Laserfiche WebLink
2.03 FIELD DEVICES (Where indicated on the Engineering Drawings) <br /> A. Monitor Modules (POPIT) <br /> 1 Provide addressable monitor modules (popit)where required to interface with <br /> contact alarm devices, or to connect a supervised zone of conventional initiating <br /> devices (any normally open dry contact device)to an intelligent data loop <br /> 2 Provide address-setting means and store an internal identification code which the <br /> control panel shall use to identify the type of device <br /> 3. Acceptable manufacturer is Bosch D9127U. <br /> B. Conventional Photoelectric Smoke Detectors <br /> 1 Provide conventional type photoelectric smoke detectors with the ability to be <br /> monitored by the control panel. <br /> 2. Provide multi-function alarm/power status LED Flash status LED under normal <br /> conditions, indicating that the detector is operational and in regular <br /> communication with the control panel. The LED may be placed into steady <br /> illumination, indicating that an alarm condition has been detected and verified. <br /> 3 Provide low profile design modular detector head with twist-lock base <br /> 4. Provide capability to connect a remote LED annunciator <br /> 5. Provide all required power to smoke detectors. <br /> 6. Acceptable manufacturer is System Sensor 2W-B <br /> C Conventional Manual Pull Stations <br /> 1 Provide single action type manual pull stations. Manual pull stations shall be <br /> designed that upon activation, shall initiate a change of status at the control <br /> panel The manual pull stations shall not be automatically resettable and shall <br /> include a visible indication of the manual pull station being activated. <br /> 2. Construct of hi-impact red molded Lexan with instructions for station operation in <br /> raised white letters <br /> 3 Where possible, provide flush mounting of pull stations Surface mounting of pull <br /> stations will be allowed if flush mounting is not possible or as indicated on the <br /> engineering drawings <br /> 4 Provide protective covers with integral sounder, as indicated by these <br /> specifications and the engineering drawings for all common area manual pull <br /> stations <br /> 5. Provide a keyed reset on each pull station <br /> 6. Acceptable manufacturer is Fire-Lite BG-12 <br /> Hobby Lobby—Zephyrhills, FL FIRE ALARM SYSTEM <br /> Issued for Permit—October 23, 2013 16720 -9 <br />