...CONTINUED
<br />B)TESTED ACCORDING TO NEMA TP 2.
<br />4. K-FACTOR RATING: TRANSFORMERS INDICATED
<br />I. FIRE ALARM SYSTEM
<br />TO BE K-RATED SHALL COMPLY WITH UL 1561
<br />1. FIRE ALARM SYSTEM IS EXISTING. NEW DEVICES
<br />REQUIREMENTS FOR NON -SINUSOIDAL LOAD
<br />SHALL MATCH BUILDING STANDARD.
<br />CURRENT -HANDLING CAPABILITY TO THE DEGREE
<br />DEFINED BY DESIGNATED K-FACTOR.
<br />2. ALL FIRE ALARM DEVICES SHALL BE WHITE IN
<br />COLOR.
<br />A)UNIT SHALL NOT OVERHEAT WHEN CARRYING
<br />FULL -LOAD CURRENT WITH HARMONIC
<br />3. PROVIDE FIRE ALARM SYSTEM DEVICES AND
<br />DISTORTION CORRESPONDING TO DESIGNATED
<br />COMPONENTS NECESSARY FOR A COMPLETE
<br />K-FACTOR.
<br />SYSTEM AND CONNECT TO EXISTING BASE BUILDING
<br />SYSTEM. THE WORK SHALL INCLUDE, BUT NOT
<br />B)INDICATE VALUE OF K-FACTOR ON
<br />LIMITED TO THE FOLLOWING.
<br />TRANSFORMER NAMEPLATE.
<br />A) EMERGENCY SIGNALING AND PAGING
<br />5. FACTORY -ASSEMBLED AND TESTED, AIR-COOLED
<br />SPEAKERS/HORNS.
<br />UNITS FOR 60 HZ SERVICE.
<br />B) FLASHING STROBES.
<br />6. CORES: GRAIN -ORIENTED, NON -AGING SILICON
<br />STEEL.
<br />C)CONDUIT, WIRING, OUTLETS, ETC. REQUIRED
<br />7, ELECTROSTATIC SHIELDING FOR ALL
<br />PROVIDING POWER TO AND INTERCONNECTING ALL
<br />TRANSFORMERS PROVIDED.
<br />COMPONENTS LISTED ABOVE.
<br />8. COILS: CONTINUOUS WINDINGS WITHOUT
<br />4. THE ENTIRE INSTALLATION, INCLUDING MATERIALS
<br />SPLICES EXCEPT FOR TAPS.
<br />AND EQUIPMENT SHALL BE COMPATIBLE WITH
<br />EXISTING BUILDING EQUIPMENT AND MEET OR
<br />A)INTERNAL COIL CONNECTIONS: BRAZED OR
<br />EXCEED THE MINIMUM STANDARDS AND
<br />PRESSURE TYPE.
<br />REQUIREMENTS STATED HERE -IN.
<br />B)COIL MATERIAL: COPPER.
<br />5. ALL EQUIPMENT AND MATERIALS USED SHALL BE
<br />STANDARD COMPONENTS, REGULARLY
<br />8• MANUFACTURER: SUBJECT TO COMPLIANCE
<br />MANUFACTURED AND OF THE SAME MANUFACTURER,
<br />WITH REQUIREMENTS, PROVIDE PRODUCTS BY
<br />AS THE EXISTING BASE BUILDING EQUIPMENT.
<br />THE FOLLOWING:
<br />6. IONIZATION SMOKE SENSORS SHALL BE ANALOG
<br />A)SQUARE D; SCHNEIDER ELECTRIC.
<br />AND FULLY ADDRESSABLE AND SHALL BE MOUNTED
<br />B)GENERAL ELECTRIC
<br />ON A PLUG-IN BASE. SENSORS SHALL BE RATED
<br />FOR THE AIR SPEED AT THE POINT OF
<br />INSTALLATION. BASES SHALL BE COMPATIBLE WITH
<br />K. LIGHTING FIXTURES:
<br />BOTH IONIZATION AND PHOTOELECTRIC SENSORS.
<br />1. FABRICATION AND MANUFACTURE:
<br />7. PHOTOELECTRIC SMOKE SENSORS SHALL BE
<br />ANALOG AND FULLY ADDRESSABLE AND SHALL BE
<br />A) FIXTURES SHALL COMPLY WITH UL STANDARDS.
<br />MOUNTED ON A PLUG-IN BASE. SENSORS SHALL
<br />FIXTURES AHD COMPONENTS SHALL BE UL LISTED
<br />BE RATED FOR THE AIR SPEED AT THE POINT OF
<br />AND LABELED.
<br />INSTALLATION. BASES SHALL BE COMPATIBLE WITH
<br />B) VERIFY TYPES OF CEILING CONSTRUCTION WITH
<br />BOTH IONIZATION AND PHOTOELECTRIC SENSORS.
<br />ARCHITECT PRIOR TO RELEASING FIXTURES FOR
<br />8. ADDRESSABLE CONTROL MODULES SHALL BE FULLY
<br />FABRICATION AND DELIVERY AND PROVIDE
<br />ADDRESSABLE AND MOUNTED WITHIN 3 FEET OF
<br />FIXTURES ADAPTED TO CEILING CONSTRUCTION
<br />THE CONTROLLED DEVICE.
<br />USED.
<br />9. HORNS SHALL PROVIDE SOUND LEVELS 15DBA
<br />C)COORDINATE RECESSED FIXTURE MOUNTING
<br />ABOVE AVERAGE AMBIENT SOUND LEVEL.
<br />APPURTENANCES, FLANGES AND TRIMS WITH
<br />COMBINED LEVEL OF HORNS AND AVERAGE
<br />CONSTRUCTION OF CEILING IN WHICH FIXTURE IS
<br />AMBIENT SOUND LEVEL SHALL NOT EXCEED
<br />TO BE RECESSED. PROVIDE CORRECT FIXTURE
<br />11ODBA.
<br />MOUNTING ASSEMBLY.
<br />10. STROBES SHALL BE FULLY SYNCHRONIZED AND
<br />D) PROVIDE FIXTURES WITH FINISH AS DESCRIBED IN
<br />SHALL HAVE CANDLEPOWER RATINGS DETERMINED
<br />THE LIGHTING FIXTURE SCHEDULE. FINISH SHALL
<br />IN ACCORDANCE WITH UL 1971.
<br />BE APPLIED BY THE FIXTURE MANUFACTURER.
<br />11. COMPLY WITH A.DA AND WITH FLORIDA BUILDING
<br />VERIFY FINAL FINISH REQUIREMENTS BEFORE
<br />CODE REQUIREMENTS.
<br />RELEASING FIXTURES FOR FABRICATION.
<br />12.NEW SPEAKERS AND STROBES LIGHTS SHALL
<br />E)RECESSED FLUORESCENT TROFFERS WITH DOORS
<br />MATCH BUILDING STANDARD.
<br />SHALL HAVE SPRING LOADED DOOR CAM
<br />LATCHES.
<br />13.FIRE ALARM WIRING SHALL BE INSTALLED PER
<br />LOCAL CODE AND NFPA 72.
<br />2. ELECTRONIC FLUORESCENT BALLASTS:
<br />14. THE SYSTEM AND ALL COMPONENTS SHALL BE UL
<br />A) ETL CERTIFIED, CBM AND UL LISTED AND MEET
<br />LISTED AND FM APPROVED SPECIFICALLY FOR
<br />OR EXCEED NEMA AND ANSI STANDARDS.
<br />OPERATION IN CONJUNCTION WITH EACH OTHER
<br />B) CLASS P THERMALLY PROTECTED AND CLASS A
<br />AND WITH THE SUPPRESSION SYSTEM, IF A
<br />SUPPRESSION SYSTEM IS PROVIDED.
<br />SOUND RATED.
<br />15. FIRE ALARM EQUIPMENT SHALL BE USED FOR ITS
<br />C) LOCATED IN FIXTURE WHICH THEY SERVE.
<br />INTENDED PURPOSE ONLY.
<br />D)OPERATE LAMPS AS SCHEDULED AND SHALL
<br />16. SUBMITTALS: SUBMITTALS SHALL CONSIST OF THE
<br />MAINTAIN CONSTANT LIGHT OUTPUT OVER ENTIRE
<br />FOLLOWING DATA TO BE SUBMITTED CONCURRENTLY
<br />OPERATING VOLTAGE RANGE.
<br />AS ONE PACKAGE. SUBMITTALS WHICH DO NOT
<br />E) MAINTAIN THE FOLLOWING PERFORMANCE:
<br />INCLUDE SHOP DRAWINGS WILL BE RETURNED
<br />WITHOUT REVIEW.
<br />1) LAMP CURRENT CREST FACTOR: 1.6
<br />A) COMPLETE POINT TO POINT WIRING DIAGRAM
<br />2) TOTAL HARMONIC DISTORTION: 10%
<br />INDICATING ALL DEVICE ADDRESSES, SIGNAL
<br />3) POWER FACTOR: 0.90
<br />CIRCUITS, AND CONDUCTOR QUANTITIES IN PLAN
<br />VIEW AND RISER STYLE. CONCEPTUAL DIAGRAM
<br />F)ALL BALLASTS FOR ALL LAMPS SHALL BE
<br />WILL BE REJECTED.
<br />PROGRAM START TYPE.
<br />B)THE CONTRACTOR SHALL SUBMIT COMPLETE
<br />G)DIMMING BALLASTS SHALL BE TYPE AND
<br />DOCUMENTATION SHOWING THE TYPE, SIZE,
<br />MANUFACTURER AS INDICATED ON FIXTURE
<br />RATING, STYLE, CATALOG NUMBER,
<br />SCHEDULE.
<br />MANUFACTURER'S NAMES, AND CATALOG DATA
<br />SHEETS, FOR ALL ITEMS TO ENSURE COMPLIANCE
<br />3. LAMPS:
<br />WITH THESE SPECIFICATIONS. REQUIRED COPES
<br />A) PROVIDE LAMPS FROM THE SAME MANUFACTURER
<br />OF THIS INFORMATION SHALL BE SUBMITTED TO
<br />IN ALL FIXTURES WITH SAME LAMP TYPES.
<br />THE ENGINEER AND SHALL BE SUBJECT TO HIS
<br />B) LINEAR FLUORESCENT LAMPS SHALL HAVE A
<br />APPROVAL
<br />MINIMUM CRI OF 80.
<br />C)BATTERY CALCULATIONS (IN ALARM) FOR THE
<br />C)COMPACT FLUORESCENT LAMPS SHALL HAVE A
<br />FACP AND AUDIO AMPLIFIER.
<br />MINIMUM CRI OF 82.
<br />D) CONTRACTOR SHALL DEVELOP DOCUMENTS,
<br />SIGNED AND SEALED BY OTHERS, TO THE LOCAL
<br />PART 3 - EXECUTION
<br />3.1 INSTALLATION
<br />AUTHORITY AS THE LOCAL AUTHORITY REQUIRES
<br />FOR PERMIT.
<br />M. GENERAL
<br />17.PROJECT RECORD DOCUMENTS:
<br />1. COMMON REQUIREMENTS FOR ELECTRICAL
<br />INSTALLATION:
<br />A) LOCATION OF THE CONTROLS, ALARM ACTUATING
<br />DEVICES AND AUDIBLE ALARM SIGNALING DEVICES
<br />K) MEASURE INDICATED MOUNTING HEIGHTS TO
<br />SHALL BE AS SHOWN ON THE PLANS. ANY
<br />BOTTOM OF UNIT FOR SUSPENDED ITEMS AND TO
<br />NECESSARY DEVIATIONS SHALL BE APPROVED BY
<br />CENTER OF UNIT FOR WALL MOUNTED ITEMS.
<br />THE ENGINEER AND INDICATED ON AS -BUILT
<br />L) HEADROOM MAINTENANCE: IF MOUNTING HEIGHTS
<br />DOCUMENTS.
<br />OR OTHER LOCATION CRITERIA ARE NOT
<br />INDICATED, ARRANGE AND INSTALL COMPONENTS
<br />J. TRANSFORMERS:
<br />AND EQUIPMENT TO PROVIDE MAXIMUM POSSIBLE
<br />1. TAPS FOR TRANSFORMERS 25 KVA AND LARGER:
<br />HEADROOM.
<br />TWO 2.5 PERCENT TAPS ABOVE AND TWO 2.5
<br />M)EQUIPMENT: INSTALL TO FACILITATE SERVICE,
<br />PERCENT TAPS BELOW NORMAL FULL CAPACITY.
<br />MAINTENANCE AND REPAIR OR REPLACEMENT OF
<br />2. INSULATION CLASS: 220 DEG. E.
<br />COMPONENTS OF BOTH ELECTRICAL EQUIPMENT
<br />UL-COMPONENT--RECOGNIZED INSULATION
<br />AND OTHER NEARBY INSTALLATIONS. CONNECT IN
<br />SYSTEM WITH A MAXIMUM OF 115 DEG. C. RISE
<br />SUCH A WAY AS TO FACILITATE FUTURE
<br />ABOVE 40 DEG. C. AMBIENT TEMPERATURE.
<br />DISCONNECTING WITH MINIMUM INTERFERENCE
<br />WITH OTHER ITEMS IN THE VICINITY.
<br />3. ENERGY EFFICIENCY FOR TRANSFORMERS RATED
<br />15 KVA AND LARGER:
<br />N) RIGHT OF WAY: GIVE TO PIPING SYSTEMS
<br />INSTALLED AT A REQUIRED SLOPE.
<br />A)COMPLYING WITH NEMA TP 1, CLASS 1
<br />EFFICIENCY LEVELS.
<br />0)FIRE RATED ASSEMBLIES: INSTALL SLEEVES FOR
<br />PENETRATIONS OF FIRE -RATED FLOOR AND WALL
<br />ASSEMBLIES UNLESS OPENINGS COMPATIBLE WITH
<br />FIRESTOP SYSTEM USED ARE FABRICATED DURING
<br />CONSTRUCTION OF FLOOR OR WALL.
<br />P)EXTEND SLEEVES INSTALLED IN FLOORS 2
<br />INCHES ABOVE FINISHED FLOOR LEVEL.
<br />Q)SIZE PIPE SLEEVES TO PROVIDE 1/4" ANNULAR
<br />CLEAR SPACE BETWEEN SLEEVE AND RACEWAY
<br />OR CABLE, UNLESS INDICATED OTHERWISE.
<br />2. FIRESTOPPING
<br />A) APPLY FIRESTOPPING TO PENETRATIONS OF FIRE
<br />RATED FLOOR AND WALL ASSEMBLIES FOR
<br />ELECTRICAL INSTALLATIONS TO RESTORE ORIGINAL
<br />FIRE RESISTANCE RATING OF ASSEMBLY.
<br />3. CLEANING:
<br />A) BRUSH AND CLEAN WORK PRIOR TO CONCEALING,
<br />PAINTING AND ACCEPTANCE.
<br />B) U-BOLTS: AT EACH FLOOR LEVEL OF RISER
<br />RACEWAYS AND CONNECTED TO ACCEPTABLE
<br />SUPPORTS.
<br />C)RISER CLAMPS: AT EACH FLOOR LEVEL OR
<br />RISER RACEWAYS AND RESTING ON SLAB.
<br />D) SPACING:
<br />1) MINIMUM 10 FEET ON CENTERS FOR METALLIC
<br />RACEWAYS AND AS REQUIRED FOR
<br />NON-METALLIC RACEWAYS, INCLUDING CABLE
<br />TRAYS.
<br />2) 5 FEET ON CENTER FOR WIREWAYS.
<br />3)PER CODE AND AS NOTED FOR OTHERS.
<br />E) MOUNT SUPPORTS TO STRUCTURE WITH:
<br />1) TOGGLE BOLTS ON HOLLOW MASONRY.
<br />2)EXPANSION SHIELDS OR INSERTS IN CONCRETE
<br />AND BRICK.
<br />3)MACHINE SCREWS ON METAL.
<br />4)BEAM CLAMPS ON FRAMEWORK.
<br />5)WOOD SCREWS ON WOOD.
<br />6) PAN THROUGH STRAPS IN METAL DECK.
<br />7)NAILS, RAWL PLUGS OR WORK PLUGS NOT
<br />PERMITTED.
<br />8) WHERE REQUIRED BY STRUCTURE, THROUGH
<br />BOLTS AND FISH PLATES.
<br />4. RACEWAYS AND BOXES:
<br />A) EXPOSED: RUN PARALLEL WITH OR AT RIGHT
<br />ANGLES TO WALLS.
<br />B)CLEARANCE FROM WATER, STEAM OR OTHER
<br />PIPING: MINIMUM 3" SEPARATION FROM STEAM
<br />AND HOT WATER PIPES, EXCEPT 1" FROM PIPE
<br />COVER AT CROSSINGS.
<br />C)PROVIDE SEPARATE COPPER WIRE GROUNDING
<br />CONDUCTOR FOR INTERRUPTED METALLIC
<br />RACEWAYS, IN FLEXIBLE CONDUIT, FOR FEEDERS
<br />AND MOTOR TERMINAL CONNECTIONS.
<br />D)EMPTY RACEWAYS OVER 10 FEET LONG:
<br />PROVIDE FISH OR PULL WIRE, GALVANIZED OR
<br />NYLON ROPE.
<br />E) EMT:
<br />1) FEEDERS AND BRANCH CIRCUITS
<br />2) DRY LOCATIONS, DRY WALLS, HUNG CEILINGS,
<br />HOLLOW BLOCK WALLS AND FURRED SPACES.
<br />F) FLEXIBLE STEEL CONDUIT:
<br />1) FOR SHORT CONNECTIONS WHERE RIGID
<br />CONDUIT IS IMPRACTICAL (MAXIMUM OF 3
<br />FEET).
<br />2)FROM OUTLET BOX TO RECESSED LIGHTING
<br />FIXTURE: MINIMUM 4 FEET, MAXIMUM 6 FEET
<br />LENGTH.
<br />3)FOR FINAL CONNECTION TO MOTOR TERMINAL
<br />BOX, TRANSFORMERS AND OTHER VIBRATING
<br />EQUIPMENT, WITH POLYVINYL SHEATHING AND
<br />GROUND CONDUCTOR, EXCEPT PVC COATING
<br />SHALL NOT BE PROVIDED IN AIR HANDLING
<br />SPACES. MINIMUM LENGTH 18" WITH SLACK.
<br />CONNECT GROUND CONDUCTOR TO ENCLOSURE
<br />OR RACEWAY AT EACH END.
<br />4)FOR EXPANSION JOINT CROSSINGS, CROSS AT
<br />RIGHT ANGLES AND ANCHOR ENDS.
<br />5) USE ONLY IN DRY LOCATIONS, DRY WALLS,
<br />SUSPENDED CEILINGS AND FURRED SPACES.
<br />6) PROVIDE LIQUIDTIGHT FLEXIBLE STEEL CONDUIT
<br />OUTDOORS AND IN NON -WEATHER TIGHT
<br />ENCLOSURES.
<br />G)EXPANSION FITTINGS: AT RIGHT ANGLES WITH
<br />SLIP JOINT CENTERED IN EXPANSION JOINT.
<br />PROVIDE ON LENGTH OF RUNS IN ACCORDANCE
<br />WITH MANUFACTURER'S RECOMMENDATIONS.
<br />PRESET TO ALLOW FOR TEMPERATURE VARIATION.
<br />H)RACEWAYS PASSING THROUGH FLOORS OR WALLS:
<br />SEAL TO ORIGINAL OR SPECIFIED FIRE RATING
<br />THROUGH FIRE -RATED CONSTRUCTION. SEAL
<br />OPENING WITH UL LISTED PENETRATION
<br />ASSEMBLY.
<br />1) RIGID STEEL OR IMC: REQUIRED FOR OUTSIDE
<br />EXPOSED INSTALLATION.
<br />J) PVC SCHEDULE 40: REQUIRED FOR DIRECTLY
<br />BURIED INSTALLATION.
<br />5. OUTLET BOXES:
<br />A) SET BOXES SQUARE AND TRUE WITH BUILDING
<br />FINISH.
<br />B)SECURE TO BUILDING STRUCTURE BY ADJUSTABLE
<br />STRAP IRONS OR GROUT IN WITH MASONRY.
<br />C) VERIFY OUTLET LOCATIONS IN FINISHED SPACES
<br />WITH ARCHITECTURAL DRAWINGS OF INTERIOR
<br />DETAILS AND FINISHES.
<br />6. JUNCTION AND PULL BOXES:
<br />A) LOCATION:
<br />1) CLEAR OF OTHER TRADES.
<br />2) CONCEAL JUNCTION AND PULL BOXES IN
<br />FINISHED SPACES.
<br />3) MOUNT IN ACCESSIBLE LOCATIONS.
<br />B) SUPPORT: FROM BUILDING STRUCTURE,
<br />INDEPENDENT OF CONDUIT. PROVIDE
<br />FLOOR -TO -CEILING CHANNELS FOR MOUNTING ON
<br />DRY WALL AND LIGHTWEIGHT CONSTRUCTION.
<br />C)OUTLET BOXES FOR FIXTURES RECESSED IN
<br />HUNG CEILINGS: ACCESSIBLE THROUGH OPENING
<br />CREATED BY REMOVAL OF FIXTURE. SECURE TO
<br />BLACK IREN CEILING SUPPORT.
<br />D) MOTOR TERMINAL BOXES: COORDINATE WITH
<br />MOTOR BRANCH CIRCUIT AND WIRING. ADD BOX
<br />VOLUME WHERE REQUIRED.
<br />7. FIRE SEALANTS: PROVIDE UL
<br />THROUGH -PENETRATION SYSTEM FOR RACEWAYS
<br />AND WIRE PASSING THROUGH FLOOR, CEILING,
<br />WALLS AND PARTITIONS. SEAL PENETRATIONS
<br />EXISTING IN ELECTRICAL ROOM. SEAL SHALL
<br />RESTORE THE HOUR RATING OF THE PENETRATED
<br />ASSEMBLY.
<br />B. WIRE AND CABLE:
<br />1. 600 VOLT CABLE:
<br />A) NOT MORE THAN THREE (3) LIGHTING OR
<br />CONVENIENCE OUTLET CIRCUITS IN 1 CONDUIT
<br />UNLESS OTHERWISE INDICATED. SEPARATE
<br />RACEWAYS FOR CONDUCTORS OF 208Y/120.
<br />B)480Y/277 VOLT SYSTEMS
<br />C) COMMUNICATION CABLE IN PLENUMS SHALL BE
<br />PLENUM RATED OR SHALL BE INSTALLED IN
<br />METAL RACEWAY.
<br />2. TESTS:
<br />A) CONTINUITY AND INSULATION TESTS:
<br />1) 600 VOLTS: MEGGER
<br />2)100 PERCENT OF FEEDERS.
<br />3)10 PERCENT OF BRANCH CIRCUITS.
<br />B)PERFORM:
<br />1) PRIOR TO CONNECTION OF EQUIPMENT.
<br />2) IN PRESENCE OF AUTHORIZED
<br />REPRESENTATIVES.
<br />C) SUBMIT WRITTEN REPORT OF RESULTS.
<br />D)CORRECT OR REPLACE CABLE TESTING BELOW
<br />MANUFACTURER'S STANDARDS.
<br />C. LIGHTING FIXTURES:
<br />1. INSTALLATION OF LIGHTING FIXTURES:
<br />A) RECESSED FIXTURES SHALL BE SUPPORTED WITH
<br />12 GAUGE WIRE HANGERS, 2 PER FIXTURE, AT
<br />DIAGONALLY OPPOSITE CORNERS. FIXTURES
<br />SHALL BE ATTACHED TO CEILING GRID TO RESIST
<br />HORIZONTAL FORCE EQUAL TO WEIGHT OF
<br />FIXTURE.
<br />B)PROVIDE FIXTURES AND/OR FIXTURE OUTLET
<br />BOXES WITH HANGERS TO PROPERLY SUPPORT
<br />FIXTURE WEIGHT. COORDINATE WITH GENERAL
<br />CONTRACTOR TO PROVIDE ADDITIONAL CEILING
<br />GRID SUPPORT WIRES TO SUPPORT FIXTURE
<br />WEIGHT.
<br />C)PROVIDE CHANNEL AND SUPPORT FOR RECESSED
<br />LIGHTING FIXTURES IN PLASTER CEILINGS.
<br />D)RECESSED FLUORESCENT TROFFERS SHALL BE
<br />HELD IN PLACE BY CADDY 515 SERIES SUPPORT
<br />CLIPS OR SIMILAR CLIPS FROM FIXTURE
<br />MANUFACTURER.
<br />E) RECESSED FIXTURES IN SUSPENDED CEILINGS
<br />SHALL HAVE FINAL CONNECTIONS MADE WITH A
<br />LENGTH OF FLEXIBLE METAL CONDUIT NOT IN
<br />EXCESS OF 72" WITH THHN CONDUCTORS AND
<br />GREEN GROUND WIRE.
<br />F) INSTALL FLUSH MOUNTED FIXTURES PROPERLY TO
<br />ELIMINATE LIGHT LEAKAGE BETWEEN FIXTURE
<br />FRAME AND FINISHED SURFACE.
<br />G)SUSPENDED FIXTURES SHALL BE SUPPORTED
<br />FROM MOUNTING BRACKETS PROVIDED BY THE
<br />MANUFACTURER FOR THE SPECIFIC CEILING TYPE
<br />AND CONSTRUCTION. PROVIDE INDEPENDENT
<br />SUPPORT WIRES FROM FIXTURE SUPPORT
<br />BRACKET TO STRUCTURE.
<br />H)MOUNT SUSPENDED FIXTURES IN ALIGNMENT WITH
<br />ARCHITECTURAL ELEMENTS AS DIRECTED BY THE
<br />ARCHITECT.
<br />1) ENSURE SUSPENDED FIXTURES ARE MOUNTED
<br />LEVEL AND PARALLEL WITH THE SPACE.
<br />J) EXIT SIGNS AND SURFACE FIXTURES INSTALLED IN
<br />GRID CEILINGS SHALL BE SUPPORTED AND FED
<br />FROM CADDY 512 SERIES ELECTRICAL BOX
<br />HANGERS, OR SIMILAR SUPPORT FROM FIXTURE
<br />MANUFACTURER, WITH 12 GAUGE WIRE INSTALLED
<br />FORM BOX TO STRUCTURE.
<br />2. QUALITY CONTROL:
<br />A)AT DATE OF SUBSTANTIAL COMPLETION, REPLACE
<br />LAMPS WHICH ARE NOT WORKING AND LAMPS
<br />WHICH ARE NOT OPERATING PROPERLY AS
<br />JUDGED BY THE ENGINEER.
<br />B) VERIFY PROPER ORIENTATION OF DIRECTIONAL
<br />LIGHT FIXTURES PRIOR TO INSTALLATION. THESE
<br />FIXTURES MAY INCLUDE, BUT ARE NOT LIMITED
<br />TO WALL WASHERS AND ADJUSTABLE ACCENT
<br />LIGHTING FIXTURES. WHERE ORIENTATION CAN
<br />NOT BE ASCERTAINED FROM DRAWINGS OR
<br />MANUFACTURER'S LITERATURE, REQUEST
<br />CLARIFICATION IN WRITING FROM ENGINEER.
<br />3. ADJUSTING AND CLEANING:
<br />A) CLEAN LIGHTING FIXTURES OF HANDLING MARKS,
<br />DUST, DIRT, CONSTRUCTION DEBRIS, ETC. THIS
<br />SHALL INCLUDE LAMPS, LENSES, REFLECTORS
<br />AND LOUVERS, IN ADDITION TO FINISHED
<br />SURFACES. CLEANING AND TOUCH-UP WORK
<br />SHALL BE PERFORMED IN ACCORDANCE WITH THE
<br />FIXTURE MANUFACTURER'S RECOMMENDATIONS,
<br />WITH PARTICULAR EFFORTS MAD TO AVOID
<br />MARRING OR HAZING SPECULAR FINISHES.
<br />DAMAGED FIXTURES OR COMPONENTS SHALL BE
<br />REPLACED WITH NEW.
<br />B) FIXTURES HAVING ADJUSTABLE AN SETTINGS
<br />SHALL BE INITIALLY SET ACCORDING TO DRAWING
<br />REQUIREMENTS AND/OR ENGINEER'S INSTRUCTION
<br />PRIOR TO SUBSTANTIAL COMPLETION. PROVIDE
<br />FINAL AIM ADJUSTMENT IN PRESENCE OF
<br />TENANT'S REPRESENTATIVE PER ENGINEER'S
<br />GUIDANCE.
<br />D. LIGHTING CONTROLS:
<br />1. ENGAGE A FACTORY AUTHORIZED SERVICE
<br />REPRESENTATIVE TO TRAIN OWNER'S MAINTENANCE
<br />PERSONNEL TO ADJUST AND MAINTAIN LIGHTING
<br />CONTROLS.
<br />2. ALL CONTROLS SHALL BE ADJUSTED AND SET FOR
<br />PROPER PERFORMANCE.
<br />E. FIRE ALARM SYSTEM
<br />1. INSTALLATION:
<br />A) THE CONTRACTOR SHALL NOTIFY THE ENGINEER
<br />IN WRITING OF ANY FIELD INSPECTOR DIRECTIVES
<br />PRIOR TO PROCEEDING. FAILURE TO NOTIFY THE
<br />ENGINEER MAY RESULT IN FORFEIT OF CHANGE
<br />ORDER COMPENSATION.
<br />BALL DEVICE ADDRESSES SHALL BE PROGRAMMED
<br />TO INDICATE DEVICE TYPE AND LOCATION.
<br />C)EXISTING TO REMAIN AND NEW STROBES ARE TO
<br />BE SYNCHRONIZED.
<br />D) INSTALL PRODUCTS IN ACCORDANCE WITH
<br />MANUFACTURER'S INSTRUCTIONS.
<br />E) INSTALL MANUAL PULL STATION WITH OPERATING
<br />HANDLE 46" AFF. INSTALL AUDIBLE AND VISUAL
<br />SIGNAL DEVICES 80" AFF TO BOTTOM OF DEVICE
<br />LENS.
<br />F) ALL WIRE SHALL BE INSTALLED IN %' EMT
<br />CONDUIT.
<br />1) FOR ALARM INITIATING CIRCUITS - #18 AWG
<br />(MINIMUM) TWISTED, SHIELDED PAIR, STRANDED
<br />PER NEC ARTICLE 760.
<br />F) MOUNT END -OF -LINE DEVICE IN BOX WITH LAST
<br />DEVICE OR SEPARATE BOX ADJACENT TO LAST
<br />DEVICE IN CIRCUIT AS REQUIRED BY
<br />MANUFACTURER.
<br />G) AUTOMATIC DETECTOR INSTALLATION: CONFORM
<br />TO NFPA 72 AND MANUFACTURER'S
<br />INSTRUCTIONS.
<br />H) JUNCTION BOXES SHALL BE SPRAY PAINTED RED.
<br />1) CONTRACTOR SHALL PROVIDE A FRAMED
<br />TYPEWRITTEN ADDRESS SCHEDULE WHICH
<br />CLEARLY INDICATES DEVICES CONNECTED TO
<br />EACH ALARM INITIATING DEVICE CIRCUIT AND
<br />SIGNAL CIRCUIT AND HANG ADJACENT TO THE
<br />FACP.
<br />J) ALL CONDUITS SHALL CONTAIN #16 AWG
<br />EQUIPMENT GROUND UNLESS MANUFACTURER
<br />PROVIDES DOCUMENTATION TO THE ENGINEER
<br />WHICH NEGATES THE NEED FOR THIS
<br />CONDUCTOR.
<br />2. FIELD QUALITY CONTROL:
<br />A) TEST IN ACCORDANCE WITH NFPA 72 AND LOCAL
<br />FIRE DEPARTMENT REQUIREMENTS.
<br />BALL WORK SHALL BE PERFORMED BY A STATE
<br />OF FLORIDA CERTIFIED ELECTRICAL CONTRACTOR
<br />OR ALARM CONTRACTOR.
<br />3. SUPERVISION AND TESTING:
<br />A) THE INSTALLATION SHALL BE SUPERVISED BY AN
<br />AUTHORIZED MANUFACTURER'S REPRESENTATIVE.
<br />B) UPON COMPLETION, THE SYSTEM SHALL BE
<br />TESTED IN ACCORDANCE WITH NFPA 72 IN THE
<br />PRESENCE OF THE OWNER AND TENANT'S
<br />REPRESENTATIVE, THE FIRE MARSHAL AND AN
<br />AUTHORIZED MANUFACTURER'S REPRESENTATIVE.
<br />C)MANUFACTURER'S AND CONTRACTOR'S
<br />CERTIFICATION OF COMPLETE OPERABLE, AND
<br />SUCCESSFULLY TESTED SYSTEM SHALL BE
<br />FURNISHED TO THE OWNER.
<br />D) INDICATE SATISFACTORY COMPLETION OF
<br />REQUIRED TESTS AND INSPECTIONS.
<br />F. LABELING:
<br />1. LABEL ALL ELECTRICAL PANELS, TRANSFORMERS,
<br />DISCONNECT SWITCHES AND OTHER EQUIPMENT.
<br />2. MARK ALL J-BOXES AND CONDUIT RUN
<br />TRANSITIONS AND AT A MINIMUM OF EVERY 50
<br />FEET, BUT AT LEAST ONCE PER RUN. CONFORM
<br />TO CLIENT STANDARD FOR LABELING.
<br />3. PROVIDE NEW OR REVISED TYPED PANEL CIRCUIT
<br />CARDS FOR EXISTING AND NEW PANELS.
<br />4. PROVIDE SIGN ON PANEL COVERS OR FRAMES
<br />STATING REQUIREMENT TO MAINTAIN A DISTANCE FO
<br />36" CLEAR OF EQUIPMENT, FURNITURE OR STORED
<br />MATERIALS. LABEL PANELS IDENTIFYING THE
<br />LOCATION THE PANEL IS FED FROM, CONVERSELY
<br />LABEL FEED SOURCE IDENTIFYING WHERE PANEL IS
<br />LOCATED.
<br />5. ALL DISCONNECT SWITCHES ARE TO BE
<br />PERMANENTLY LABELED INDENTIFYING WHAT IT
<br />CONTROLS AND WHERE THE DEVICE IS LOCATED.
<br />6. LABEL COMMUNICATION DEVICES WITH USER AND
<br />FUNCTION AND LABEL ALL CONDUITS OR CABLE A
<br />MINIMUM OF EVERY 20 FEET.
<br />7. LABEL ALL RECEPTACLES WITH PANEL DESIGNATION
<br />AND CIRCUIT NUMBER. LABEL SHALL BE CLEAR
<br />MYLAR, P-TOUCH TYPE.
<br />2017 -Humana
<br />Zephyrhills Guidance
<br />Center
<br />7920 GALL BLVD.
<br />ZEPHYRHILLS, FL
<br />33541
<br />moo
<br />S m.lu HENNESSY
<br />GROUP
<br />A member company of SH Group, Inc.
<br />Syska Hennessy group, Inc
<br />9000 Southside Blvd.
<br />Building 100, 1st Floor
<br />Jacksonville, FI 32256
<br />Tel: 904.525.8669
<br />www.syska.com
<br />Florida C.O.A. #00001897
<br />JAY J. LANE FL# 71396
<br />1 ISSUE FOR CONSTRUCTION 4/18/18
<br />Delta Issue Description Date
<br />Nr.
<br />DECLARATIVE STATEMENT: TO THE BEST OF THE ENGINEER'S
<br />KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH
<br />THE APPLICABLE MINIMUM BUILDING CODES AND THE
<br />APPLICABLE FIRE -SAFETY STANDARDS AS DETERMINED BY
<br />THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTER
<br />533.70 AND CHAPTER 633, FLORIDA STATUTES.
<br />Drawn: EF Check: JL Owner Approval:
<br />Job No: HUM17390
<br />Scale: NONE
<br />ELECTRICAL
<br />Title: SPECIFICATIONS
<br />Sheet: ■