Rhvac-Residential&Ltght Commercial HVAC Loads � Elite Software Deve�opment,Inc.
<br /> HVAC Designs Walnut Grove TH 1202 N
<br /> Tam a,FL 33615 Pa e 7
<br /> S stem 1 Room Load Summa
<br /> Htg Min Run Run Cig Clg Min Act
<br /> Room Area Sens Htg Duct Duct Sens Lat Cig Sys
<br /> No Name SF Btuh CFM Size Vel Btuh Btuh CFM CFM
<br /> —Zone 1—
<br /> 2 Foyer 57 2,145 49 4 - 889 143 45 52
<br /> 3 Bed 2 145 3,217 73 5 - 1,401 345 7� g1
<br /> 4 Bath 2 54 682 16 4 • 339 60 17 20
<br /> 5 KEtchen 201 235 5 6 • 2,054 500 104 119
<br /> 6 GreatlDi�ing 415 3,211 73 6,6 • 3,573 1,142 181 208
<br /> 7 M Wic 27 31 1 4 - 54 0 3 3
<br /> 8 M Bath 106 125 3 4 - 308 80 16 18
<br /> 9 M Bed _ 197 4,227._ __..96 6 - __ 1,699___ 750 86 99
<br /> _ . _.. _ _ _....._
<br /> Duct Latent _ Z35
<br /> _. _ _.._. __. _.__.... _. _ __.
<br /> System 1 total 1,202 ,_ 13,872 315 10,316 3,255 521 600
<br /> __ _..._ _ _ _...._ __ ____ _....
<br /> System 1 Main Trunk Size: 10x13 in.
<br /> Velocity: 665 ftJmin
<br /> Loss per 100 R: 0.085 in.wg
<br /> Ouct size results above are from Manual D Ductsize.
<br /> Runout duct velocities are not printed with duct size results from Manual D Ductsize since they can vary within the room. See the Manual D Ductsize
<br /> report for duct velocities and other data.
<br /> Coolin S stem Summa
<br /> Cooling SensiblelLatent Sensible Latent Total
<br /> Tons S lit Btuh Btuh Btuh
<br /> Recommended �,15 75•/.125°/. 10,316 3,439 13,755
<br /> ACtual: 1.55 75%125% 13,950 4�650 18�600
<br /> Equipment Data
<br /> Heatina Svstem Coolina S�ntem
<br /> Type: Air Source Heat Pump Air Source Heat Pump
<br /> Model: 4A6H3018C1 4A6H3018C1
<br /> Indoor Model: GAF2AOA18S11+TDR
<br /> Brand: HERITAGE 13 HERITAGE 13
<br /> Description: Air Source Heat Pump Air Source Heat Pump
<br /> Efficiency: 8.2 HSPF 14 SEER
<br /> Comment: p
<br /> Sound: 0 0
<br /> Capacity: 17,600 Btuh 18,600 Btuh
<br /> Sensible Capaclty: nla 13,950 Btuh
<br /> Latent Capacity: nla 4,650 Btuh
<br /> AHRI Reference No.: nla ,q,q41Y99
<br /> This cy�tem's equipment was selected in accordance with ACCA Manual S.
<br /> Manual S equlpment sizing data: SODB:93F,SOWB:77F,WODB:40F,SIDB:75F,SIRH:55%,WIDB:72F,Sen.gain:10,316 Btuh,Lat gain:3,255
<br /> Btuh,Sen,loss:13,872 Btuh,Entering clg.coil DB:75F,Entering clg.coil WB:63.9F,Entering htg.coil DB:72F,Clg.coil TD:18F,Htg.coil TD:40F,
<br /> Req.cig.airflow:521 CFM,Req.htg.airflow:315 CFM
<br /> Monday,November 04,2013,11:48 AM