<br /> i � Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. �
<br /> Advanced Air Solutions Inc. Kline Residence i
<br /> I ,_Tampa FL 33634_
<br /> �! j Sy_stem 1L_Zone 1_Summary_Loads (Avera�e Load Procedure for_Rooms) __ P�e7I �
<br /> i Component Area Sen Lat Sen Total f
<br /> ' Description Quan Loss Gain Gain Gain
<br /> I 1A-cm-o. Glazing-Single pane, operable window, clear, 144 5 0 0 8,867 8,867 ',
<br /> metal frame no break, u-value 1.27, SHGC 0 75
<br /> 11A: Door-Wood-Hollow Core 42 0 0 612 612
<br /> 13A-2ocb� Wall-Block, board insulation only, R-2 board 1237.5 0 �� 5,g22 5 g22 �
<br /> insulation, open core, brick finish
<br /> I 166-13� Roof/Ceiling-Under Attic with Insulation on Attic 1434 4 0 0 5,522 5,522
<br /> Floor(also use for Knee Walls and Partition Ceilings),
<br /> Vented Attic, No Radiant Barrier, Dark Asphalt i
<br /> Shingles or Dark Metal, Tar and Gravel or i
<br /> Membrane, R-13 insulation �
<br /> I!, FLOOR ON SLAB. Floor-Over open crawl space or 1434.4 0 0 710 710
<br /> garage, Custom, FLOOR ON THE SLAB
<br /> Subtotals for structure. 0 0 21,533 21,533
<br /> IPeople 4 80Q 920 1,720
<br /> Equipment: 0 1,200 1,200
<br /> Lighting. 200 682 682
<br /> Ductwork: 0 0 2,918 2,918 �
<br /> Infiltration: Winter CFM: 0, Summer CFM:44 0 1,387 967 2,354
<br /> System 1, Zone 1 Load Totals 0 2,187 28,220 30,407 I
<br /> � � Check Figures �
<br /> , Supply CFM� 1,284 CFM Per Square ft.. p 895 * I I�
<br /> � Square ft. of Room Area. 1,434 Square ft. Per Ton: 5 6 6
<br /> Volume(ft') of Cond. Space: (clg.) 11,475
<br /> I ` Based on area of rooms being heated or cooled(whichever governs system) rather than entire floor area.
<br /> - -
<br /> ' (Zone Loads - - - —
<br /> - --- -- -- -
<br /> - - -- --- ,
<br /> Total Sensible Gain — —� �
<br /> 28,220 Btuh 93 % �i
<br /> I Total Latent Gain. 2,187 Btuh 7 % '
<br /> Total Cooling Required. 30,407 Btuh 2.53 Tons(Based On Sensible+ Latent)
<br /> Ij �i Notes - -
<br /> - -- -- -
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program. —�
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. '
<br /> ' All computed results are estimates as building use and weather may vary. �
<br /> � Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at �
<br /> your design conditions.