Laserfiche WebLink
SECTION !V—SYSTEM DESIGN <br /> UL EX. 5174 6-5-98 Page 4-12 <br /> REV 1 <br /> WATER SUPPLY REQUIREMENTS MANUAL PULL STATION REQUIREMENTS <br /> The water flow valve located in each AUTOMAN Regulated A remote manual pull station allows the PIRANHA system to be <br /> Release and each regulated Actuator assembly must be connect- manualiy operated at some point distant from the regulated <br /> ed to the building's potable water supply by a waterline sized to release assembly The pull station should be installed at a maxi- <br /> provide a simultaneous flowing water pressure at each PIRANHA mum height of 60 in. (152 cm) and located in the path of exit.The <br /> Water Pressure Testing Assembly gauge between 30 and 100 psi pull station is the only source of manual actuation of the regulated <br /> when the waterline is flow tested. release assembly. <br /> Each PIRANHAwaterline must meet the following requirements. Two styles of remote pull stations are available. metal stamped <br /> and plastic molded. <br /> • The minimum waterline must be 3/4 in. pipe or tubing for a one The total length of the cable used for each manual pull station <br /> or two tank PIRANHA system and 1 in.pipe or tubing for a three Within a system must not exceed 150 ft. (46 m) <br /> tank PIRANHA system <br /> • Must be dedicated to the PIRANHA system The maximum number of pulley elbows that may be used per sys- <br /> tem is 20 <br /> • Must include a single,full flow, indicating, locked-open, tamper- One pulley tee, Part No. 15342, is allowed per system. <br /> proof shut-off valve <br /> Exception: When using a pulley tee, Part No 15342, in the pull <br /> • Must be connected to the potable water supply line immediately station line, the maximum length of wire rope to each pull station <br /> downstream from the main shut-off valve must not exceed 125 ft. (38 m) and the maximum number of <br /> • A maximum of three(3)PIRANHA water flow valves can be con- eibows must not exceed 18 <br /> nected to a common waterline when all the valves operate Metal Stamped Style—Part No.4835 or 54011 <br /> simultaneously See Figure 22. <br /> Parts that may be used for installation of a metal stamped remote <br /> See "Sizing and Instailing Waterline" in Section V, Installation, for manual pull station are <br /> General and Sizing Requirements. <br /> Descri�tion Part No. <br /> BACKFLOW PREVENTER Remote Manual Pull Station Assembly' S4011 <br /> Each AUTOMAN Regulated Release and Regulated Actuator Remote Manual Pull Station Assembly 4835 <br /> Assembly includes an anti-siphon vacuum breaker which serves Pulley Elbow 423250 <br /> r as the approved backflow prevention device for the PIRANHA Pulley Elbow 415670 <br /> system. Pulley Tee�' 15342 <br /> 1/16 in. Stainless Steel Cable 50 ft. (15 m) 15821 <br /> � Oval Press-To-Crimp Sleeves 4596 <br /> Glass Break Rod (1) 4834 <br /> ` Assembly includes parts listed below� <br /> '*Designed for 32°F to 130°F(0°C to 54°C)temperature areas.Utilized when two remote <br /> manual pull staUOns are being connected to one regulated release assembly. <br /> MAIN WATER <br /> so�e Plastic Molded Style—Part No.415255 <br /> AUTOMAN REGULATED REGULATED <br /> RELEASE ACTUATOR ACTUATOR Parts that may be used for installation of a plastic molded remote <br /> manual pull station are <br /> LOCKABLE SHUT-OFF VALVE Part No. <br /> Description <br /> FIGURE 22 Remote Manual Pull Station Assembly 415255 <br /> 0016t8 Trim Ring Shipping Assembly (25) 415256 <br /> NOTICE Replacement Seal Shipping Assembly(25) 415317 <br /> No other shutoff devices shall be located 1/16 in. Stainless Steel Cable 500 ft. (152 cm) �4596 <br /> between the main water shut-off valve and the Oval Press-To-Crimp Sleeves 423250 <br /> Lockable Shut-Off Valve The shut-off valve on Pulley Elbow 15342 <br /> the dedicated waterline must be locked open. Pulley Tee <br />