DN-6999:C
<br /> Monitor Modules
<br /> NMM-100(A), NMM-100P(A), J �I�T I �I E R J
<br /> NZM-100(A), and NDM-100(A)
<br /> for FireWarden Series Panels by �I o n eywe I I
<br /> ,
<br /> General
<br /> Four diiferent monitor modules are available for Notifier's Fire- —_ �__------- --- -_�--�—
<br /> -;:?�.«s�,�_:._.::_��_:.-�.�:��.,_.,�,.T:.., :i
<br /> Warden Series intelligent control panels for a variety of appli- ,,.;.,
<br /> cations. Monitor modules supervise a circuit of dry-contact � '��f �� -
<br /> � n� Y ;?•:3:,;.
<br /> input devices, such as conventional heat detecrors and pull {;tiT�� ",mM� ' ���•,�`.,i',
<br /> � a.��:�° u�
<br /> stations, or monitor and power a circuit of two-wire smoke �',i�;.' •<::� � '" `��i�4_
<br /> w.�
<br /> detectors(NZM-100(A}) ` �� ,���..a..�.�
<br /> NMM-100(A)is a standard-sized module(typically mounts to a """'
<br /> 4" [10.16 cm] square box) that supervises either a Style D ����;�;� � „�,•,,,
<br /> (Class A) or Sryle B (Ciass B) circuit of dry-contact input i ,,..,.., ;���.-�,
<br /> devices. '"°""' ^d��.°•.. . �.
<br /> NMM-100P(A) is a miniature monitor module a mere 1.3" �`°�'' �a� �,�a ^6�
<br /> (3.302 cm)H x 2.75" (6.985 cm) W x 0.5" (1270 cm) D that '����n � i,� e�'
<br /> supervises a Sryle B (Class B) circuit of dry-contact input -_--- ---�i`.��C,�Z'`�\a�D���_ -� �
<br /> devices. Its compact design allows the NMM-100P(A) to be �� T��ja. e '�1�F� �;',
<br /> �' � , � °
<br /> mounted in a single-gang box behind the device it monitors. I� . i ry��_�r;�-.<< �
<br /> \.`�,; � ��aa�,:
<br /> N2M-100(A) is a standard-sized module that monitors and ,�;?�.;-.�.,-_�-_�_�_�--=-��•'_. .�
<br /> supervises compatible two-wire,24 volt,smoke detectors on a ---��-"�' ,�
<br /> Style D(Class A) or Style B(Class B)circuit.
<br /> NDM-100(A) is a standard-sized dual monitor module that NMM-100(A)(Type H)
<br /> monitors and supervises two independent two-wire Style B
<br /> (Class B) dry-contact initiating device circuits (IDCs) at two
<br /> separate,consecutive addresses in intelligent,two-wire systems. NMM-100(A) OPERAT/ON
<br /> Each NMM-100(A) uses one of the available module
<br /> �1MIVI-100(A� Monitor Module addresses on an SLC loop. it responds to regular polls from
<br /> Built-in rype identification automatically identifies this device the control panel and reports its type and the status(open/nor-
<br /> • as a monitor module to the control panel. mal/short)of its Initiating Device Circuit(IDCI.A flashing LED
<br /> indicates that the module is in communication with the control
<br /> • Powered directiy by two-wire SLC toop.No additional power panel. The LED latches steady on alarm (subject to current
<br /> required. limitations on the loop).
<br /> � High noise(EMFJRFI)immunity. NMM-100(A) SPECIFICATlONS
<br /> • SEMS screws with clamping plates for ease oi wiring. Nominal operating voltage: 15 to 32 VDC.
<br /> • Direct Decade entry of address: 01 - 99 on FireWarden-
<br /> 1�0-2,01 -50 on FireWarden-50 Max(mum current draw:5.0 mA(LED on).
<br /> • LED ilashes during normal operation and latches on steady Average operating current: 350 NA (LED flashing), 1 com-
<br /> to indicate alarm. munication every 5 seconds,47k EOL.
<br /> The NMM-100(A)Monitor Module is intended for use in intelli- Maximum IDC wiring resistance:40 ohms.
<br /> gent, hvo-wire systems, where the individual address of each EOL resistance:47K ohms.
<br /> module is selected using the built-in rotary switches. It pro-
<br /> vides either a two-wire or four-wire fault-tolerant Initiating Temperature range:32°F to 120°F(0°C to 49°C)
<br /> Device Circuit(IDC) for normally-open-contact tire alarm and Humidiry range: 10%to 93°/a noncondensing.
<br /> supervisory devices. The module has a panel-controlled LED
<br /> indicator Dlmensions: 4.5" (11 43 cmy high x 4" (1016 cm) wide x
<br /> 1.25" (3.175 cm) deep. Mounts to a 4" (10 16 cm) square x
<br /> NMM-f00(A)APPLlCAT/ONS 2.125"(5.398 cm)deep box.
<br /> Use to monitor a zone of four-wire smoke detectors, manual
<br /> fire alarm pull stations, waterflow devices, or other normally-
<br /> open dry-contact alarm activation devices. May also be used
<br /> to monitor normally-open supervisory devices with special
<br /> supervisory indication at ihe control panel. Monitored circuit
<br /> may be wired as an NFPA Style B(Class By or Style D(Class
<br /> A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
<br /> (provided) terminates the Sryle B circuit. No resistor is
<br /> required for supervision of the Style D circuit.