05-17-'12 12:53 F�OM-Wallace Associates 7275200789 T-739 P0003/0004 F-117 <br /> q-3 Provide signage for the entire area which is symbolic, tactile, displayed verbal and <br /> pictorial in accordance with 11-4.30 Florida building Code. <br /> A-4 Provide passage type ixk set hardware for door leading to waiting area from exit <br /> passage 110. <br /> A-5 Eliminate thumb locks from all exterior exit doors. All exit doors shalt require single <br /> operation for exiting. <br /> A-6 Complete the installation of lockers for p�tients to seCUre their belongings. <br /> A-7 Nurse Ca!! signage for the entire area shall match with the room signage. <br /> A-8 All penetrations in the case work shall be tightly sealed to minimize entry of rodents and <br /> i�sects as per the requirements of chapter 59A�$.108. <br /> A-9 Complete the installation of window treatment in the patient care areas to provide <br /> patient privacy. <br /> A-10 Complete the instatlation of pass through cabinets in all the 3 OR's as shown on <br /> �pproved floor plans. <br /> A-11 Provide code required pull station within 5'-0" of exit at east entry 183 and passage 118 <br /> as shown on the approved floor plans. <br /> A-12 Exit door in the exit passage 118 shall swing in the direction of travel. Revise the door <br /> swing ac�ordingly. <br /> A-13 Provide directional exit signs in passage 110 and 111 to clearly identify the direction of <br /> trave�. <br /> A-14 Complete the installation of soap dispensers at the OR scrub sinks. <br /> A-15 Provide smooth tr�nsition at the iwo showers in the male and female locker rooms. <br /> A-16 Manifolds for the medical gases in the exterior medical gas areas sh�lt be protected <br /> from the inclement weather. <br /> A-17 Door leading out of the recovery area which is in a rated fire/smoke wall shall drop on <br /> activation of building fire alarm to have positive iatching. <br /> A-18 Eliminate the hold open device from door leading to the clean/s#erile corridor from the <br /> recovery area. <br /> A-19 SeaUcaulk all conduit penetrations in the rated 1 Hr fire/smoke compartment wall in the <br /> recovery area. <br /> MECHANICAL <br /> z <br />