Laserfiche WebLink
I <br />3 <br />4 I 5 <br />r <br />u <br />I <br />0 <br />w <br />5 <br />C. CAST -IN -PLACE CONCRETE (CONTINUED) <br />7. REINFORCING SPLICE AND EMBEDMENT SCHEDULES: <br />ACI STANDARD 90 AND 180 DEGREE HOOK REINFORCEMENT... <br />BAR SIZE <br />HOOK EMBEDMENT LENGTH (IN.) <br />fc = 4000 PSI <br />fc = MW PSI <br />fc 6000 PSI <br />#3 <br />7 <br />7 <br />6 <br />#4 <br />10 <br />9 <br />8 <br />#5 <br />12 <br />11 <br />10 <br />#6 <br />.15 <br />13 <br />12. <br />#7 <br />17 <br />15 <br />14 <br />#8 <br />19 <br />17 <br />16 <br />#9 <br />22 <br />19 <br />18 <br />#10 <br />24 <br />22 <br />20 <br />#11 <br />27 <br />24 <br />22 <br />REINFORCEMENT SPLICE AND EMBEDMENT SCHEDULE FOR fc=4000 PSI <br />BAR SIZE <br />SPLICE LENGTH <br />EMBEDMENT LENGTH <br />TOP BARS <br />(IN.) 1 <br />OTHER BARS <br />(IN.) <br />TOP BARS <br />(IN.) 1 <br />OTHER BARS <br />(IN.) <br />#3 <br />24 <br />19 <br />19 <br />15 <br />#4 <br />32 <br />25 <br />25 <br />19 <br />#5 <br />40 <br />.31 <br />31 <br />24 <br />#6 <br />48 <br />37 <br />37 <br />29 <br />#7 <br />70 <br />54 <br />54 <br />42 <br />#8 <br />80 <br />62 <br />62 <br />48 <br />#9 <br />91 <br />70 <br />70 <br />54 <br />#10 <br />102 <br />79 <br />79 <br />61 <br />#11 <br />113 <br />87 <br />87 <br />67 <br />D. CONCRETE MASONRY <br />1. REFER TO DETAIL 1/S-002 FOR TYPICAL CMU LOAD BEARING WALL REINFORCING <br />ELEVATION. <br />2. ALL MASONRY SHALL CONFORM TO THE REQUIREMENTS OF IBC AND ACI 530. THE <br />MINIMUM SPECIFIED DESIGN COMPRESSIVE STRENGTH OF CONCRETE MASONRY (fm) <br />SHALL BE 1500 PSI AT 28 DAYS. <br />3. ALL CONCRETE MASONRY UNITS (CMU) SHALL BE 2-CELL, HOLLOW LOAD BEARING, <br />NORMAL WEIGHT AGGREGATE UNITS CONFORMING TO ASTM C90. <br />CMU SHALL HAVE A MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF 1900 psi ON THE <br />NET AREA AT 28 DAYS. <br />4. MORTAR SHALL CONFORM TO ASTM C270, TYPE S. MORTAR SHALL HAVE A MINIMUM <br />SPECIFIED COMPRESSIVE STRENGTH OF 1800 psi AT 28 DAYS. <br />5. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60. REINFORCEMENT LAP <br />SPLICES IN CMU WALLS, COLUMNS, PILASTERS AND BEAMS SHALL CONFORM TO TABLE <br />FOR NOTE #19 ON SHEET S-002. <br />PROVIDE TYP. VERT. WALL <br />REINFORCING ABOVE OPENINGS. <br />TERMINATE BOTTOM OF BARS <br />WITH STD. ACI 900 HOOK AT <br />BOTTOM LAYER OF LINTEL MASONRY CONTROL JOINT IINP OPENING JAMB, REF. 3/S-002 <br />REINFORCING. OR FOR SIZE & REINFORCING, TYP. <br />TOP OF WALL. MASONRYI ION JOINT <br />REF. ARCH. <br />OPENING LINTEL, RI <br />2IS-002 FOR SIZE & <br />REINFORCING, TYP. <br />TOP OF CONC <br />Nu ELEV. <br />PROVIDE <br />REINF ORCI <br />OPENINGS <br />D. CONCRETE MASONRY <br />6. GROUT SHALL CONFORM TO ASTM C476 AND SHALL HAVE A MINIMUM SPECIFIED <br />COMPRESSIVE STRENGTH (f'g) OF 2000 PSI AT 28 DAYS. THE COMPRESSIVE STRENGTH <br />OF THE GROUT SHALL BE DETERMINED IN ACCORDANCE WITH ASTM C1019. ALL CMU <br />CELLS SHALL BE FILLED SOLID WITH GROUT. <br />7. VERTICAL CELLS TO BE FILLED SHALL HAVE VERTICAL ALIGNMENT SUFFICIENT TO <br />MAINTAIN A CLEAR, UNOBSTRUCTED, CONTINUOUS VERTICAL CELL NOT LESS THAN 2 <br />1/2"x3" PLAN DIMENSIONS. <br />8. PROVIDE A DOWEL OF SAME SIZE AS VERTICAL REINFORCING FOR EACH VERTICAL <br />REINFORCING BAR. FOUNDATION DOWELS SHALL BE EXTENDED AN EMBEDMENT <br />LENGTH INTO THE FOUNDATION CONCRETE AND ONE LAP LENGTH INTO MASONRY WALL <br />UNLESS NOTED OR INDICATED OTHERWISE. <br />9. ALL VERTICAL WALL REINFORCING (INCLUDING JAMBS) SHALL EXTEND CONTINUOUSLY <br />FROM BASE OF WALL TO EMBED 6" INTO THE UPPERMOST BOND BEAM. REFER TO <br />DETAILS 1/S-002 FOR TYPICAL CMU WALL REINFORCING UNLESS NOTED OTHERWISE ON <br />THE DRAWINGS. <br />10. PROVIDE CONCRETE MASONRY CONTROL JOINTS (MCJ) AS SHOWN ON THE DRAWINGS. <br />11. REFER TO 3/S-002 FOR CMU OPENING JAMB REINFORCING AND DIMENSIONS.. REFER TO <br />2/S-002 FOR OPENING LINTEL REINFORCING AND DIMENSIONS. <br />12. REFER TO 1/S-002 FOR CMU BOND BEAM LOCATIONS, DIMENSIONS, REINFORCING, AND <br />SPACING, U.N.O. ALL INTERIOR CMU WALLS SHALL HAVE BOND BEAMS LOCATED AT THE <br />SAME LEVELS AS PERIMETER CMU WALL BOND BEAMS. <br />13. HORIZONTAL REINFORCING BARS AROUND PERIMETER OF OPENINGS SHALL EXTEND A <br />MINIMUM OF 24 INCHES OR 40 BAR DIAMETERS, WHICHEVER IS LARGER, PAST THE <br />CORNER OF THE OPENING. WHERE THE MINIMUM LENGTH CANNOT BE ACHIEVED, <br />PROVIDE A STANDARD ACI 180 DEGREE HOOK AT END OF BAR. <br />14. PROVIDE A MINIMUM OF THREE VERTICAL CELLS GROUTED SOLID WITH (1) - #6 VERTICAL <br />IN EACH CELL AT ENDS OF CMU WALLS, CMU WALL INTERSECTIONS AND CORNERS, <br />EACH SIDE OF A CMU WALL MASONRY CONTROL OR ISOLATION JOINT, UNLESS. NOTED <br />OTHERWISE. BEAM SUPPORT LOCATIONS NOT AT PILASTERS SHALL HAVE A MINIMUM OF <br />THREE VERTICAL CELLS GROUTED FULL WITH (1) #6 VERTICAL IN EACH CELL. PROVIDE A <br />DOWEL OF SAME SIZE AS THE VERTICAL REINFORCING AT THE BASE OF THE WALL FOR <br />EACH VERTICAL REINFORCING BAR. <br />15. REFER TO SHEET S-002 FOR TYPICAL CMU WALL CORNER AND INTERSECTION <br />REINFORCING DETAIL. <br />IIII <br />��� <br />!� <br />_4UMA <br />Iuu <br />MINE <br />II�H.�. <br />HN <br />HMO <br />1�\CC�C>������I�I�il��l��lilOO�11��O1i1 <br />IIIS� <br />"Imm <br />Hl�i <br />IIIIIIIIIIIIIIIII1/11 <br />111nnI1INlllllnOSlMMONONn <br />1ftH■��tn <br />IHI�I <br />1�1n�nw�11 <br />H���IIIIIIIIJISIu <br />O <br />!1l�#1�1��1�=II=�I��IHRI <br />M- <br />IMII/NMsMMi1N=#1MMM=1MMMMM=kumIIlmmI#i#I <br />IIIMM <br />mmmmmmmHii1mmmmmmmmmmmHii1mMMHI <br />MEN! <br />i� { :>=LMM===E�crj==rzj=c==l"Mc==l <br />fib= <br />- <br />•CONT. <br />PROVIDE' • BOND BEAM <br />BOTTOM OF OPENINGS. <br />r <br />FOUNDATION DOWEL, <br />REF. NOTES 8 & 14 <br />TYP. REINFORCING & <br />SPACING (1) - #6 C 16" O.C. <br />(U.N.O.) <br />TYPICAL LOAD BEARING CMU WALL ELEVATION - - <br />3-002) NOT TO SCALE <br />CMU JAMB SCHEDULE <br />OPENING <br />WIDTH <br />JAMB <br />WIDTH (W) <br />REINF. BAR <br />SIZE <br />NUMBER OF <br />BARS PER CELL <br />4'-0" OR LESS <br />16" <br />#5 <br />2 <br />TYPICAL CMU JAMB DETAILS & SCHEDULE DETAIL <br />3-0021 NOT TO SCALE <br />TYP. <br />NOTE: <br />CONTROL JOINTS NOT SHOWN FOR CLARITY. SEE <br />REINFORCED CONCRETE MASONRY WALLS NOTE 10: <br />A^I 111 ^r%^l IT 1-1 1/ 1 IAllf1Tl 1 <br />CMU LINTEL SCHEDULE <br />OPENING <br />WIDTH <br />LINTEL <br />DEPTH (D) <br />REINF. BAR <br />SIZE <br />NUMBER OF <br />TOP BARS <br />NUMBER OF <br />BOT. BARS <br />4'-0" OR LESS <br />811 <br />#5 <br />-- <br />2 <br />CONT. BOND BEAMS W/ (2) - #5 (MIN. <br />U.N.O.) AT TOP OF WALL, BOTTOM <br />OF WALL, STEEL BEAM BEARING <br />ELEVATION, AND EVERY SIXTH <br />COURSE ALONG WALL HEIGHT. <br />BOND BEAM REINFORCING AT TOP <br />AND BOTTOM OF WALL AND STEEL <br />BEAM BEARING ELEVATION SHALL <br />BE CONT. THRU CONTROL JOINTS <br />IN <br />_E <br />AND QUANTITY IN EACH CELL. <br />C <br />SOLID GROUT <br />LINTEL FULL DEPTH <br />REF. SCHEDULE <br />FOR BAR SIZE <br />& QUANTITY <br />21 /2"4 L e j; 21 /2" <br />DOUBLELINTEL <br />CMU LINTEL DETAIL & SCHEDULE <br />3-00 NOT TO SCALE <br />PVC CONTROL SEALANT <br />JOINT MATERIAL� � BACKSTOP <br />MATERIAL <br />'1 <br />VERTICAL WALL REINFORCING, -' <br />SEE GENERAL STRUCTURAL <br />NOTES <br />TYPICAL MASONRY CONTROL <br />JOINT (MCJ) DETAIL <br />3-0021 NOT TO SCALE <br />D. CONCRETE MASONRY <br />16. REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR DIMENSIONS, OPENING <br />SIZES, LOCATIONS, AND ADDITIONAL INFORMATION AND REQUIREMENTS. <br />17. CONTRACTOR SHALL SUBMIT CMU WALL LAYOUT PLANS AND ELEVATIONS FOR <br />APPROVAL PRIOR TO BEGINNING CONSTRUCTION. THE CMU WALL LAYOUT PLANS AND <br />ELEVATIONS SHALL BE SUBMITTED WITH THE REINFORCING SHOP DRAWINGS FOR THE <br />SUPPORTING FOUNDATION OR FRAMING LEVEL. THE CMU WALL LAYOUT PLANS AND <br />ELEVATIONS SHALL LOCATE AND INDICATE DIMENSIONS FOR ALL CMU WALLS, WALL <br />OPENINGS, MASONRY CONTROL JOINTS, AND ALL CMU VERTICAL CELLS. HORIZONTAL <br />ELEMENTS AND CMU VERTICAL CELLS THAT WILL BE REINFORCED, AND CONTAIN <br />DOWELS SHALL BE INDICATED AND LOCATED ON THE CMU LAYOUT PLANS AND <br />ELEVATIONS. <br />18. HORIZONTAL BOND BEAM AND JOINT REINFORCING FOR INTERIOR AND EXTERIOR WALLS <br />SHALL BE CONTINUOUS THROUGHOUT, EXCEPT AT MASONRY CONTROL JOINTS IT SHALL <br />BE AS FOLLOWS - <br />A. INTERMEDIATE HORIZONTAL BOND BEAM AND JOINT REINFORCING SHALL BE <br />DISCONTINUOUS AT MASONRY CONTROL JOINTS EXCEPT THAT REINFORCEMENT IN <br />BOND BEAMS AT THE BOTTOM AND TOP OF WALL AND STEEL BEAM BEARING <br />ELEVATIONS SHALL BE CONTINUOUS. <br />B. WHERE CONTROL JOINT DOES NOT OCCUR AT A CORNER, PROVIDE BENT CORNER BARS <br />TO MATCH AND LAP WITH THE HORIZONTAL REINFORCING BARS OF EACH BOND BEAM <br />AT ALL CMU WALL CORNERS AND INTERSECTIONS UNLESS NOTED OR INDICATED <br />OTHERWISE. <br />C. USE OPEN KNOCK OUT BLOCK BOND BEAM BLOCKS. DO NOT USE TROUGH TYPE BLOCKS <br />FOR BOND BEAMS UNLESS NOTED OTHERWISE. TROUGH TYPE BLOCKS MAY BE USED <br />FOR BOND BEAMS WHICH ARE ALSO LINTELS AND ARE DIRECTLY ABOVE AN OPENING. <br />19. VERTICAL AND HORIZONTAL REINFORCING SHALL MEET THE FOLLOWING LAP SPLICE <br />AND EMBEDMENT REQUIREMENTS - <br />REINF. <br />BAR <br />SIZE <br />LAP SPLICE <br />LENGTH IN <br />CMU WALL <br />(IN.) <br />EMBEDMENT W/ STD. <br />ACI .90 DEGREE HOOK <br />(IN.) <br />STRAIGHT <br />EMBEDMENT (IN.) <br />#4 <br />15 <br />10 <br />19 <br />#5 <br />23 <br />12 <br />24 <br />#6 <br />43 <br />15 <br />29 <br />#7 <br />60 <br />17 <br />42 <br />#8 <br />92 <br />19 <br />48 <br />20. ALL CONCRETE MASONRY WALLS SHOWN ON THE ARCHITECTURAL AND STRUCTURAL <br />DRAWINGS HAVE BEEN DESIGNED TO RESIST THE REQUIRED CODE VERTICAL AND <br />LATERAL FORCES APPLIED TO THEM IN THE FINAL CONSTRUCTED CONFIGURATION ONLY <br />ASSUMING FULL BRACING TOP, BOTTOM, AND/OR SIDE OF WALL AS INDICATED. IT IS THE <br />RESPONSIBILITY OF THE CONTRACTOR TO PROPERLY AND ADEQUATELY BRACE ALL <br />MASONRY WALLS AT ALL STAGES DURING CONSTRUCTION TO RESIST ERECTION LOADS <br />AND LATERAL LOADS THAT COULD POSSIBILY BE APPLIED TO THEM PRIOR TO <br />COMPLETION OF CONSTRUCTION. <br />21. ALL CONCRETE MASONRY CONSTRUCTION REQUIRES SPECIAL INSPECTION. REFER TO <br />THE "BUILDING CODE" AND CONTRACT DOCUMENTS FOR ADDITIONAL INFORMATION AND <br />REQUIREMENTS. <br />22. ALL CMU CONSTRUCTION SHALL BE PLACED IN RUNNING BOND PATTERN. <br />48 BAR DIAMETERS <br />VERTICAL CORNER BARS, <br />SEE GENERAL STRUCTURAL <br />NOTES <br />BOND BEAM <br />REINFORCEMENT <br />TYPICAL PLAN DETAIL FOR <br />BOND BEAM REINFORCING <br />3-002) NOT TO SCALE <br />,1W A" <br />wwx <br />- <br />a HaskeO Company <br />ENGINEERING #31348 <br />S -to -19 <br />STUARTT. WEBB <br />STRUCTURAL ENGINEER <br />REG. NO.88469 <br />U. <br />cl <br />rn <br />0 <br />04 <br />0 <br />O <br />F= <br />U <br />�a <br />o <br />a <br />z� <br />Oo <br />0 <br />U <br />n <br />W <br />o <br />0 <br />T_ <br />N <br />U <br />ti <br />a <br />N <br />aS <br />cn <br />co <br />WL <br />z <br />I=- ao <br />O -j <br />o <br />to <br />W <br />N J <br />Za, <br />°°(�� <br />1m <br />ci-- <br />�o <br />Q� <br />�N <br />�¢ <br />CON <br />a <br />M <br />qw_ <br />(L <br />J <br />N <br />w <br />Z <br />C) <br />z <br />o. <br />LO <br />.I <br />Z --I <br />¢Q <br />O <br />F- <br />m <br />Op <br />Z <br />J <br />Z -j <br />Z <br />93: <br />1 -L <br />U <br />L } <br />1 <br />Oa <br />D <br />�0 <br />o <br />co <br />ui <br />0 <br />0 <br />J ` <br />a <br />� <br />z <br />Z <br />wU <br />H <br />p <br />J <br />Z a <br />w <br />U <br />w <br />m <br />0. <br />SHEET <br />IDENTIFICATION <br />S-002 <br />Eli <br />E <br />