Rhvac-Residential&Light Commercial HVAC Loads � Elite Software Development,Inc.
<br /> HVAC Designs Wainut Grove TH 1202 N
<br /> Tam ,FL 33615 Pa e 6
<br /> Total Buildin Summa Loads
<br /> Component Area Sen Lat Sen Total
<br /> Description Quan Loss Gain Gain Gain
<br /> OP LOW E MIN:Glazing•NFRC CODE MIN Operable 2 52.2 835 0 654 654
<br /> Pane Low E,ground reflectance=0.23,outdoor
<br /> insect screen with 50°/.coverage,light color blinds
<br /> at 45°with 1C�7.coverage,u-value 0.5,SHGC 0.5
<br /> FD LOW E MIN:Glazing-NFRC CODE MIN Glass Door 2 20 320 0 278 278
<br /> Pane Low E,ground reflectance=0.23,light color
<br /> blinds at 45°with 100'/e coverage,u-value 0.5,
<br /> SHGC 0.5
<br /> 11N:Door-Metal•Polystyrene Core 40 434 0 343 343
<br /> 12B-0sw:Part-Frame,R•11 insulation in 2 x 4 stud 165.4 481 0 321 321
<br /> cavity,no board insulation,siding finish,wood
<br /> studs
<br /> 13A-4ocs:Wall Block,board insulaGon only,R-4 board 286.5 1,311 0 749 T49
<br /> insulation,open core,siding Nnish
<br /> 13A-4ocs:Part-Block,board lnsulation only,R-4 board 96 412 0 275 275
<br /> insulation,open core,sidfng finish
<br /> 168•30-�d:RooflCeiling-Under Attic with Insulation on 1202.6 1,231 0 2,041 2,041
<br /> Attic Floor(also use for Knee Wall and Partition
<br /> Ceilings),vented attic,no radiant barrier,R-30
<br /> insulation,dark asphalt
<br /> 22A-pm:Floor-Slab on grade,No edge insulation,no 84 3,172 0 0 0
<br /> insulation below floor,any floor cover,passive,
<br /> _____heavy dry or light wet soil_
<br /> -- - --- - _ - -__ _ _-- __ - ----- ---_ ----- _ _ - -' -- --- ---- ---
<br /> Subtotals for structure: 8,196 0 4 661 4 661
<br /> Pe0P1e� 3 690 900 1,590
<br /> Equipment: 640 2,040 2,680
<br /> Lighting: 0 0 0
<br /> Ductwork: 1,728 235 1,573 1,809
<br /> Infiltration:Winter CFM:112,Summer CFM:58 3,948 1,690 1,142 2,632
<br /> Ventiladon:Winter CFM O,Summer CFM 0 0 0... 0 0
<br /> _ __ _.... __ _..__
<br /> Total Building Load Tot�ls: 13,872 3,255 10,316 13,572
<br /> Check Figures
<br /> Total Building Supply CFM: 600 CFM Per Square ft.: 0.499
<br /> Square ft.of Room Area: 1,202 Square it.Per Ton: �,pqg
<br /> Volume(ft')of Cond.Space: 9,620
<br /> Buildfn Loads
<br /> Total Heati�g Required Including Ventllatlon AIr: 13,872 Btuh 13.872 MBH
<br /> Totai Sensible Gsfn: 10,316 Btuh 76 °/.
<br /> Total Latent Gain: 3,255 Btuh 24 °/.
<br /> Total Cooling Required Including Ventiladon Air: 13,572 Btuh 1.15 Tons(Based On 75°k Sensible Capacity)
<br /> Notes
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions.
<br /> Monday,November 04,2013,11:48 AM