PART 1 - GENERAL <br />AND MUNICIPAL DEPARTMENTS AFFECTED BY <br />1.1 GENERAL REQUIREMENTS <br />CONNECTION OF SERVICES. <br />A. DRAWINGS AND GENERAL PROVISIONS OF CONTRACT <br />B. WHERE CONFLICTS BETWEEN VARIOUS CODES, <br />INCLUDING GENERAL AND SUPPLEMENTARY CONDITIONS <br />ORDINANCES, RULES AND REGULATIONS EXIST, <br />AND DIVISION 1 SPECIFICATION SECTIONS, APPLY TO <br />COMPLY WITH THE MOST STRINGENT. WHEREVER <br />THIS SECTION. WHERE THE REQUIREMENTS OF THIS <br />REQUIREMENTS OF THESE SPECIFICATIONS, DRAWINGS, <br />SECTION AND DIVISION EXCEED THOSE OF DIVISION 1, <br />OR BOTH, EXCEED THOSE OF THE ABOVE ITEMS, THE <br />THIS SECTION AND DIVISION TAKE PRECEDENCE. <br />REQUIREMENTS OF THESE SPECIFICATIONS, DRAWINGS <br />BECOME THOROUGHLY FAMILIAR WITH ALL <br />OR BOTH, SHALL GOVERN. CODE COMPLIANCE, AT A <br />REQUIREMENTS THAT AFFECT THIS DIVISION, SECTION <br />MINIMUM, IS MANDATORY. CONSTRUE NOTHING IN <br />OR BOTH. WORK REQUIRED UNDER THIS DIVISION <br />THESE CONSTRUCTION DOCUMENTS AS PERMITTING <br />INCLUDES ALL MATERIAL, EQUIPMENT, APPLIANCES, <br />WORK NOT IN COMPLIANCE, AT A MINIMUM, WITH <br />AND LABOR REQUIRED TO COMPLETE THE ENTIRE <br />THESE CODES. <br />ELECTRICAL SYSTEM AS REQUIRED BY THE DRAWINGS <br />C. PROVIDE AND MAINTAIN ALL NECESSARY SIGNAL LIGHTS <br />AND SPECIFICATIONS, OR REASONABLY INFERRED TO <br />AND GUARDS FOR THE SAFETY OF THE PUBLIC. <br />BE NECESSARY TO FACILITATE EACH SYSTEM'S <br />OBTAIN AND PAY FOR ALL PERMITS FOR WORK IN <br />FUNCTIONALITY AS IMPLIED BY THE DESIGN AND THE <br />THIS DIVISION. <br />EQUIPMENT SPECIFIED. <br />D. WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL <br />B. THE SPECIFICATIONS AND DRAWING FOR THE <br />ELECTRICAL CODE AND ALL OTHER GOVERNING <br />PROJECT ARE COMPLEMENTARY, AND PORTIONS OF <br />STANDARDS. <br />THE WORK DESCRIBED IN ONE, SHALL BE PROVIDED <br />1.4 JOB CONDITIONS <br />AS IF DESCRIBED IN BOTH. IN THE EVENT OF <br />DISCREPANCIES, NOTIFY THE ENGINEER AND REQUEST <br />A. CONNECTIONS TO EXISTING WORK: <br />CLARIFICATION PRIOR TO PROCEEDING WITH THE WORK <br />1. INSTALL NEW WORK AND CONNECT TO EXISTING <br />INVOLVED. <br />WORK WITH MINIMUM INTERFERENCE WITH EXISTING <br />C. DRAWINGS ARE GRAPHIC REPRESENTATIONS OF THE <br />FACILITIES. <br />WORK UPON WHICH THE CONTRACT IS BASED. THEY <br />2. TEMPORARY SHUTDOWNS OF EXISTING SERVICES: <br />SHOW THE MATERIALS AND THEIR RELATIONSHIP TO <br />ONE ANOTHER, INCLUDING SIZES, SHAPES, LOCATIONS <br />A) AT NO ADDITIONAL CHARGES. <br />AND CONNECTIONS. THEY ALSO CONVEY THE SCOPE <br />B)AT TIMES NOT TO INTERFERE WITH NORMAL <br />OF WORK, INDICATING THE INTENDED GENERAL <br />OPERATION OF EXISTING FACILITIES. <br />ARRANGEMENT OF THE EQUIPMENT, FIXTURES, OUTLETS <br />AND CIRCUITS WITHOUT SHOWING ALL OF THE EXACT <br />C)ONLY WITH WRITTEN CONSENT OF THE OWNER. <br />DETAILS AS TO ELEVATIONS, OFFSETS, CONTROL LINES <br />3. ALARM AND EMERGENCY SYSTEMS: NOT TO BE <br />AND OTHER INSTALLATION REQUIREMENTS. USE THE <br />INTERRUPTED. <br />DRAWINGS AS A GUIDE WHEN LAYING OUT THE WORK <br />AND TO VERIFY THAT MATERIALS AND EQUIPMENT WILL <br />4. MAINTAIN CONTINUOUS OPERATION OF EXISTING <br />FIT INTO THE DESIGNATED SPACES AND WHICH, WHEN <br />FACILITIES AS REQUIRED WITH NECESSARY <br />INSTALLED PER MANUFACTURER'S REQUIREMENTS, WILL <br />TEMPORARY CONNECTIONS BETWEEN NEW AND <br />ENSURE A COMPLETE, COORDINATED, SATISFACTORY <br />EXISTING WORK. <br />AND PROPERLY OPERATING SYSTEM. <br />5. CONNECT NEW WORK TO EXISTING WORK IN NEAT <br />D. DRAWINGS ARE SCHEMATIC IN NATURE, SHOW THE <br />AND ACCEPTABLE MANNER. RESTORE EXISTING <br />VARIOUS COMPONENTS OF THE SYSTEMS <br />DISTURBED WORK TO ORIGINAL WORKING CONDITION <br />APPROXIMATELY TO SCALE AND ATTEMPT TO INDICATE <br />INCLUDING MAINTENANCE OF WIRING CONTINUITY AS <br />HOW THEY SHALL BE INTEGRATED WITH OTHER PARTS <br />REQUIRED. <br />OF THE WORK. FIGURED DIMENSIONS TAKE <br />B. DEMOLITION: <br />PRECEDENCE TO SCALED DIMENSIONS. DETERMINE <br />1. FURNISH ALL LABOR, EQUIPMENT AND MATERIALS <br />EXACT LOCATIONS BY JOB MEASUREMENTS, BY <br />REQUIRED TO DEMOLISH, CAP, PATCH, REPAIR <br />CHECKING THE REQUIREMENTS OF OTHER TRADES AND <br />AND DISPOSE OF THE DIVISION 16 SYSTEM NO <br />BY REVIEWING ALL CONTRACT DOCUMENTS. CORRECT <br />LONGER REQUIRED AS PART OF AN ACTIVE SYSTEM <br />ERRORS THAT COULD HAVE BEEN AVOIDED BY <br />OF THE PROJECT AS SPECIFIED HEREIN AND AS <br />PROPER CHECKING AND INSPECTION, AT NO <br />INDICATED ON THE DRAWINGS. <br />ADDITIONAL COST. <br />E. SPECIFICATIONS DEFINE THE QUALITATIVE <br />2. UNDER THIS SCOPE, FURNISH ALL LABOR, <br />REQUIREMENTS FOR PRODUCTS, MATERIALS AND <br />EQUIPMENT, APPLIANCES AND MATERIALS TO <br />WORKMANSHIP UPON WHICH THE CONTRACT IS BASED. <br />PERFORM ALL OPERATIONS IN CONNECTION WITH <br />THE DEMOLITION OF THE DIVISION 16 SYSTEMS AS <br />1.2 DESCRIPTION <br />INDICATED ON THE DRAWINGS AND AS SPECIFIED <br />A. SPECIFICATIONS ARE OF A SIMPLIFIED FORM AND <br />HEREIN AND/OR AS REQUIRED BY THE LOCAL <br />INCLUDE INCOMPLETE SENTENCES. WORDS OR <br />BUILDING CODE. THE WORK SHALL INCLUDE BUT <br />PHRASES SUCH AS 'THE CONTRACTOR SHALL", "SHALL <br />NOT BE LIMITED TO THE FOLLOWING: <br />BE", "FURNISH", "PROVIDE", "A", "AN", 'THE" AND <br />A) UNLESS OTHERWISE NOTED IN THE <br />"ALL" HAVE BEEN OMITTED FOR BREVITY. <br />CONSTRUCTION DOCUMENTS, ALL CONTRACTORS <br />B. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL <br />SHALL REVIEW THE EXISTING CONDITIONS, IN <br />ARRANGEMENT OF SYSTEMS AND WORK. FOLLOW <br />ADDITION TO THE ARCHITECTURAL DOCUMENTS, <br />DRAWINGS IN LAYING OUT WORK AND CHECK <br />AND THE DIVISION 15/16 DOCUMENTS, TO <br />DRAWINGS OF OTHER TRADES TO VERIFY SPACE <br />DETERMINE THE COMPLETE SCOPE OF WORK. <br />CONDITIONS. MAINTAIN HEADROOM AND SPACE <br />B) REMOVE ALL EXISTING ELECTRICAL EQUIPMENT, <br />CONDITIONS. <br />BUSWAYS, CONDUIT, RACEWAYS, LIGHTING <br />C. DEFINITIONS: <br />FIXTURES, WIRING AND ASSOCIATED EQUIPMENT <br />1. "FURNISH" OR "PROVIDE": TO SUPPLY, INSTALL <br />WITHIN THE AREA TO BE DEMOLISHED, WHETHER <br />AND CONNECT UP COMPLETE AND READY FOR <br />SPECIFICALLY INDICATED OR NOT, THAT IS NO <br />SAFE AND REGULAR OPERATION OF PARTICULAR <br />LONGER REQUIRED UNLESS OTHERWISE INDICATED. <br />WORK REFERRED TO UNLESS SPECIFICALLY <br />C)OPENINGS REMAINING IN ENCLOSURES AS A <br />OTHERWISE NOTED. <br />RESULT OF DEMOLITION SHALL BE SEALED WITH <br />2. "INSTALL": TO ERECT, MOUNT AND CONNECT <br />SHEET METAL CAP OR OTHER APPROVED <br />COMPLETE WITH RELATED ACCESSORIES. <br />APPROPRIATE MEANS, UNLESS OTHERWISE <br />INDICATED. <br />3. "SUPPLY": TO PURCHAS, PROCURE, ACQUIRE AND <br />DELIVER WITH RELATED ACCESSORIES. <br />D) WHERE EXISTING EQUIPMENT IS TO BE <br />4. "WORK": LABOR, MATERIALS, EQUIPMENT <br />RELOCATED, EXTREME CARE SHALL BE TAKEN TO <br />APPARATUS, CONTROLS, ACCESSORIES AND OTHER <br />PREVENT DAMAGE DURING THE REMOVAL AND <br />ITEMS REQUIRED FOR PROPER AND COMPLETE <br />REINSTALLATION. WHERE DAMAGE OCCURS, THE <br />INSTALLATION. <br />EQUIPMENT SHALL BE REPLACED OR REPAIRED <br />TO THE SATISFACTION AND APPROVAL OF THE <br />5. "WIRING": RACEWAY, FITTING, WIRE, BOXES AND <br />ARCHITECT AT NO ADDITIONAL COST TO THE <br />RELATED ITEMS. <br />OWNER. <br />6. "CONCEALED": EMBEDDED IN MASONRY OR OTHER <br />E) PROVIDE FOR CUTTING, PATCHING AND <br />CONSTRUCTION, INSTALLED IN FURRED SPACES, <br />RESTORATION OF EXISTING FINISHES. <br />WITHIN DOUBLE PARTITIONS OR HUNG CEILINGS, IN <br />TRENCHES, IN CRAWL SPACES OR IN ENCLOSURES. <br />F) PROVIDED FOR REMOVAL, DISPOSAL AND SALVAGE <br />OF EQUIPMENT FROM JOB SITE. <br />7. "EXPOSED": NOT INSTALLED UNDERGROUND OR <br />"CONCEALED" AS DEFINED ABOVE. <br />G)PROVIDE FOR CLEANING, TESTING AND REPAIR OF <br />8. "EQUAL": EQUAL IN MATERIALS, WEIGHT, SIZE, <br />EXISTING EQUIPMENT TO BE REUSED. <br />DESIGN AND EFFICIENCY OF SPECIFIED PRODUCT. <br />3. PERFORM A COMPREHENSIVE FIELD INSPECTION OF <br />D. SCOPE OF WORK: PROVIDE LABOR, MATERIALS, <br />THE EXISTING CONDITIONS TO THOROUGHLY <br />TOOLS, EQUIPMENT, SERVICES AND FEES NECESSARY <br />FAMILIARIZE HIMSELF WITH THE PROJECT AND <br />FOR COMPLETE SAFE INSTALLATION IN CONFORMITY <br />DETERMINE THE COMPLETE SCOPE OF NEW AND <br />WITH APPLICABLE CODES AND REQUIREMENTS OF <br />DEMOLITION WORK. THE CONTRACTOR SHALL <br />AUTHORITIES HAVING JURISDICTION AS INDICATED ON <br />VERIFY IN THE FIELD EXACT SIZES, CAPACITIES <br />DRAWINGS AND HEREIN SPECIFIED. <br />AND LOCATIONS OF ALL EXISTING EQUIPMENT <br />PRIOR TO INSTALLATION OF ANY PROPOSED WORK. <br />E. THE CONTRACTOR SHALL SECURE ALL PERMITS, <br />PROPOSED WORK SHALL BE COORDINATED WITH <br />APPROVALS AND PAY ALL FEES FOR ALL WORK <br />EXISTING CONDITIONS TO ASSURE PROPER <br />INSTALLED. CERTIFICATES SHALL BE DELIVERED TO <br />INSTALLATION. THIS FIELD SURVEY AND <br />THE OWNER BEFORE FINAL PAYMENT WILL BE MADE. <br />DETERMINATION OF THE COMPLETE SCOPE OF <br />F. THE ELECTRICAL WORK SHALL COMPLY WITH THE <br />WORK SHALL BE PERFORMED PRIOR TO THE FINAL <br />NATIONAL ELECTRICAL CODE, NFPA 70, CURRENTLY IN <br />BID. SPECIFIC ATTENTION IS BROUGHT TO <br />FORCE, AND ALL AMENDMENTS THERE TO. <br />PHYSICALLY LARGER AND HEAVY PIECES OF <br />EQUIPMENT THAT ARE NEW TO BE INSTALLED OR <br />G. ALL MATERIALS SHALL BE UL LISTED. <br />EXISTING TO BE REMOVED AND THE ROUTING OF <br />1.3 ORDINANCES, CODES AND CLIENT STANDARDS <br />SUCH EQUIPMENT WITH THE AVAILABLE MEANS AND <br />SITE CONDITIONS. <br />A. COMPLY WITH NATIONAL FIRE PROTECTION ASSOCIATION <br />(NFPA) STANDARDS, STATE AND LOCAL BUILDING <br />4. THE CONTRACTOR SHALL REMOVE ALL EXISTING <br />CODES AND ALL OTHER APPLICABLE CODES AND <br />ELECTRICAL EQUIPMENT AND ASSOCIATED <br />ORDINANCES FOR PERFORMANCE, WORKMANSHIP, <br />ACCESSORIES WHETHER SPECIFICALLY INDICATED OR <br />EQUIPMENT AND MATERIALS. ADDITIONALLY, COMPLY <br />NOT THAT ARE NOT LONGER REQUIRED. ANY <br />WITH ROLES AND REGULATIONS OF PUBLIC UTILITIES <br />EQUIPMENT WHICH MUST REMAIN AS PART OF AN <br />ACTIVE SYSTEM AND IS IN CONFLICT WITH THE <br />THOSE AREAS. <br />PROPOSED WORK SHALL BE RELOCATED AT NO <br />21.ALL EXISTING ELECTRICAL EQUIPMENT, CONDUITS <br />ADDITIONAL EXPENSE. THERE SHALL BE NO <br />AND WIRING THAT INTERFERE WITH ANY NEW <br />ADDITIONAL EXPENSE TO THE OWNER FOR THIS <br />CONSTRUCTION SHALL BE RELOCATED OR <br />TYPE OF DEMOLITION WORK, UNLESS, IN THE <br />REROUTED AS REQUIRED TO CLEAR THE NEW <br />ARCHITECT'S AND OWNER'S OPINION, IT IS BEYOND <br />CONSTRUCTION. RECONNECT ALL EXISTING <br />THE SCOPE AND INTENT OF THE CONTRACT <br />EQUIPMENT THAT ARE TO REMAIN AND ARE NOT <br />DOCUMENTS. <br />AFFECTED BY THE NEW CONSTRUCTION, TO THE <br />5. COOPERATE AND COORDINATE DEMOLITION OF <br />NEWLY RELOCATED OR REROUTED SYSTEM TO <br />DIVISION 16 SYSTEMS AS REQUIRED WITH ALL <br />ENSURE A SAFE AND OPERATIONAL SYSTEM IS <br />OTHER TRADES. THE CONTRACTOR SHALL <br />PROVIDED. <br />SUPERVISE AND ASSIST IN THE REMOVING AND <br />&DISCONNECT AND RECONNECT THE EXISTING <br />REPLACING OF EXISTING MATERIALS FOR <br />ELECTRICAL EQUIPMENT AS REQUIRED BY THE <br />INSTALLATION OF ELECTRICAL ITEMS AND ITEMS <br />CONSTRUCTION MODIFICATIONS. <br />RELATED TO ALL OTHER TRADES. <br />1.5 COORDINATION <br />6. NORMAL FUNCTIONS OF OCCUPIED AREAS MUST <br />CONTINUE DURING THE CONSTRUCTION PHASES. <br />A. COORDINATE ARRANGEMENT, MOUNTING AND SUPPORT <br />EVERY EFFORT SHALL BE MADE TO INSURE SUCH <br />OF ELECTRICAL EQUIPMENT: <br />FUNCTIONS ARE NOT DISTURBED. THE <br />1. TO ALLOW MAXIMUM POSSIBLE HEADROOM UNLESS <br />CONTRACTOR SHALL BE RESPONSIBLE FOR THE <br />SPECIFIC MOUNTING HEIGHTS THAT REDUCE <br />INSTALLATION AND REMOVAL OF TEMPORARY <br />HEADROOM ARE INDICATED. <br />SYSTEMS AS REQUIRED TO MAINTAIN THE <br />FUNCTIONS OF OCCUPIED AREAS. THE <br />2. TO PROVIDE FOR EASE OF DISCONNECTING THE <br />CONTRACTOR SHALL SCHEDULE ANY WORK WHICH <br />EQUIPMENT WITH MINIMUM INTERFERENCE TO <br />MAY BE REQUIRED IN OCCUPIED AREAS DURING <br />OTHER INSTALLATIONS. <br />UNOCCUPIED HOURS. <br />3. TO ALLOW RIGHT OF WAY FOR PIPING AND <br />7. WHERE REQUIRED BY APPLICABLE HEALTH AND <br />CONDUIT INSTALLED AT REQUIRED SLOPE. <br />SAFETY REGULATIONS, THE CONTRACTOR SHALL <br />4. SO CONNECTING RACEWAYS, CABLES, WIREWAYS, <br />FURNISH AND MAINTAIN SAFETY AND DUST <br />CABLE TRAYS AND BUSWAYS WILL BE CLEAR OF <br />BARRIERS. <br />OBSTRUCTIONS AND OF THE WORKING AND ACCESS <br />8. DEMOLITION SHALL BE CARRIED OUT WITH CAUTION <br />SPACE OF OTHER EQUIPMENT. <br />TO ASSURE THAT EXISTING CONDITIONS TO REMAIN <br />B. COORDINATE INSTALLATION OF REQUIRED SUPPORTING <br />WILL BE UNDAMAGED. EXISTING CONDITIONS TO <br />DEVICES AND SET SLEEVES IN CAST -IN -PLACE <br />REMAIN THAT ARE DAMAGED OR DEFACED BY WORK <br />CONCRETE, MASONRY WALLS AND OTHER STRUCTURAL <br />UNDER THIS CONTRACT SHALL BE RESTORED OR <br />COMPONENTS AS THEY ARE CONSTRUCTED. <br />REPLACED EQUAL TO THE CONDITIONS AT THE <br />C. COORDINATE LOCATION OF ACCESS PANELS AND <br />TIME OF AWARD OF THE CONTRACT. <br />DOORS FOR ELECTRICAL ITEMS THAT ARE BEHIND <br />9. CUT, PATCH AND RESTORE ALL EXISTING SURFACES <br />FINISHED SURFACES OR OTHERWISE CONCEALED. <br />NOT RECEIVING NEW FINISHES THAT HAVE BEEN <br />D. PROVIDE SLEEVES WITH APPLICABLE FIRESTOPPING <br />DISTURBED DURING EXECUTION OF THIS CONTRACT. <br />FOR ALL PENETRATIONS. <br />MATERIALS AND FINISHES USED SHALL BE SIMILAR, <br />IN ALL RESPECT, TO ADJACENT SURFACES. <br />1.6 QUALITY ASSURANCE <br />t 0. EXISTING CONDUIT AND WIRING WHICH ARE TO <br />A. QUALITY AND GAUGES OF MATERIALS: <br />REMAIN AS PART OF AN EXISTING OR PROPOSED <br />1. NEW, BEST OF THEIR RESPECTIVE KINDS, FREE <br />ACTIVE SYSTEM THAT THE CONTRACTOR DETERMINES <br />FROM DEFECTS AND LISTED BY UNDERWRITERS <br />TO BE DEFECTIVE SHALL BE BROUGHT TO THE <br />LABORATORIES, INC., OR BEARING THEIR LABEL <br />ATTENTION OF THE ENGINEER. <br />2. MATERIALS AND EQUIPMENT OF SIMILAR <br />11.IXISTING EQUIPMENT TO BE REMOVED SHALL BE <br />APPLICATION: SAME MANUFACTURER, EXCEPT AS <br />CLEANED, REPAIRED AND REUSED AT THE <br />NOTED. <br />DISCRETION OF THE ENGINEER WHEREVER <br />APPLICABLE. <br />B. VOLTAGE CHARACTERISTICS: <br />12. CONNECTIONS TO EXISTING WORK SHALL BE <br />1. 208Y/120 VOLTS, 60 HERTZ WITH GROUNDED <br />SIMILAR, IN ALL RESPECTS, TO THE EXISTING <br />NEUTRAL <br />SYSTEM AND CONDITIONS UNLESS OTHERWISE <br />1.7 PRODUCT DELIVER, STORAGE AND HANDLING <br />INDICATED. EXISTING WORK SHALL BE ALTERED <br />AND/OR TEMPORARILY REMOVED AND REPLACED AS <br />A. MOVING OF EQUIPMENT. WHERE NECESSARY, SHIP IN <br />REQUIRED FOR COMPLETION OF REQUIREMENTS OF <br />CRATED SECTIONS OF SIZE TO PERMIT PASSING <br />THE PROJECT. <br />THROUGH AVAILABLE SPACES. <br />13. THE OWNER ASSUMES NO RESPONSIBILITY FOR <br />B. ACCESSIBILITY: <br />LOSS OR DAMAGE TO MATERIALS OR STRUCTURES <br />1. FOR OPERATION, MAINTENANCE AND REPAIR. <br />ON SITE FOR THE SALVAGE VALUE OF EQUIPMENT <br />2. MINOR DEVIATIONS: PERMISSIBLE. <br />WHICH THE CONTRACTOR MAY HAVE REFLECTED IN <br />HIS BID. <br />3. CHANGES OF MAGNITUDE OR INVOLVING EXTRA <br />14. REMOVE FROM JOB SITE AND PROPERLY DISPOSE <br />COST: NOT PERMISSIBLE WITHOUT REVIEW. <br />ALL EXISTING ELECTRICAL EQUIPMENT, CONDUIT <br />4. GROUP CONCEALED ELECTRICAL EQUIPMENT <br />AND WIRING REMOVED DURING CONSTRUCTION NO <br />REQUIRING ACCESS WITH EQUIPMENT FREELY <br />LONGER REQUIRED AS PART OF AN ACTIVE <br />ACCESSIBLE THROUGH ACCESS DOORS. <br />SYSTEM AND NOT TO BE REUSED. <br />1.8 SUBMITTALS <br />15. CLEAR AWAY ALL DEBRIS AND DEMOLISHED <br />A. SUBMIT SHOP DRAWINGS AND PRODUCT DATA FOR <br />MATERIAL AT FREQUENT INTERVALS. THE <br />ENGINEER'S REVIEW PRIOR TO PURCHASING ANY <br />CONTRACTOR SHALL NOT ALLOW DEBRIS TO <br />EQUIPMENT IN ACCORDANCE WITH GENERAL <br />ACCUMULATE TO THE EXTENT THAT IT WILL <br />REQUIREMENTS SPECIFIED IN ARCHITECTURAL <br />INTERFERE WITH WORK, PASSAGE OF THE <br />SPECIFICATIONS. ALL SUBMITTALS SHALL BE <br />WORKMEN AND THE OPERATION OF THE EXISTING <br />HIGHLIGHTED TO INDICATE SPECIFIC PRODUCTS OR <br />OCCUPIED AREAS. <br />MATERIALS BEING USED. PROVIDE (1) ELECTRONIC <br />16.IT IS THE INTENT OF THIS SPECIFICATION THAT ALL <br />COPY OF SUBMITTAL MATERIAL WITH DESCRIPTIVE DATA <br />WORK, INCLUDING THE INSIDE OF EQUIPMENT, IS <br />FOR ALL PRODUCTS AND MATERIALS, INCLUDING BUT <br />LEFT IN A CLEAN CONDITION. ALL CONSTRUCTION <br />NOT LIMITED TO THE FOLLOWING, PRIOR TO <br />DIRT AND DEBRIS SHALL BE REMOVED FROM <br />INSTALLATION: CIRCUIT BREAKERS, SAFETY SWITCHES, <br />MATERIAL AND EQUIPMENT. <br />LIGHTING FIXTURES, LIGHTING CONTROLS, FIRE ALARM, <br />17. PROVIDE A DETAILED INVENTORY OF ALL EXISTING <br />RACEWAYS AND WIRE. <br />ELECTRICAL EQUIPMENT IN SCOPE OF WORK, TO <br />1.9 MAINTENANCE MANUALS AND AS -BUILT DRAWING <br />BE STORED FOR LATER REUSE. INVENTORY SHALL <br />INCLUDE TYPE, SIZE, CAPACITIES AND QUANTITIES <br />A. PROVIDE (1) ELECTRONIC COPY AND (1) HARD COPY <br />OF EACH ITEM OR PIECE OF EQUIPMENT. <br />OF OPERATING AND MAINTENANCE MANUALS FOR <br />OWNER'S USE FOR EACH PIECE OF EQUIPMENT. <br />18. EQUIPMENT TESTING: EXISTING EQUIPMENT, <br />EACH ITEM SHALL BE CROSS-REFERENCED AND <br />INSTRUMENTS AND ACCESSORIES TO REMAIN SHALL <br />NUMBERED WITH AS -BUILT DRAWING DESCRIPTIONS. <br />BE TESTED FOR DEFECTS AND SHALL BE <br />ADJUSTED, REPAIRED OR REPLACED WHERE <br />B. AS -BUILT DRAWING: DELIVER TO OWNER, TWO SETS <br />REQUIRED. CONDITIONS, QUALIFICATIONS AND <br />OF RED -LINED PLANS SHOWING ACTUAL FIELD <br />PROCEDURES REGARDING ADJUSTMENTS OR <br />INSTALLATION. <br />REPLACEMENT OF EXISTING EQUIPMENT AS DEEMED <br />PART 2 - PRODUCTS <br />NECESSARY BY THE CONTRACTOR SHALL BE <br />SUBMITTED TO THE ARCHITECT FOR APPROVAL <br />2.1 GENERAL <br />THE CONTRACTOR SHALL NOT PROCEED WITH <br />A. NAMEPLATES: <br />EQUIPMENT REPLACEMENT WITHOUT THE WRITTEN <br />APPROVAL OF THE ARCHITECT. THE ARCHITECT <br />1 • FASTENED WITH STAINLESS STEEL SELF TAPPING <br />SHALL DETERMINE WHETHER REPLACEMENT IS <br />SCREWS, ENGRAVED BLACK LAMACOID SHEET WITH <br />REQUIRED AND SHALL SPECIFY THE REPLACEMENT <br />3/8 IN. WHITE LETTERING FOR UTILITY POWER, <br />EQUIPMENT TO BE USED. <br />RED WITH WHITE LETTERS FOR EMERGENCY <br />EQUIPMENT, BLUE WITH WHITE LETTERING FOR UPS, <br />19. ADDITIONAL REQUIREMENTS: FOR BREAKERS, <br />OR BUILDING STANDARD. <br />CONDUCTORS, PANELBOARDS, ETC., REFER TO THE <br />APPROPRIATE SPECIFICATION SECTION FOR TESTING <br />2. INSPECTION: SUBJECT TO REVIEW, INDICATING <br />REQUIREMENTS AND ADDITIONAL REQUIREMENTS OF <br />EQUIPMENT, AMPERAGE AND VOLTAGE. <br />EXISTING EQUIPMENT AND SYSTEMS TO BE PART <br />3. PROVIDE FOR: <br />OF THE NEW ACTIVE SYSTEMS. <br />A) DISCONNECT SWITCHES. <br />20.REMOVE ALL UNUSED CONDUITS AND WIRING, <br />SWITCHES, RECEPTACLES, LIGHT FIXTURES, ETC., <br />B) CIRCUIT BREAKERS. <br />WHERE CEILINGS, CEILING TILES OR WALLS ARE <br />C)CABINETS. <br />BEING DEMOLISHED. REMOVE ALL POWER WIRING <br />BACK TO ITS OVERCURRENT DEVICE AND MARK <br />D) EQUIPMENT PANELS. <br />CIRCUIT BREAKERS AS "SPARE". INSTALL BLANK <br />COVERS ON ALL BOXES. REFER TO DRAWINGS <br />B. CIRCUIT IDENTIFICATION: <br />FOR ADDITIONAL REQUIREMENTS. WHERE WALLS <br />1. PROVIDE PANEL AND CIRCUIT IDENTIFICATION FOR <br />AND CEILING ARE TO REMAIN, MAINTAIN EXISTING <br />EACH ELECTRICAL RECEPTACLE, EXPOSED JUNCTION <br />CONDUIT, WIRING AND BOXES SERVING ALL <br />BOX, POWER POLE AND FLOOR PENETRATION. <br />ELECTRICAL EQUIPMENT, OUTLETS AND SWITCHES IN <br />2. IDENTIFICATION SHALL BE A SELF ADHESIVE, WHITE <br />STICKER WITH BLACK LETTERING, 3/16" HIGH, <br />ARIAL FONT. <br />3. INCLUDE THE FULL PANEL NAME AND CIRCUIT <br />NUMBER ON EACH STICKER (EXAMPLE "R2A-12") <br />4. FASTEN STICKER TO THE VISIBLE PORTION OF <br />EACH DEVICE COVER, SQUARE WITH DEVICE. <br />5. DO NOT PLACE STICKER OVER ANY FASTENING <br />SCREWS OR ACROSS AND COVER JOINTS/SEAMS. <br />C. SUPPORTS: <br />1. SUPPORT FROM BUILDING CONSTRUCTION: BEAM <br />CLAMPS, STEEL FISHPLATES (IN CONCRETE FILL <br />ONLY) OR CANTILEVER BRACKETS. <br />2. GROUPED LINES AND SERVICES: TRAPEZE <br />HANGERS OF BOLTED ANGLES OR CHANNELS. <br />3. WHERE BUILDING CONSTRUCTION IS INADEQUATE, <br />PROVIDE ADDITIONAL FRAMING. <br />4. SHALL COMPLY WITH SEISMIC REQUIREMENTS OF <br />THE BUILDING CODE. <br />5. FIELD FABRICATION: <br />A) WHERE FIELD CUTTING OF STANDARD LENGTHS <br />OF CHANNEL ARE REQUIRED, MAKE CUTS <br />STRAIGHT AND PERPENDICULAR TO <br />MANUFACTURED SURFACES. <br />B)FOR FIELD -CUT OR DAMAGED SURFACES OF <br />COATED CHANNELS, DRESS CUT ENDS, DAMAGED <br />SURFACES, OR BOTH, WITH AN ABRASIVE <br />MATERIAL (E.G. FILE, GRINDING STONE OR <br />SIMILAR) AND CLEANER TO REMOVE OILS, RUST, <br />SHARP EDGES AND SHARDS. <br />C)FOR CHANNEL WITH FACTORY -APPLIED COATING, <br />RE -FINISH CUT EDGES WITH A COATING <br />COMPATIBLE WITH THE FACTORY FINISH AND AS <br />RECOMMENDED BY THE MANUFACTURER (E.G. <br />MANUFACTURER'S TOUGH -UP PAINT OR <br />ZINC -RICH COLD -GALVANIZING COMPOUND, AS <br />APPLICABLE). <br />D. FIRE STOPPING FLOOR AND WALL PENETRATIONS <br />1. FIRE RESISTANT PENETRATION SEALANTS: TWO <br />PART, FORMED IN PLACE, SILICONE SEALANT <br />FORMULATED FOR USE IN THROUGH PENETRATION <br />FIRE STOPPING AROUND CABLES, RACEWAYS AND <br />CABLE TRAY PENETRATIONS THROUGH FIRE RATED <br />WALLS AND FLOORS. SEALANTS AND ACCESSORIES <br />SHALL HAVE FIRE RESISTANCE RATINGS INDICATED, <br />AS ESTABLISHED BY TESTING IDENTICAL <br />ASSEMBLIES IN ACCORDANCE WITH ASTM E 418, <br />BY UNDERWRITER'S LABORATORIES, INC., OR OTHER <br />ACCEPTABLE TO AUTHORITY HAVING JURISDICTION. <br />2. SLEEVES FOR RACEWAYS AND CABLES: <br />A) STEEL PIPE SLEEVES: ASTM A 53/A 53 M, <br />TYPE E, GRADE B, SCHEDULE 40, GALVANIZED <br />STEEL, PLAIN ENDS AND DRIP RINGS. <br />B) CAST-IRON PIPE SLEEVES: CAST OR FABRICATED <br />"WALL PIPE" EQUIVALENT TO DUCTILE -IRON <br />PRESSURE PIPE, WITH PLAIN ENDS AND INTEGRAL <br />WATERSTOP, UNLESS OTHERWISE INDICATED. <br />3. SLEEVES FOR RECTANGULAR OPENINGS: <br />GALVANIZED SHEET STEEL WITH MINIMUM <br />0.052-INCH THICKNESS AS INDICATED AND OF <br />LENGTH TO SUIT APPLICATION. <br />2.2 MATERIALS <br />A. RACEWAYS: <br />1. ELECTRICAL METALLIC TUBING (EMT): THIN WALL <br />PIPE, GALVANIZED THREADLESS. COLORED EMT IS <br />NOT ALLOWED UNLESS OTHER WISE NOTED. <br />2. INTERMEDIATE METAL CONDUIT (IMC): GALVANIZED, <br />THREADED. <br />3. RIGID STEEL CONDUIT (GRC): FULL WIGHT PIPE, <br />GALVANIZED, THREADED. <br />4. WIRE BASKET CABLE TRAY: WIDTH AS INDICATED <br />- 6" HIGH WIRE MESH CABLE TRAY. <br />A)PROVIDE ELECTRO-PLATED ZINC GALVANIZING <br />FINISH. <br />B) USING 12" RADIUS, 90 DEGREE BENDS AND 1" <br />FITTING. DESIGN FOR 120 LBS PER FOOT <br />LOADING CAPACITY. <br />C) PROVIDE ALL REQUIRED MOUNTING ACCESSORIES, <br />CONNECTOR PLATES, SPLICE PLATES, ETC. FOR A <br />COMPLETE INSTALLATION. <br />D) TRAY SHOULD BE ELECTRICALLY CONTINUOUS <br />AND BONDED TO BUILDING GROUND. <br />E)TRAY TO BE BY COOPER B-LINE OR APPROVED <br />EQUAL <br />B. FITTINGS AND ACCESSORIES: <br />1. RACEWAY FITTINGS: <br />A) EMT FITTINGS: ROLLED STEEL, STEEL <br />SET -SCREW TYPE. <br />B) FLEXIBLE METALLIC CONDUIT: ANGLE WEDGE <br />TYPE WITH INSULATED THROAT. <br />C)BUSHING: METALLIC INSULATED TYPE. <br />D) IMC AND GRC: THREADED. <br />C. BOXES: <br />1. OUTLET BOXES: EXCEPT AS OTHERWISE REQUIRED <br />BY CONSTRUCTION, DEVICES OR WIRING. <br />A) FORM TYPE WELDED TYPE IS NOT PERMITTED. <br />B) LIGHTING FIXTURES: 4" SQUARE, 1-1/2" DEEP <br />ABOVE CEILING AND 2-1/8" DEEP IN WALL <br />C)TELEPHONE AND DATA: 4-11/16", 2-1/8" <br />DEEP IN WALL <br />D) WITH RAISED COVERS AND FIXTURE STUDS <br />WHERE REQUIRED. <br />E) THROUGH -THE -WALL TYPE NOT PERMITTED. <br />F) PROVIDED COVER FOR BOXES WITHOUT FIXTURE <br />OR DEVICE. <br />G) FIRE ALARM BOXES SHALL BE PAINTED RED. <br />H)MARK CIRCUIT NUMBERS ON ALL JUNCTION BOX <br />COVERS ABOVE CEILING. <br />2. JUNCTION AND PULL BOXES: <br />A) GALVANIZED SHEET STEEL. <br />B) COVERS: SCREW -ON, EXCEPT AS NOTED. <br />C)PROVIDE INSULATED SUPPORTS FOR CABLES. <br />D) LOCATION: AS NOTED OR REQUIRED AND <br />ACCESSIBLE. <br />E) PROVIDE BARRIERS BETWEEN: <br />1) 480Y/277 VOLT WIRING ENERGIZED FROM <br />SEPARATE SERVICES. <br />2) 280Y/120 VOLT AND 480Y/277 VOLT WIRING. <br />3) EMERGENCY AND NORMAL WIRING. <br />F) PROVIDE BARRIERS IN EXISTING BOXES BETWEEN: <br />1) 480Y/277 VOLT WIRING ENERGIZED FROM <br />SEPARATE SERVICES. <br />2) 208Y/120 VOLT AND 4BOY277 VOLT WIRING. <br />3) EMERGENCY AND NORMAL POWER WIRING. <br />D. WIRE AND CABLE- <br />1. CONDUCTORS: <br />A) ASTM STANDARD SOLID NO. 10 AND SMALLER, <br />STRANDED NO. 8 AND LARGER. <br />B) TYPE: COPPER; ALUMINUM SHALL NOT BE USED. <br />C)GENERAL USE: <br />1) NO. 12 MINIMUM UNLESS OTHERWISE NOTED. <br />2)NO. 10 MINIMUM UNLESS OTHERWISE NOTED. <br />D)CONTROL AND ALARM, EXCEPT AS NOTED: <br />1) NO. 14 MINIMUM <br />2) NO. 12 MINIMUM FOR 120 VOLT CIRCUITS <br />OVER 200 FEET. <br />E) OTHER VOLTAGES AND PHASE: AS REQUIRED TO <br />MAINTAIN VOLTAGE DROP. <br />F) INCREASE RACEWAY SIZES FOR LARGER WIRE AS <br />REQUIRED. <br />2. INSULATION: <br />A) THWN/THHN: FEEDERS AND BRANCH CIRCUITS <br />EXCEPT AS NOTED. <br />B)THHN/YHWN-2: UNDERGROUND AND OUTDOORS. <br />C) SFF-2: BRANCH CIRCUITS LOCATED IN: <br />1) WIRING CHANNELS OF CONTINOUS <br />FLUORESCENT FIXTURES. <br />2) AMBIENT TEMPERATURES OVER 75 DEGREE C. <br />D) COLOR CODING: CONDUCTORS SHALL BE COLOR <br />CODED ON THE BASIS OF VOLTAGE <br />1) 480/277: BROWN - PHASE A, ORANGE - <br />PHASE B, YELLOW - PHASE C, GRAY - <br />NEUTRAL, GREEN WITH YELLOW STRIPE - <br />GROUND. <br />2) 208/120: BLACK - PHASE A, RED - PHASE <br />B, BLUE - PHASE C, WHITE - NEUTRAL, <br />GREEN - GROUND. <br />3) WHERE COLOR INSULATION IS NOT AVAILABLE, <br />APPLY COLOR TAPE OVERLAPPING 6" MINIMUM <br />LENGTH IN ALL ACCESSIBLE LOCATIONS. <br />E) 600 VOLT INSULATION, INCLUDING CONTROL <br />WIRING. <br />3. ACCESSORIES: <br />A) TAG: <br />1) FLAMEPROOF LINEN OR FIBER IN ACCESSIBLE <br />LOCATIONS. <br />2) FEEDERS: INDICATE FEEDER NUMBER, SIZE, <br />PHASE AND POINTS OF ORIGIN AND <br />TERMINATIONS. <br />3) CONTROL AND ALARM WIRING: INDICATE TYPE <br />(CONTROL OR ALARM), SIZE OF WIRE, AND <br />POINTS OF ORIGIN AND TERMINATIONS. <br />B) TERMINATIONS, SPLICES AND TAPS UNDER 600 <br />VOLTS: <br />1) COPPER CONDUCTORS NO. 10 AND SMALLER: <br />COMPRESSION -TYPE OR TWIST -ON SPRING <br />LOADED CONNECTORS AND CLEAR <br />NYLON -INSULATED COVERING. <br />2) COPPER CONDUCTORS NO. 8 AND LARGER: <br />HYDRAULIC CIRCUMFERENTIAL COMPRESSION <br />TYPE USING MANUFACTURER'S RECOMMENDED <br />TOOLING. <br />3) CABLE LUGS AND CONNECTORS: <br />COMPRESSION TYPE OF SAME METAL AS <br />CONDUCTOR. PROVIDE TO MATCH CABLE, WITH <br />MARKING INDICATING SIZE AND TYPE. <br />4) COPPER LUG CONNECTIONS TO BUS BARS: <br />USE ANTI -SEIZE COMPOUND ON TANG. <br />E. DEVICES: <br />1. WIRING DEVICES SHALL BE MANUFACTURED BY <br />HUBBELL OR APPROVED EQUAL <br />A) CONVENIENCE RECEPTACLES: 125V, 20AMP, <br />MATCH BUILDING STANDARD. <br />B) GFCI RECEPTACLES: 125V, 20AMP, STRAIGHT <br />BLADE, NON -FEED THROUGH TYPE, MATCH <br />BUILDING STANDARD. <br />C) LIGHTING SWITCHES: 120/277V, 20A, MATCH <br />BUILDING STANDARD. <br />2. NYLON SPECIFICATION GRADE. <br />3. SIDE OR BACK WIRED <br />4. PROVIDE AS INDICATED ON DRAWINGS. <br />5. WHERE DEVICES ARE GROUPED, PROVIDE GANGED <br />PLATES. <br />6. DEVICE COLORS AND PLATES SHALL BE IVORY TO <br />MATCH BUILDING STANDARD. <br />F. DISCONNECT SWITCHES: <br />1. FUSED OR NON -FUSED AS NOTED. <br />2. VOLTAGE AS REQUIRED. <br />3. HEAVY DUTY, EXCEPT AS NOTED <br />4. HORSEPOWER RATED FOR MOTOR LOADS. <br />5. TOGGLE TYPE: <br />A) NON -FUSED, LOAD BREAK. <br />B) MAXIMUM RATINGS: <br />1) 20 AMP AT 600 VOLTS <br />2) 30 AMP AT 250 VOLTS. <br />C)2 POLE EQUAL TO SQUARE D - CLASS 2510, <br />NO. KG1. <br />D) 3 POLE: EQUAL TO SQUARE D - CLASS 2510, <br />NO. KG2. <br />6. KNIFE -BLADE TYPE: <br />A) LOAD BREAK, QUICK-MAKE/QUICK-BREAK, UL <br />CLASS R UP TO 600 AMPS. <br />B) MAXIMUM RATING EXCEPT AS NOTED: 800 AMP. <br />C) ARC QUENCHERS. <br />D)INDIVIDUALLY MOUNTED: EQUAL TO GENERAL <br />ELECTRIC "TH" OR EQUAL. <br />E) PANELBOARD OR SWITCHBOARD MOUNTED: <br />EQUAL TO GENERAL ELECTRIC "QMR" OR EQUAL. <br />7. ENCLOSURES: <br />A) DEAD FRONT. <br />B) NEMA TYPE 1 - INDOORS <br />C)NEMA TYPE 3R - OUTDOORS <br />D)NEMA TYPE 4X STAINLESS STEEL - OUTDOOR AS <br />NOTED. <br />8. FUSES: <br />A)FOR MOTOR AND TRANSFORMER LOADS: <br />1) CURRENT LIMITING, DUAL ELEMENT, TIME DELAY <br />TYPE, MAXIMUM RATING 600 AMP AT REQUIRED <br />VOLTAGE. <br />2) 200,000 AMP INTERRUPT RATING: EQUAL TO <br />BUSSMAN FUSETRON FRN OR FRS OR <br />LO-PEAK FPN OR LPS (UL CLASS R). <br />B)FOR OTHER LOADS: <br />1) CURRENT LIMITING, DUAL ELEMENT TYPE. <br />2)200.000 AMP INTERRUPT RATING: EQUAL TO <br />BUSSMAN LIMITRON LIPS OR LPN (UL CLASS <br />RK1, UP TO 600 AMP; CLASS L, OVER 600 <br />AMP). <br />C)PROVIDE ALL FUSES FROM THE SAME <br />MANUFACTURER. <br />D) PROVIDE 1 SPARE MATCHING FUSE FOR EACH <br />SET OF 3. <br />G. CIRCUIT BREAKERS: <br />1. MOLDED CASE: <br />A) THERMAL -MAGNETIC, QUICK-MAKE/QUICK-BREAK, <br />EXCEPT WHERE SPECIFIED WITH ELECTRONIC TRIP <br />OR 100% RATING. <br />B) MANUALLY OPERATED WITH INSULATED TRIP -FREE <br />HANDLE <br />C) MULTI -POLE TYPES WITH INTERNAL TRIP BAR. <br />D)TERMINALS: UL LISTED FOR 75 DEGREE C AND <br />SUITABLE FOR COPPER CABLE. <br />E) ENCLOSURE: <br />1) DEAD FRONT. <br />2) NEMA TYPE 1 - EXCEPT AS NOTED. <br />F) FRAMES, INTERRUPT RATING AND <br />INTERCHANGEABLE TRIPS: <br />1)120 VOLTS, 100 AMP FRAME: INTERRUPTING <br />CAPACITY AND NUMBER OF POLES AS <br />INDICATED ON DRAWINGS. <br />2) 277 VOLTS, 100 AMP FRAME: INTERRUPTING <br />CAPACITY AND NUMBER OF POLES AS <br />INDICATED ON DRAWINGS. <br />H. GROUNDING: <br />1. GROUNDING CLAMPS SHALL BE BRONZE, <br />SOLDERLESS TYPE WITH BRONZE SCREWS SUITABLE <br />FOR RECEIVING REQUIRED OR NOTED CONDUCTORS. <br />2. GROUNDING WIRES SHALL BE UL AND NEC <br />APPROVED TYPES, COPPER, WITH INSULATION <br />COLOR IDENTIFIED GREEN, EXCEPT WHERE <br />OTHERWISE SHOWN ON THE DRAWINGS, OR <br />SPECIFIED. WIRES SHALL BE SOLID FOR 110 AND <br />SMALLER, STRANDED FOR SIZES #8 AND LARGER. <br />3. PARTS OF THE ELECTRICAL INSTALLATION TO BE <br />GROUNDED SHALL INCLUDE, BUT NOT BE LIMITED <br />TO THE FOLLOWING: CONDUIT SYSTEM FOR LIGHT <br />AND POWER, CABINETS, MOTOR FRAMES, HOUSINGS <br />OF ALARM AND CONTROL PANELS AND ASSOCIATED <br />DEVICES, LIGHTING FIXTURES, TELEPHONE SYSTEM, <br />FIRE ALARM SYSTEM, SMOKE DETECTION SYSTEM, <br />INDIVIDUAL STARTERS AND OTHER NON -CURRENT <br />CARRYING METAL PARTS OF ELECTRICAL <br />EQUIPMENT. <br />4. GROUND CONDUCTORS SHALL BE OF SIZES AND <br />MATERIAL IN ACCORDANCE WITH THE REQUIREMENTS <br />OF THE NATIONAL ELECTRICAL CODE. CABLE FOR <br />GROUNDING CONNECTIONS SHALL BE BARE IN <br />ACCORDANCE WITH THE LATEST REVISION OF ASTM <br />DESIGNATIONS B3 AND B8. ALL OPEN BARE <br />GROUNDING CABLE SHALL BE SECURED IN PLACE <br />WITH CLAMPS, CLAMP BACKS AND X INCH BOLTS. <br />5. GROUND WIRES SHALL BE CONTINUOUS WITHOUT <br />SPLICES. THERE SHALL BE NO SOLDERED JOINTS <br />IN ANY GROUND CONNECTION. CONNECTORS, <br />CLAMPS, ETC. SHALL BE SOLDERLESS TYPE. <br />6. ALL CONDUITS SHALL BE TERMINATED IN <br />GROUNDED BUSHING. BOND TO BOX WITH A #6 <br />AWG BARE COPPER WIRE. <br />7. GROUND INTERRUPTED METALLIC RACEWAYS WITH <br />GROUND CONDUCTORS CONNECTED TO METALLIC <br />RACEWAY AT EACH END. <br />8. UPON COMPLETION OF GROUNDING SYSTEM, TEST <br />SYSTEM FOR CONTINUITY AND RESISTANCE TO <br />DEMONSTRATE COMPLIANCE WITH REQUIREMENTS <br />AND SUBMIT CERTIFICATION TO ARCHITECT THAT <br />MATERIAL AND INSTALLATION HAS BEEN PROPERLY <br />INSTALLED. <br />9. INSPECT ALL CONNECTIONS PRIOR TO CONCEALING. <br />10. GROUND BUSHINGS SHALL BE PLATED MALLEABLE <br />IRON BODY, INSULATED, TYPE, RATED 150 <br />DEGREES C. <br />11. GROUND WIRE INSULATION SHALL MATCH THAT OF <br />POWER CONDUCTORS, AND SHALL BE GREEN. <br />CONFORMING TO ASTM B33 AND UL 44. <br />2017 -Humana <br />Zephyrhills Guidance <br />Center <br />7920 GALL BLVD. <br />ZEPHYRHILLS, FL <br />33541 <br />JAY,/ <br />ew <br />GROUP <br />_; N <br />•:�/ <br />A member company of SH Group, Inc. <br />- 96 <br />Syska Hennessy group, Inc <br />O S <br />9000 Southside Blvd. <br />Building 100, 1st Floor <br />= �• ,� OF r <br />����'•�0 •�� <br />A <br />'% fQ �••••'' <br />Jacksonville, FI 32256 <br />Tel: 904.525.8669 <br />• <br />www.syska.com <br />Florida C.O.A. #00001897 <br />JAY J. LANE FL# 71396 <br />1 ISSUE FOR CONSTRUCTION 4/18/18 <br />Delta Issue Description Date <br />Nr. <br />DECLARATIVE STATEMENT: TO THE BEST OF THE ENGINEER'S <br />KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH <br />THE APPLICABLE MINIMUM BUILDING CODES AND THE <br />APPLICABLE FIRE -SAFETY STANDARDS AS DETERMINED BY <br />THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTER <br />533.70 AND CHAPTER 633, FLORIDA STATUTES. <br />Drawn: EF Check: JL Owner Approval: <br />Job No:HUM17390 Scale: NONE <br />ELECTRICAL <br />TitleSPECIFICATIONS <br />Sheet: ■ <br />2 <br />