<br /> � System 1, Zone 1 Summary Loads (Average Load Procedure for Rooms) ;
<br /> ��� . � � -- �, �`�
<br /> i C��n � �a �r � �33� ° t'�
<br /> Z CHURCH: Glazing-CHURCH 3X5 WINDOW, u-value 105 1,106 0 2,906 2,906
<br /> 0.35, SHGC 0.32
<br /> Z CHURCH: Door-Wood - Panel 40 192 0 172 172
<br /> 13A-4fcb: Wall-Block, board insulation oniy, R� board 415 1,494 0 811 811
<br /> insulation, filled core, brick finish
<br /> 16C-30: RooflCeiling-Under Attic with Insulation on Attic 600 576 0 787 787
<br /> Floor (also use for Knee Walls and Partition I
<br /> Ceilings), Vented Attic, No Radiant Barrier, White or
<br /> Light Color Shingles, Any Wood Shake, Light Metal, I
<br /> Tar and Gravel or Membrane, R-30 insulation
<br /> 22A-pt: Floor-Slab on grade, No edge insulation, no 70 2,077 0 0 0 I ;
<br /> insulation below floor, any floor cover, passive, light I
<br /> dry soil I
<br /> Subtotals for structure: 5,445 0 4,676 4,676 I
<br /> People: 30 6,000 6,900 12,900 �
<br /> Equipment: 0 0 0 ',
<br /> Lighting: 0 0 0 I,
<br /> Ductwork: 1,508 0 1,885 1,885 I
<br /> Infiltration: Winter CFM: 62, Summer CFM: 53 2,032 1,917 937 2,854
<br /> System 1, Zone 1 load Totals: 8,985 7,917 14,501 22,418
<br /> Ch�k �'i�tres
<br /> Supply CFM: 660 CFM Per Square ft.: 1.099
<br /> Square ft. of Room Area: 600 Square ft. Per Ton: 321
<br /> Volume (ft') of Cond. Space: 4,800
<br /> Zc� M.n�ds
<br /> Total Heating Required: 8,985 Btuh 8.985 MBH
<br /> Total Sensible Gain: 14,501 Btuh 65 %
<br /> Total Latent Gain: 7,917 Btuh 35 %
<br /> � Total Cooling Required: 22,418 Btuh 1.87 Tons (Based On Sensible + Latent)
<br /> i ��
<br /> i Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are perFormed per ACCA Manual J 8th Edition, Version 2, and ACCA Manuat D.
<br /> All computed results are estimates as building use and weather may vary. I
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> I your design conditions.
<br /> �
<br /> I
<br /> i
<br /> I
<br /> i
<br /> �
<br /> I I
<br /> � �
<br /> , �
<br /> '
<br /> � i
<br /> -- - — - - - - — — -- - - - �
<br /> C:\ ...1ZEPHYRHILLS CHURCH OF CHRIST.rh9 Wednesday, June 15, 2011, 8�43 PM
<br />
|