Laserfiche WebLink
05-17-'12 12;53 F�OM-�allace Associates 7275200789 T-739 P0004/0004 F-117 <br /> M-1 Secure final fiiters in RTU-1,2 and 3. <br /> M-2 Provide a Second monitoring IoCation for the master�larm panel. This facility meets the <br /> requirements of a level one medical gas system. <br /> M-3 Provide interlock between the fire/smoke dampers and each respective �ir handker <br /> during manual shutdown of the unit. <br /> M-4 F_xtend the retief lines from the sterilizers to tne flaor drains <br /> FI PROTECTI N <br /> FP-1 <br /> ECTRt AL <br /> E-1 Provide and revise the circuit brea[cer settings summary for ground fauit pick-up setting <br /> for AHCA review as required by FAC chapter 59A-4. <br /> �-2 Provide and replace the three circuit breakers `LSLA' MB, `C-1' MB, and `EQLA' MB in <br /> the essenti�l equipment room with the adjustable circuit bre�kers as required by FAC <br /> Chspter 59A-4. <br /> E-3 Provide a pull station and horn/strobe at the exist door 183 in east as required by NFPA <br /> 101. <br /> Please feel free to contact me if you have any further questions. <br /> Sanjay K,ochhar <br /> 4£�xce of Plans and Coz�stzuction <br /> Agency fox Health Care Adminis�rat�oz� <br /> 400'V�.Robinson St., Suate 5-325 <br /> Qrlando,FL. 32801 <br /> (407)420-2550 �ax (407) 317'7182 <br /> mail to: Sanj�y.KOChhar(�ehca,myflorida.COm <br /> ..d,..�.�' �flV£R PLORIDA <br /> :ti. . ��u���� <br /> •', � a��a�c� <br /> From:Amir Yacoub[mailto:amir@oliveriarchitects.mm] <br /> Ser�:Thursday, May 17,2012 8:56 AM <br /> To: Kochhar, Sanjay <br /> Cc;Joe Qtiveri;Thomas LoCicero <br /> Subject: RE: 0945-FMC ASC Zephyrhills final AHCA inspection <br /> 3 <br />