Laserfiche WebLink
, I I <br /> � <br /> i <br /> i <br /> � i <br /> i <br /> I <br /> il . <br /> pril 6, 1995 � <br /> � <br /> ; <br /> ■ � <br /> The ;Edge Group, P.A. � <br /> 444 �Bunker Road, Suite 201 <br /> West Palm Beach, FL 33405-3694 <br /> � <br /> Attri: Don Edge i <br /> . ' East Pasco Medical Center <br /> Outpatient Surgery Unit/First Floor Rehab Services <br /> Log No. H-425-M/CON No. NR-920606AM <br /> PEI Project No. H93-15 <br /> The following are the Agency For Health Care Administration's <br /> (AHCA) comments dated March 9, 1995 and Peninsula Engineering, <br /> Inc. 's responses, dated April 6, 1995: <br /> ELECTRICAL <br /> COMMENT• <br /> � I <br /> E-34 Revise Circuit 1LN1-31 such that there are six <br /> receptacles or less per 59A-3 or indicate which circuit <br /> ; serves the P.H. controller. ' <br /> � <br /> RESPONSE• <br /> � � <br /> We shall comply, please refer to the revised Sheet E-3, <br /> dated April 6, 1995, Start #9 attached. The P.H. <br /> controller has been moved to another ci�rcuit. I <br /> � <br /> COMMENT• <br /> � I <br /> E-35 Provide revised schedules for all panels effected by this " <br /> revision. <br /> RESPONSE• ; <br /> � I <br /> , We shall comply all panel schedules affected by this work ' <br /> have been updated and are attached. Please refer to <br /> revised Sheet E-12, dated April 6, 1995, Star #9 � <br /> ' attached. ' <br /> COMMENT• ; <br /> � <br /> E-36 The lighting over the pool in hydrotherapy shall meet all , <br /> ' the requirements of NFPA-70, Article 680-6 (b) (1) or � I <br /> � relocate the fixtures as required. <br /> 1833 Etlgewater Drive ■ Orlando, Florida 32804 ■ 407/246-1688 ■ FAX 407/246-1664i <br /> ' � ! il <br /> ; j , <br />