /> Ceilings), Vented Attic, No Radiant Barrier, White or
<br /> Light Color Shingles, Any Wood Shake, Light Metal,
<br /> Tar and Gravel or Membrane, R-30 insulation
<br /> 22A-pl: Floor-Slab on grade, No edge insulation, no 70 2,077 0 0 0 i,
<br /> insulation below floor, any floor cover, passive, light i
<br /> dry soil ,
<br /> Subtotals for structure: 5,445 0 4,676 4,676 �'�,
<br /> People: 30 6,000 6,900 12,900 I
<br /> Equipment: 0 0 0 j
<br /> Lighting: 0 0 0 ':
<br /> Ductwork: 1,508 376 1,885 2,261 i�
<br /> Infiltration: Winter CFM: 62, Summer CFM: 53 2,032 1,917 937 2,854 i
<br /> Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0!
<br /> AED Excursion: 0 0 103 103 i
<br /> Total Building Load Totals: 8,985 8,293 14,501 22,794 i
<br /> C�ti� �
<br /> Total Building Supply CFM: 660 CFM Per Square ft.: 1.099 I
<br /> Square ft, of Room Area: 600 Square ft. Per Ton: 316 �
<br /> Volume (ft') of Cond. Space: 4,800 ��
<br /> Total HeaUng Required Including Ventilation Air: 8,985 Btuh 8.985 MBH
<br /> Total Sensible Gain: 14,501 Btuh 64 °�
<br /> Total Latent Gain: 8,293 Btuh 36 %
<br /> Total Cooling Required Incfuding Ventilation Air: 22,794 Btuh 1.90 Tons (Based On Sensible + Latent)
<br /> �
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> � Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.