Laserfiche WebLink
. i <br /> GrounDinG LUG nSTaLL <br /> Necessary Components: <br /> One of the following ground lugs(or any UL 2703 compliant ground'lug)- <br /> Burndy.CL50.1TN Ground Lug_(UL 2703-E351343 / UL 467-E9999) <br /> ILSCO SGB-4Ground Lug-(UL 2703-E354420 /UL 467-E34440) <br /> ILSCO GBL-4DBT(UL 2703-E354420 /UL 467-E34440) <br /> ILSCO GBL4DBTH(UL 27tl3-E354420 /UL 467-E34440) <br /> NSCO GBL-4SS.(UL 2703-E354420 /-UL 467-E34440) <br /> Note:Drill and deburr-hole in Ground Lug prior to installation <br /> - 14 AWG-4 AWG Copper Ground Wire* Torque values: <br /> - 8-32 x 0:5"Serrated Flange Head Bolt(300 SedesSS) 14-10 AWG=20 in-lbs. <br /> - 8-32,Serrated Flange Nut(300 Series S$) 8 AWG=25 in-lbs. <br /> 11/3rand 1/4"wrenches or ratchets/sockets &4 AWG=35 in4bs. <br /> 1 Insert the:flange=bolt into the.module ground hole.Place StarWasher over bolt,Place ground lug over the bolt and <br /> Star Washer,and turn to desired orientation.. <br /> 2', Install Flange Nut.. <br /> 3 Tighten Flange Nut/Bolt. <br /> 4 Place wire in Ground lug channel and tighten set screw-to complete assembly. <br /> *Wire should be sized in accordance with the National Electrical Code,NFPA 70,Section 690.45,and a minimum of <br /> 1/47clearance required between bare copper_wire and aluminum. <br /> r <br /> { <br /> Drill hole per grounding lug manufacturers <br /> . . specifications in the upslope part of Rock-it Coupling <br /> for.attaching.grounding lug. <br /> 4 , <br /> i r , <br /> Note:Deburr hole in Ground Lug and Rock-it Coupling prior to installation. <br /> www.ecofastensolarcom info@ecofastensolarcom -877-859-3947 6 <br />