RI►vsa - 4t�s�al � Li�t Co�nciai HYAC t.oadc EBfs 8ollware Drwiopmsnt, N�c.
<br /> E s
<br /> � Lindem�xt BeMaon Bojack . ZEPHYRHICl.S Chtm:h Of Christ
<br /> � C lem�ont, FL 34711 ------ P 5
<br /> I � � tem_ 1 Summary Loads _ ___ _ _ _ _ �I
<br /> � ��� � � � �: ��
<br /> ��� . � � � � �
<br /> Z CHURCH: Glazing-CHURCH 3X5 WINDOW, u-value 105 1,106 0 2,906 2,906
<br /> 0.35, SHGC 0.32
<br /> Z CHURCH: Door-Wood - Panel 40 192 0 172 172
<br /> 13A-4fcb: Wali-Block, board insulation only, R�l board 415 1,494 0 811 811
<br /> insulation, filled core, brick finish
<br /> 16C-30: Roof/Ceiling-Under Attic with Insulation on Attic 600 576 0 787 787 �''I
<br /> Floor (also use for Knee Walls and Partition �
<br /> Ceilings), Vented Attic, No Radiant Barrier, White or
<br /> Light Color Shingles, Any Wood Shake, Light Metal,
<br /> Tar and Gravel or Membrane, R-30 insulation
<br /> 22A-pl: Floor-Slab on grade, No edge insulation, no 70 2,077 0 0 0,
<br /> insutation below floor, any floor cover, passive, light
<br /> dry soil
<br /> Subtotals for structure: 5,445 0 4,676 4,676
<br /> People: 30 6,000 6,900 12,900 ;
<br /> Equipment: 0 0 0 I
<br /> Lighting: 0 0 0 ;
<br /> Ductwork: 1,508 376 1,885 2,261 i
<br /> In�ltration: Winter CFM: 62, Summer CFM: 53 2,032 1,917 937 2,854 i
<br /> Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0
<br /> AED Excursion: 0 0 103 103
<br /> System 1 Load Totals: 8,985 8,293 14,501 22,794
<br /> Ch�dc �gures
<br /> Supply CFM: 660 CFM Per Square ft.: 1 099
<br /> Square ft. of Room Area: 600 Square ft. Per Ton: 316
<br /> Volume (ft') of Cond. Space: 4,800 i
<br /> Sy�t+�rr Ldads�
<br /> Total Heating Required Including Ventilation Air: 8,985 Btuh 8.985 MBH
<br /> , Total Sensible Gain: 14,501 Btuh 64 %
<br /> ; Total Latent Gain: 8,293 Btuh 36 %
<br /> Total Cooling Required Including Ventilation Air. 22,794 Btuh 1.90 Tons (Based On Sensible + Latent)
<br /> �
<br /> I Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> I Calculations are performed per ACCA Manuat J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturePs performance data at
<br /> � your design conditions.
<br /> �
<br /> I
<br /> �
<br /> I
<br /> , �;
<br /> �
<br /> - — -- --- - - - - - - _— J
<br /> C:\ ...�ZEPHYRHILLS CHURCH OF CHRIST.rh9 Wednesday, June 15, 2011, 8:43 PM