�� SYSTEM SPECIFICATIONS <br /> , , System Capacity Temperature and Humidity Ranges <br /> • Annunciators. .. .. .. . .8 This system meets NFPA requirements for operation at 0 — <br /> 49°C/32 — 120°F and at a relative humidity 93% ± 2% RH <br /> Electrical Specifications (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the <br /> useful life of the system's standby batteries and the electronic <br /> • MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, components may be adversely affected by extreme tempera- <br /> 1 0 A ture ranges and humidiry. Therefore, it is recommended that <br /> • MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, this system and its peripherals be installed in an environment <br /> 3.90 A with a normal room temperature of 15—27°C/60—80°F <br /> • MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, <br /> o.5a A. Agency Listings and Approvals <br /> • MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, The listings and approvals below apply to the basic MS-5UD-3 <br /> 2.2� A. and MS-10UD-7 control panels. In some cases, certain mod- <br /> • Wire size: minimum 14 AWG (2.0 mm2) with 600 V insula- ules or applications may not be listed by certain approval <br /> tion,supervised, nonpower-limited agencies, or listing may be in process. Consult factory for lat- <br /> est listing status. <br /> Cabinet Specifications • UL Listed: File S624 <br /> Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x • FM Approved <br /> 0 72" (1.82 cm.) deep. Backbox: 19 00" (48.26 cm.) high x • CSFM:7165-0075:0214 <br /> 16.65" (4229 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring . MEA: MEA. 333-07-E <br /> (TR-CE):22.00" (55.88 cm.)high x 19 65"(49 91 cm.)wide. <br /> NOTE:For ULC-listed models,see DF-60440. <br /> Shipping Specifications <br /> NFPA Standards <br /> Dimensions: <br /> The MS-5UD-3(E) and MS-10UD-7(E) complies with the fol- <br /> —20.00" (50.80 cm.)high lowing NFPA 72 Fire Alarm Systems requirements: <br /> —22.5" (57 15 cm.)wide —LOCAL (Automatic, Manual, Waterflow and Sprinkler <br /> —8 5"(21.59 cm.)deep. Supervisory) <br /> Weight:27 Ib(12.20 kg) —AUXILIARY(Automatic, Manual and Waterflow) (requires <br /> 4XTMF) <br /> —REMOTE STATION (Automatic, Manual and Waterflow) <br /> (Where a DACT is not accepted, the alarm, trouble and <br /> supervisory relays may be connected to UL 864 listed <br /> transmitters. For reverse polarity signaling of alarm and <br /> trouble, 4XTMF is required.) <br /> —PROPRIETARY(Automatic, Manual and Waterflow) <br /> —CENTRAL STATION (Automatic, Manual and Waterflow, <br /> and Sprinkler Supervised). <br /> —OT, PSDN (Other Technologies, Packet-switched Data <br /> Network) <br /> FireLite� Alarms and System Sensor� are registered trademarks of <br /> Honeywell I nternational I nc. <br /> 002010 by Honeywell International Inc.All rights reserved.Unauthorized use <br /> of this document is strictly prohibited. <br /> I�O �oo� This document is not intended to be used for installation purposes. <br /> We try to keep our product information up-to-date and accurate. <br /> We cannot cover all specific applications or anticipate all requirements. <br /> g�q��Np���� All specifications are subject to change without notice. � <br /> QUALITY SrSTEMS MadeintheU.S.A. <br /> For more information,contact Fire-Lite Alarms.Phone:(800)627-3473,FAX.(877)699-4105. <br /> www.firelite.com <br /> Page 4 of 4—DF-52416:D•07/26/2010 <br />