Laserfiche WebLink
t <br /> G.roununG LUG .rSTaLl- <br /> k <br /> I <br /> k <br /> Necessary Components: <br /> One of following ground lugs(orany UL 2703 compliant ground lug): <br /> Bur idy CLS0-1TN Ground Lug(UL 2703-E351343.f UL 467-E9999) <br /> ILSCO SGB-4 Ground.Lug(UL 2703-E354420 /.UL 467-E34440) <br /> ILSCO GBL-4D9T(UL 2703-E354420'./UL 467-E34440) <br /> ILSCO GBL-4DM(UL 270.3.-E354420 /UL 467 E34440) <br /> ILSCO GBL-4SS(UL 2703-E354420 /UL 467.-'E34440) <br /> Note:Drill and deburr hole In Ground Lug prior to Installation <br /> - 14 AWG-4 AWG Copper Ground Wirt* Torque Values: <br /> - 8:32 x 0.57.Serrated Flange Head Bolt(300 Series SS) 14.10-AWG=201n4s. <br /> 8-32Serrated Flange Nut(300 Series SS) 8.AWG=25 in-lbs. <br /> 11/327 and 1 f4"wrenches or ratchets/sockets 6-4 AWG=-3S ln4bs. <br /> 1 Insertthe flange bolt into the module ground hole.Place Star Washer over bolt.Place ground iug over the bolt and. <br /> Star Washer,and turn to desired orientation. <br /> 2 Install Flange Nut. <br /> .3 Tighten Flange Nut/Bolt. <br /> 4 Placewirein Ground Lug channel and tighten setscrew to complete.assembly. <br /> *Wire should be sized in accordance with the National Electrical Code,NFPA 70,Section 690.45,and-a minimum of <br /> 1f47clearance required between bare copper wire and aluminum. <br /> Drill hole per grounding lug.manufacturers <br /> "a specifications in the upslope:part of Rock-it Coupling. <br /> ' for attaching grounding lug. <br /> Note:Deburrhole In-Ground Lug and Rock-it Coupling prior to Installadon. <br /> www.eoafastensolancom lnfo@ecofastensalarcom 877-859-3947 6 <br />