Laserfiche WebLink
. SECTION IV—SYSTEM DESIGN <br /> ' UL EX. 5174 6-5-98 Page 4-7 <br /> REV 1 <br /> TANK AND CARTRIDGE RE(�UIREMENTS CHART <br /> The following chart is used to determine tank (and cartridge) I'B- THRU TEE THRU TEE <br /> quirements after the total Rumber of nozzles have been determined. � <br /> Maximum <br /> Total No. Quantity and Nitrogen Cartridge <br /> of Nozzles Size of Tank(s) Size Required (Part No) � <br /> 7 (1) PIRANHA-7 LT-20-R (7032) BULLTEE `� <br /> 10 (1) PIRANHA-10 LT-30-R (5373) ���. <br /> 13 (1) PIRANHA-13 LT-30-R (5373) BULL <br /> � TEE <br /> 14 (1) PIRANHA-7 LT-20-R (7032) <br /> (1) PIRANHA-7' LT-20-R (7032) � THRU <br /> 17 (1) PIRANHA-7 LT-20-R (7032) � TEE <br /> (1) PIRANHA-10' LT-30-R (5373) <br /> 20 (1) PIRANHA-10 LT-30-R (5373) CONTINUOUS SPLIT <br /> (1) PIRANHA-10' LT-30-R (5373) SYSTEM SYSTEM <br /> 23 (1) PIRANHA-10 LT-30-R (5373) FIGURE 14 <br /> (1) PIRANHA-13* LT-30-R (5373) OO7fi85 <br /> 26 (1) PIRANHA-13 LT-30-R (5373) <br /> (1) PIRANHA-13" LT-30-R (5373) GENERAL DISTRIBUTION PIPING RULES <br /> ►(Common to All Size Systems Both High and Low Proximity) <br /> 27 (7) PIRANHA-7 LT-20-R (7032) <br /> (1) PIRANHA-10" LT-30-R (5373) 1 Maximum elevation difference between the top of the tank to <br /> (1) PIRANHA-10` LT-30-R (5373) the highest nozzle = 9 ft. <br /> Additional combinations are available up to a maximum system 2• Maximum elevation difference between the lowest nozzle to <br /> size of 39 nozzles(three PIRANHA-13) the highest nozzle = 8 ft. <br /> ' Regulated Actuator 3. The water supply pressure must be between 30 to 100 psi at <br /> each Water Pressure Testing Assembly gauge. <br /> DISTRIBUTION PIPING REC�UIREMENTS 4 Minimum amount of total linear piping for a single nozzle <br /> Once the nozzle placement and quantity of tanks has been deter- system used to protect a fryer,wok, range, tilt skiilet or brais- <br /> mined, it is then necessary to determine the piping configuration ► ing pan = 8 0 ft. <br /> from each tank to the discharge nozzles.This section contains the 5. Maximum nozzles allowed downstream of the center outlet of <br /> guidelines and limitations for designing the distribution piping so a thru tee = 2. See Figure 15 <br /> that the system will discharge from all nozzles utilized at proper <br /> flow rates.These limitations should also be referred to when select- 6. Linear pipe lengths are measured center to center of fittings. <br /> ing the mounting location for the regulated release and agent tank. <br /> THRU TEE <br /> DISTRIBUTION PIPING DEFINITIONS / <br /> Bull Tee:A bull tee is defined as a tee positioned in the system so �� <br /> /� <br /> that the flow enters the center inlet of the tee and exits 90°out both � <br /> side outlets. See Figure 14. <br /> Thru Tee:A thru tee is defined as a tee positioned in the system CENTER <br /> so that the flow enters a side inlet and exits straight through the OUTLET <br /> tee to the opposite outlet and also exits 90°through the center out- FIGURE 15 <br /> let. See Figure 14 �,686 <br /> Continuous System:A continuous distribution piping system is 7 Multiple bull tees are allowed in both continuous and split sys- <br /> ►one that does not include a bull tee between the agent tank and tems as long as maximum linear and equivalent lengths are <br /> the first nozzle. See Figure 14 not exceeded. <br /> ►Split System:A split distribution piping system contains a bull tee g. No nozzles are allowed on the 1/2 in. pipe run. <br /> between the agent tank and first nozzle See Figure 14 <br /> � 9 Minimum number of nozzles in a system = 2 (low proximity <br /> Equivalent Length: Length of distribution piping, defined in feet, ; only) <br /> which includes the actual length of pipe (measured from center to <br /> center of fittings) and a given pipe length value assigned to each <br /> fitting used that must be added to the overall pipe length sum. <br /> Linear Length:The actual length of piping measured from center <br /> to center of fittings. <br />