Laserfiche WebLink
SHEET NOTES <br />32 <br />32 <br />32" <br />36" <br />Building T <br />Building T <br />OCCUPANCY & MEANS OF EGRESS: RESIDENTIAL BUILDINGS <br />OCCUPANCY LOAD (FBC-B TABLE 1004.5 & FFPC TABLE 7.3.1.2) <br />RESIDENTIAL UNITS (R-2) 200 S.F. GROSS / OCC. <br />TRAVEL DISTANCE (FBC-B TABLE 1017.2 & FFPC 30.2.6) FBC-B ALLOWED FFPC ALLOWED <br />WITHIN DWELLING UNITS N/A 125'-0" <br />UNIT ENTRY TO AN EXIT N/A 200'-0" <br />MOST REMOTE POINT WITHIN A STORY TO AN EXIT 250'-0" N/A <br />EXITING REQUIREMENTS <br />NUMBER OF EXITS (FBC-B 1006 & FFPC 7.4) <br />STAIR (COMMON) (FBC-B 1011 & FFPC 7.2.2) <br />WIDTH <br />RISE <br />RUN <br />LANDING <br />HEADROOM <br />HANDRAIL DIAMETER <br />HANDRAIL PROJECTION FROM WALL <br />TRAVEL WITHIN UNIT <br />= 48'-4" (FFPC) <br />= 43'-0" (FFPC) <br />e II - Fourth Floor Life Safety Plan <br />e 11 - Second Floor Life Safety Plan <br />FBC-B REQUIRED FFPC REQUIRED <br />2 EXITS 2 EXITS <br />PROPOSED <br />53' <br />86'-1" <br />112' <br />PROPOSED <br />2 EXITS <br />44"(MIN) <br />44"(MIN) <br />>44" <br />7" (MAX) <br />4" (MIN) - 7" (MAX) <br />6" 5 R 5 7" <br />11"(MIN) <br />1V (MIN) <br />11" <br />36"(MIN) <br />36"(MIN) <br />>36" <br />80" <br />80" <br />>80" <br />1.25"-2" (MAX) <br />1.25"-2" (MAX) <br />1.5" <br />1.5" <br />2.25" <br />2.25" <br />1/16" = 1'-0" <br />Third Floor Similar 1/16" = 1'-0" <br />'d <br />i <br />A REFER TO SHEET A1.03 FOR GENERAL NOTES <br />B RATINGS SHOWN INDICATE REQUIRED SEPARATION RATINGS ONLY, <br />REFER TO SHEET A1.02 FIRE -RESISTANCE RATING REQUIREMENTS FOR <br />BUILDING ELEMENTS AND SHEETS A1.04 AND A1.05 FOR ALL <br />CONSTRUCTION ASSEMBLIES, ASSEMBLIES REFERENCED WITHIN THESE <br />DOCUMENTS COMPLY WITH BOTH SETS OF REQUIREMENTS <br />C OPENINGS INTO AND THROUGH ASSEMBLIES RATED FOR SEPARATION <br />SHALL BE PROTECTED AS NOTED ON A1.03, SPECIFICATION SECTION <br />078413, AND PER CODE REQUIREMENTS <br />D SEE CONTRACTOR'S FIRE PROTECTION DRAWINGS FOR STANDPIPE AND <br />HOSE CONNECTION DETAIL, COORDINATE LOCATIONS WITH <br />ARCHITECTURAL PLANS <br />E SEE CONTRACTOR'S FIRE PROTECTION DRAWINGS FOR IDENTIFICATION <br />OF SPRINKLER AREAS AND SPRINKLER SYSTEM TYPE <br />F LOCATE FIRE EXTINGUISHERS PER FLOOR AS SHOWN AND AS <br />OTHERWISE NECESSARY SUCH THAT THE TRAVEL DISTANCE FROM ANY <br />POINT ON THE FLOOR TO THE NEAREST EXTINGUISHER IS WITHIN 75' <br />G REFER TO ELECTRICAL DRAWINGS FOR EXIT AND EMERGENCY LIGHT <br />AND TWO-WAY COMMUNICATIONS SYSTEM LOCATIONS <br />H CONTRACTOR SHALL COORDINATE WITH THE AHJ AND VERIFY WHETHER <br />SEPARATE PERMITS SHALL BE REQUIRED FOR THE FIRE ALARM SYSTEM, <br />FIRE SPRINKLER SYSTEM, AND FIRE SUPPRESSION SYSTEM <br />FIRE PROTECTION RESPONSIBILITY <br />THE CONTRACTOR'S FIRE PROTECTION ENGINEER SHALL BE THE <br />"ENGINEER OF RECORD" FOR THE FIRE PROTECTION SYSTEM AND SHALL <br />PREPARE COMPLETE AND FINAL FIRE PROTECTION DESIGN DOCUMENTS <br />WITH HYDRAULIC CALCULATIONS, SIGNED AND SEALED, AS DEFINED BY THE <br />F.A.C. 61 G15-32 AND SHALL SUBMIT REQUIRED DOCUMENTATION TO THE <br />ARCHITECT FOR GENERAL REVIEW. UPON APPROVAL THE CONTRACTOR <br />SHALL SUBMIT SIGNED AND SEALED DOCUMENTS TO THE AHJ FOR REVIEW <br />AND APPROVAL. <br />KEYNOTES <br />01 FIRE ALARM CONTROL PANEL (FACP), REFER TO CONTRACTOR'S FIRE <br />PROTECTION DRAWINGS <br />02 FIRE ALARM ANNUNCIATOR PANEL (FAAP), REFER TO CONTRACTOR'S <br />FIRE PROTECTION DRAWINGS <br />03 FIRE SPRINKLER RISER CLOSET, REFER TO CONTRACTOR'S FIRE <br />PROTECTION DRAWINGS <br />04 STANDPIPE / HOSE VALVE CONNECTION, REFER TO CONTRACTOR'S FIRE <br />PROTECTION DRAWINGS <br />05 FIRE EXTINGUISHER IN SEMI -RECESSED CABINET, REFER TO DETAILS, <br />GENERAL NOTES / LEGEND FOR MOUNTING REQUIREMENTS <br />06 ELEVATOR CONTROLLER CLOSET <br />07 ELEVATOR CONTROLLER <br />08 AREA OF REFUGE TWO-WAY COMMUNICATION SYSTEM, REFER TO <br />ELECTRICAL DRAWINGS <br />09 "NOT AN EXIT" SIGN, CONTRACTOR TO PROVIDE A 7"X10" DURABLE <br />SELF-ADHESIVE VINYL SIGN PER LIFE SAFETY PLANS <br />10 KNOX BOX FOR EMERGENCY ACCESS BY FIRE DEPARTMENT TO ALL <br />RESTRICTED ACCESS AREAS FOR THE PROJECT, CONTRACTOR SHALL <br />PROVIDE AND COORDINATE EXACT LOCATION WITH AHJ <br />11 EMERGENCY RESPONDER RADIO COVERAGE SYSTEM, CONTRACTOR <br />SHALL PROVIDE 2-HOUR RATED CHASE, CONDUIT, RATED BACKBOARD, <br />AND POWER PER OWNER'S CONSULTANT REQUIREMENTS <br />LEGEND <br />— DESIGNATES 1 HR FIRE RATING FOR ADJACENT <br />WALL <br />2-2-2-2— DESIGNATES 2 HR FIRE RATING FOR ADJACENT <br />WALL <br />SEMI -RECESSED FIRE EXTINGUISHER IN CABINET, <br />REFER TO GENERAL NOTES <br />0 DESIGNATES DOOR IS NOT AN EXIT <br />4 FLOOR OCCUPANCY (GROSS UNIT / SQUARE <br />FOOTAGE) USING STAIRS (TOTAL / NUMBER OF <br />120 STAIRS) <br />t100 ROOM AREA (IN SF) <br />50 OCCUPANT LOAD FACTOR <br />2 OCCUPANT LOAD (PERSONS) <br />T32 <br />EGRESS LOAD (PERSONS) <br />REQUIRED EXIT WIDTH PER CODE <br />PROVIDED EXIT WIDTH <br />STARTING POINT <br />D=120' <br />"-- TOTAL DISTANCE TO GRADE LEVEL <br />7__� <br />PATH OF TRAVEL <br />5 <br />FORUM <br />ARCHITECTURE & <br />INTERIOR DESIGN, INC. <br />237 S. Westmonte Drive, Suite 220 <br />Altamonte Springs, FL 32714 <br />407.830.1400 <br />AR97193 <br />www.foru marchitecture.com <br />Zephyr <br />Commons <br />Apartments <br />City of Zephyrhills, FL <br />09/16/2022 <br />Karen V McIntyre <br />SET DISTRIBUTIONS: <br />11/24/21 j 100% DID Set <br />12/23/21 ; Owner Review Set <br />02/17/22 1 Permit Set <br />A SHEET REVISIONS: <br />r PROJECT NO. <br />H <br />Building Type II - <br />Life Safety Plans <br />4097 <br />Building T <br />II - First Floor Life Safe <br />Plan <br />1/16" = 1'-0" <br />A1.21 <br />