Laserfiche WebLink
'GrounDi.nG LUG InSTaLL <br /> is <br /> Necessary. Components: <br /> - One of the following ground lugs(or any UL 2703 compliant ground lug): <br /> Burndy CL50-1 TN Ground Lug(UL 2703-E351343 / UL 467-:E9999). <br /> ILSCO SGB-4 Ground Lug(UL 2703-E354420 /UL.467-E34440) <br /> ILSCO.GBL-4DBT,(UL 2703-E354420 /.UL 467-.E34440) <br /> ILSCO GBL-4DBTH(UL 2703-.E354420 /UL 467-E34440) <br /> ILSCO GBL=4SS(UL 2703-E354420 /UL 467-E34440) <br /> Note:Drill and deburr hole in Ground Lug prior to installation <br /> - 14 AWG-4 MG Copper Ground Wire* Torque Values: <br /> - 8-32.x 0.5"Serrated Flange Head Bolt(300 Series SS). 14=1 GAWG=20 in-Ibs. <br /> 8-32 Serrated Flange Nut(300 Series SS) 8 AWG=25 in-Ibs. <br /> 11/32'and.1/4"-wrenches or ratchets/sockets 6-4-AWG=35 in-Ibs. <br /> 1 Insert the flange bolt into the module.ground.hole.Place Star.Washer over bolt:Place ground lug over the bolt:and <br /> Star Washer,and turn to desired orientation. <br /> 2 .Install Flange Nut. <br /> 3 Tighten Flange Nut/Bolt. <br /> 4 Place wire in Ground Lug channel and tighten set screw.to complete assembly. <br /> *Wire should be sized in accordance with.the National Electrical Code,NFPA 70,Section 690A5,and a minimum of <br /> 1/4"clearance required between-bare copper wire and aluminum. <br /> Drill hole per.grounding lug manufacturers <br /> specifications in the upslope part of Rock-it.Coupling, <br /> for attaching grounding lug. <br /> 17, <br /> Note:Deburr hole in Ground Lug and'Rock-It.Coupling prior to installation. <br /> www:ecofastensolarcom info@ecofastensolar.com 877-859-3947 6 <br />