DN-6995:C•Ai-320
<br /> NP-100(A� Series J ���� � � � �
<br /> Addressable Photoelectr�c Detectors
<br /> for the FireWarden Series by H oneywe i l
<br /> General
<br /> ��..,. ,� ...�_ -
<br /> The NP-100(A), NP-100T(A) and NP-100Fi(A) addressable, � � '
<br /> low-profile plug-in photoelectric detectors use a state-of-the- /�
<br /> art photoelectric sensing chamber with communications lo l�°, �• -� � ` �
<br /> provide open area protection and are used exclusively with i �'.�� '. , � ' � .
<br /> NOTIFIER's FireWarden Series(FireWarden-100-2 and Fire- �. - � ' � `�,:• ,a ,�;.;. ,
<br /> Warden-50 and S artan NSP-25 Addressable Fire Alarm • 'i,; .� �.a,,.;- � ,:�'���'`�«�,•,;,,,;,:.?��;. �
<br /> ) P � ) , s� -r.-_
<br /> Control Panels (FACPs). The NP-100T(A) adds thermal sen- -`'��.:��`;='��� , _ , :�.i;y;� �`��i�•`"?���
<br /> sors that will alarm at a fixed temperature of 135°F (57°C) - `" _ °:'a°'• '`��'%`' y��
<br /> :.;,;��:,;,Y. -''::,=:� .:,;:�:�+,,:�'"..
<br /> Since these detectors are addressable, they will help emer- _ ���.i�:,�:;:��`;�� •
<br /> gency personnel quickly locate a fire during its early stages, ' � '�=��„`""'' `' '
<br /> potentially saving precious rescue time while also reducing ,,.����'�`"��=��=v.`;s,4'�' �
<br /> property damage. Two LEDs on each sensor light to provide a ' ��.-. �'��i�
<br /> 7 . .
<br /> local,visible sensor indication.Remote LED annunciator capa- � '
<br /> biliry is available as an optional accessory, PN RA100Z(A). - -- '
<br /> The NP-100R(A}is a remote test capable detector for use with NP-100(A)In 6210LP(A�Base m
<br /> DNR(A)/DNRW duct smoke detector housings.
<br /> �eatures Applications
<br /> SLC loop Use photoelectric detectors in life-safety applications to pro-
<br /> • Two-wire loop connection. vide a broad range of fire-sensing capability, especially where
<br /> • Unit uses base for wiring. smoldering fires are anticipated.lonization detectors are often
<br /> Addressing better than photoelectric detectors at sensing fast, flaming
<br /> fires.
<br /> • Addressable by device.
<br /> • Rotary,decimal addressing:01 -99 with FireWarden•100-2 Construction
<br /> and NSP-25,and 01 -50 with FireWarden-50 These detectors are constructed of oif-white fire resistant plas-
<br /> Architecture iic. NP-100(A)series plug-in, low-profile smoke detectors are
<br /> • Unique single-source, dual-chamber design to respond designed to commercial standards and ofier an attractive
<br /> quickly and dependably to a broad range of fires. appearance.
<br /> • Sleek,low-profiie design.
<br /> • Integral communications and built-in type identiFication. �nstallation
<br /> • Built-in tamper-resistant feature. NP-100(A)series piug-in detectors use a detachable mounting
<br /> • Removable cover and insect-resistant screen for simple base to simplify installation,service and maintenance.
<br /> field cleaning. Mount base(all base types)on an electrical backbox which is
<br /> Operation at least 1.5"(3.81 cm)deep.For a chart of compatible junction
<br /> • Withstands air velocities up to 4,000 feet-per-minute(20 ml
<br /> boxes,see DN-60054
<br /> sec.)without triggering a false alarm. NOTE:Because ol the inherent supervrsion provrded by the SLC
<br /> • Factory preset at 1.5% nominal sensitivity for panel alarm loop, end-of-line resistors are not requrred. Wiring 'T-taps" or
<br /> lhreshold level branches are permrtted for Sryfe 4(Class 8J wiring. NP-i00R(A)
<br /> mou�ts rn a DNR(A)/ONRW duct detector housrng.
<br /> � Visible LED"blinks"when the unit is addressed{communi-
<br /> cating with the fire panel)and latches on in alarm. Qperation
<br /> Mechanicals Each NP-100 A series detector uses one of 99
<br /> ( ) possible
<br /> • Sealed against back pressure. addresses on the FireWarden-100-2 and NSP-25,or one of 50
<br /> • Direct surface mounting or electrical box mounting. possible addresses on the FireWarden•50 Signaling Line Cir-
<br /> • Mounts to. single-gang box, 3.5" (8.89 cm) or 4.0" (10 16 cuit (SLC). It responds to regular polis from ihe system and
<br /> cm)octagonal box,or 4 0"(10.16 cm)square electrical box �eports its type and status.
<br /> (using a plaster ring—incJuded). The addressable photoelectric sensor in the NP-100(A)series
<br /> Other systern features has a unique unipolar chamberthat responds quickly and uni-
<br /> formly to a broad range of smoke conditions. It can withstand
<br /> • Fully coated circuit boards and superior RF/transient pro- Wind gusts up to 4,000 feet-per-minute (20 m/sec.) without
<br /> tection. sending an alarm level signal. Because of its unipolar cham-
<br /> • 94-VO plastic flammability rating. ber, the NP-100(A) series is approximately two times more
<br /> • Low standby current. responsive than most photoelectric sensors. This makes it a
<br /> Options more stable detector.
<br /> • Remote LED output connection,PN RA100Z(A)
<br /> DN-6995:C•12/07i?01 1—Page 1 of 2