Laserfiche WebLink
ONEMOjetc. <br /> 5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or <br /> exceed that required under FRSA/TRI April 2012(04-12),Appendix A,Table IA. <br /> Alternatively,the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design <br /> pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment, <br /> density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used <br /> methods are ANSI/SPRI WD1,FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. <br /> Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention <br /> Data Sheet 149(January 2016)for Zone 2/3 enhancements. <br /> 5.7 Exposure Limitations: <br /> Lastobond Eaves Protection Sheet,Lastobond 195,Lastobond Eco,Lastobond Smooth Seal HT,RESISTO L81236, <br /> Gtip-Rite Eave &Valley Protector or RESISTO LB1244 shall not be left exposed for longer than 30-days after <br /> installation. <br /> Lastobond Shield,Lastobond Pro HT-N,RESISTO SA SMOOTH PLY 40,Lastobond Shield HT or Lastobond Pro HT- <br /> S,EnviroShield shall not be left exposed for longer than 90-days after installation. <br /> Lastobond TU HT or Colphene FR GR shall not be left exposed for longer than 180-days after installation. <br /> 5.8 Tile Slippage Limitations(TAS 103 per FRSA/TRI April 2012(04-12)): <br /> When loading roof tiles on the underlayment in direct-deck tile assemblies,the maximum roof slope shall be as <br /> follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. <br /> Underlayment Tile Profile Staging Method Maximum <br /> Slope <br /> Flat Max.10-tile stack 6:12 <br /> Lugged Max.10-tile stack 5:12 <br /> Max.10-tile stack(bottom 2-tile stack <br /> shall be inverted,followed by 8 tiles high 6:1 <br /> on slope,as shown below) <br /> TX <br /> Lastobond TU HT <br /> Lugged <br /> Colphene FR GR Flat Max.10-tile stack Sm! <br /> Lugged Max.10-tile stack 6:12 <br /> MEMO ETC,LLC Evaluation Report S18010.06.09-1112 <br /> Certificate ofAuthorization#32455 6'EDITION(2017)FBC NON-HVHZ EVALUATION FL2569-R14 <br /> Soprerna Roof Underlayments Revision 12:02/12/2018 <br /> Page 6 of 8 <br />