Laserfiche WebLink
Wiring Requirements <br /> While shielded wire is not required, it is recommended that all <br /> SLC wiring be twisted-pair to minimize the effects of electrical <br /> interference. Wire size should be no smaller than 18 AWG <br /> (0.78 mmz) and no larger than 12 AWG (3.1 mmz) The wire <br /> size depends on the length of the SLC circuit. Use the table <br /> . below to determine the specific wiring requirements for the <br /> SLC. <br /> SLC Wire Distance in Feet yyire Size Wire Type <br /> Requirements (m) <br /> Non-P/enum(FPLR): <br /> Twisted-pair,unshielded 10,000 feet(3,048 m) 12 AWG(3.31 mm2) Genesis 4315,Belden 5020UL <br /> P/enum(FPLP): <br /> Genesis 4515,Belden 6020UL <br /> Non-Plenum(FPLR): <br /> Twisted-pair,unshielded 8,000 feet(2,438 m) 14 AWG(2.08 mmZ) Genesis 4313,Belden 5120UL <br /> P/enum(FPLP): <br /> " Genesis 4513,Belden 6120UL <br /> Non-Plenum(FPLR): <br /> Twisted-pair,unshielded 4,875 feet(1,486 m) 16 AWG(1.31 mm2) Genesis 4311,Belden 5220UL <br /> P/enum(FPLP): <br /> Genesis 4511,Belden 6220UL <br /> Non-Plenum(FPLR). <br /> Twisted- air,unshielded 3,225 feet 983 m Z Genesis 4306,Belden 5320UL <br /> P � ) 18 AWG(0.821 mm ) <br /> Plenum(FPLP): <br /> Genesis 4506,Belden 6320UL <br /> FireWarden-100-2 Wire Requirements <br /> DN-7101.A•09/2't/07—Page 3 of 4 <br />