Laserfiche WebLink
160 <br />(a) All three story buildings with interior halls, <br />corridors, or stairs shall have at least one elevator <br />with full firemen emergency service. <br />6. Stairs & Stairwells. <br />(a) All three story buildings with interior stairs <br />and stairwells, the stairs and stairwells shall be of <br />non-combustible construction. <br />(b) The stairwell enclosure shall be of a minimum <br />of two hour fire rated. <br />(c) Doors from stairs on each floor will be a <br />minimum of "B" (1-1/2 hour) rated with automatic <br />closers. <br />7. Conditional Requirements for Buildin s <br />Four Story Buildings - a maximum of 60 feet in <br />height and Five Story Buildings - a maximum of <br />75 feet in height. <br />1. The Zephyrhills Fire Department shall have, or <br />pending delivery of, an aerial apparatus with a minimum <br />of 75 feet of verticle reach and the necessary manpower <br />to man it before a four or five story building can be <br />permitted. <br />2. Four story buildings shall be Type I, Type II, <br />or Type IV protected construction regardless of its <br />occupancy classification. <br />3. Five story buildings shall be Type I or Type II <br />construction regardless of its dassificatiori. <br />4. All four and five story buildings shall have <br />full automatic sprinkler system as per NFPA 13 with the <br />exceptions listed in IV, 1 (b) & (c). <br />5. Standpipe System - Wet. <br />(a) All four and five story buildings shall have a <br />wet standpipe system as per NFPA 14 and the SBC.