ABOVEGROUND PLUMBING SYSTEMS <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A. RELATED DOCUMENTS: PROVISIONS OF THE CONTRACT, INCLUDING CONDITIONS OF THE CONTRACT, DRAWINGS <br />AND DIVISION 1 - GENERAL REQUIREMENTS OF THE SPECIFICATION, APPLY TO THIS SECTION. <br />B. DESCRIPTION: ABOVEGROUND PLUMBING SYSTEMS ARE INDICATED BY CONTRACT DOCUMENTS AND SHALL <br />INCLUDE WORK NECESSARY AND INCIDENTAL TO COMPLETION AND PERFORMANCE OF THE WORK. <br />C. INCLUDED: ABOVEGROUND PLUMBING SYSTEMS INCLUDE, BUT IS NOT LIMITED TO THE FOLLOWING: <br />1. DOMESTIC WATER SYSTEM. <br />2. SANITARY WASTE SYSTEM. <br />3. DRAINS AND CLEANOUTS. <br />D. RELATED WORK: <br />1. PLUMBING INSULATION. <br />2. UNDERGROUND PLUMBING. <br />3. PLUMBING FIXTURES AND EQUIPMENT. <br />1.02 QUALITY ASSURANCE <br />A. REGULATORY REQUIREMENTS: COMPLY WITH LOCAL WATER AND SEWER DEPARTMENT REGULATIONS WHICH <br />REQUIRE THAT PRODUCTS USED FOR DRAINAGE AND DOMESTIC WATER SYSTEMS BE SELECTED FROM LISTS <br />SPECIFIED IN CODE, WHICH COMPLY WITH CERTAIN PUBLISHED STANDARDS OR CODES, AND THAT PRODUCTS BE <br />USED AS INTENDED. <br />B. MANUFACTURER QUALIFICATIONS: MANUFACTURER SHALL HAVE 5 YEAR MINIMUM DOCUMENTED EXPERIENCE IN <br />DESIGN, PRODUCTION, FABRICATION AND INSTALLATION OF TYPE WORK REQUIRED FOR THE WORK. UPON <br />REQUEST, PROVIDE PROOF OF QUALIFICATIONS. <br />C. INSTALLER QUALIFICATIONS: INSTALLER SHALL HAVE 5 YEARS MINIMUM DOCUMENTED EXPERIENCE IN DESIGN, <br />PRODUCTION, FABRICATION AND INSTALLATION OF TYPE WORK REQUIRED FOR THE WORK. UPON REQUEST, <br />PROVIDE PROOF OF QUALIFICATIONS. <br />D. WELDING QUALIFICATIONS: <br />1. QUALITY WELDING PROCEDURES SHALL BE IN ACCORDANCE WITH ANSI B31.1 FOR SHOP AND PROJECT SITE <br />WELDING OF PIPING WORK. <br />2. CERTIFY WELDING OF PIPING WORK USING THE STANDARD PROCEDURE SPECIFICATIONS WITH WELDERS <br />TESTED UNDER SUPERVISION OF THE NATIONAL CERTIFIED PIPE WELDING BUREAU. <br />1.03 SUBMITTALS <br />A. PRODUCT DATA: SUBMIT PRODUCT SPECIFICATIONS, TECHNICAL DATA, STANDARD DETAIL DRAWINGS AND <br />INSTALLATION INSTRUCTIONS OF MANUFACTURER FOR EACH PRODUCT. INCLUDE PUBLISHED DATA, CERTIFIED <br />CONFORMANCE REPORT OR CERTIFIED LABORATORY TEST REPORT OF MANUFACTURER SUBSTANTIATING EACH <br />PROPOSED PRODUCT MEETS REQUIREMENTS OF CONTRACT DOCUMENTS AND HAS BEEN TESTED WITH <br />ADJACENT PRODUCT IDENTICAL TO PRODUCTS TO BE USED IN THE WORK AND IS INTENDED FOR APPLICATION. <br />B. SHOP DRAWINGS: SUBMIT SHOP DRAWINGS FOR EACH PIPING SYSTEM, FITTINGS AND DRAINS SHOWING PIPE <br />SIZES, LOCATIONS, ELEVATIONS AND SLOPES OF HORIZONTAL RUNS, FITTINGS, ACCESSORIES AND <br />CONNECTIONS. <br />C. OPERATION AND MAINTENANCE MANUALS: PROVIDE MAINTENANCE MANUAL WITH IDENTIFICATION NUMBER OF <br />EACH VALVE, WITH LOCATION, SECTION OF SYSTEM OR EQUIPMENT CONTROLLED AND CONDITION OF VALVE (NO <br />OR NC). <br />D. RECORD DRAWINGS: SUBMIT SHOWING LOCATION AND ELEVATIONS OF ABOVEGROUND PLUMBING PIPING. <br />1.04 WARRANTY <br />A. GENERAL: WARRANTY WORK MEETING PROVISIONS OF CONDITIONS OF THE CONTRACT, EXCEPT WARRANTY <br />SHALL INCLUDE ADDITIONAL REQUIREMENTS SPECIFIED IN THIS ARTICLE. <br />B. WARRANTY SYSTEMS SHALL BE FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP. FURNISH MANUFACTURER <br />WARRANTIES. <br />PART 2-PRODUCTS <br />2.01 ABOVEGROUND DOMESTIC WATER PIPING SYSTEM <br />A. PIPING 2% INCH AND SMALLER: <br />1. PIPE: TYPE L HARD TEMPER, COPPER TUBING IN STRAIGHT LENGTHS, MEETING REQUIREMENTS OF ASTM B88. <br />2. FITTINGS: SLEEVE TYPE WITH SOLDER COMPLETELY FILLING JOINTS BY CAPILLARY ACTION. CAST BRASS <br />FILINGS SHALL CONFORM TO ANSI B16.18. WROUGHT COPPER FITTINGS SHALL HAVE WALL THICKNESS AT <br />LEAST EQUAL TO THE TUBE AND CONFORM TO ANSI B16.22. <br />B. VALVES: <br />1. VALVES SHALL BE INSTALLED AS INDICATED ON DRAWINGS AND APPROPRIATE FOR INTENDED SERVICE. <br />2. BALL VALVES: <br />a. SIZE 2 INCH AND SMALLER: 150 TO 600 WOG RATING, 2 PIECE BRONZE BODY, CHROME PLATED BALL WITH <br />LARGE PORT OPENING, SOLDER OR THREADED ENDS, BLOW OUT PROOF STEM WITH EXTENSION FOR <br />INSULATED PIPING, RTFE SEATS. <br />4. CHECK VALVES: <br />a. 150 TO 300 WOG RATING, BRONZE BODY, THREADED BONNET, REPLACEABLE TEFLON DISC. <br />b. SIZES 4 INCH AND LARGER: 125 TO 200 WOG RATING, IRON BODY, BOLTED BONNET, FLANGED ENDS, BRONZE <br />TRIM, REPLACEABLE DISC AND SEAT. <br />5. SILENT CHECK VALVES: <br />a. 125 TO 200 WOG RATING, CENTER GUIDED WAFER TYPE, IRON BODY, BRONZE DISC, STAINLESS STEEL <br />SPRING, SCREWED 1/2 TO 2 INCH AND FLANGED 2-1/2 INCH AND LARGER. <br />9. SAFETY RELIEF VALVES: <br />a. BRONZE BODY, DIAPHRAGM OPERATED, 125 PSI MAXIMUM WORKING PRESSURE, 250 F MAXIMUM OPERATING <br />TEMPERATURE, ASME LABELED FOR RELIEVING PRESSURE AS FLUID SHOULD NOT DISCHARGE INTO THE <br />SPRING CHAMBER. <br />C. ACCESSORIES <br />1. THERMOMETERS: <br />a. MERCURY RED READING SEPARABLE WELL TYPE WITH ADJUSTABLE ANGLE SCALE WITH CLEAR PLASTIC <br />WINDOW FOR EASY READING FROM FLOOR. RANGE SHALL HAVE OPERATING TEMPERATURE NEAR MIDDLE <br />OF SCALE. SCALE SHALL BE NOT LESS THAN 7 INCHES LONG, AND CASE SHALL BE CAST METAL. <br />b. ACCEPTABLE MANUFACTURERS: <br />1) H. 0. TRERICE CO. <br />2) MOELLER INSTRUMENT COMPANY, INC. <br />3) WEKSLER-GAUGES. <br />3. WATER HAMMER ARRESTORS (SHOCK ABSORBERS): <br />a. AT EACH LOCATION OF A QUICK OPENING VALVE OR SOLENOID VALVE THAT CAN GENERATE A WATER <br />HAMMER SUCH AS, BUT NOT LIMITED TO, FLUSH VALVE TOILETS COLD WATER MAIN, EMERGENCY SHOWERS, <br />WASHING EQUIPMENT, DISHWASHING OR EQUIPMENT WASHING, LAUNDRY MACHINES, AND LIKE EQUIPMENT, <br />PROVIDE ONLY A GAS SUPPRESSION TYPE SHOCK ABSORBER WITH SEALED AIR CHAMBERS OF SIZE AND <br />CAPACITY AS RECOMMENDED BY PDI STANDARDS AND WARRANTED BY MANUFACTURER. <br />b. WATER HAMMER ARRESTER SHALL CONSIST OF A COPPER BODY WITH AN ACETAL PISTON, BUNA NITRILE <br />O-RINGS AND LEAD FREE SOLDER. THE DEVICE SHALL BE PRE -CHARGED AND SEALED AT THE FACTORY. <br />c. AIR CHAMBER FOR PLUMBING FIXTURES SHALL BE FULL SIZE OF SUPPLY PIPE AND 12 INCHES LONG. AIR <br />CHAMBERS SHALL BE PROVIDED AT ALL FIXTURE CONNECTIONS. <br />d. ACCEPTABLE MANUFACTURERS: <br />1) JAY R. SMITH MFG. CO. <br />2) JOSAM COMPANY. <br />3) PRECISION PLUMBING PRODUCTS. <br />4) WADE <br />5) ZURN. <br />4. VACUUM BREAKERS: <br />a. PROVIDE VACUUM BREAKERS ON PLUMBING FIXTURES AND WATER USING DEVICES WHERE REQUIRED BY <br />LOCAL AND STATE PLUMBING AND HEALTH CODES AND AS REQUIRED BY LOCAL PLUMBING INSPECTION <br />DEPARTMENT OR AS SPECIFIED. <br />b. EXPOSED VACUUM BREAKERS AND PIPING SHALL BE CHROME PLATED. <br />c. INSTALL IN AN EASILY ACCESSIBLE LOCATION FOR OBSERVATION, INSPECTION AND REPAIRS AND IN SUCH <br />MANNER AS APPROVED BY THE LOCAL PLUMBING INSPECTION DEPARTMENT. <br />2.02 SANITARY, WASTE AND VENT PIPING SYSTEM <br />A. SYSTEM PIPING SHALL BE: <br />1. CAST IRON, SERVICE WEIGHT, BELL AND SPIGOT OR THREADED, (IPS) MEETING REQUIREMENTS OF ASTM A74. <br />2. CAST IRON, SERVICE WEIGHT, NO HUB CONFORMING TO CISPI 301, WITH CLAMP -ALL OR HUSKEY COUPLINGS. <br />COUPLINGS SHALL BE CONSTRUCTED OF TYPE 304 STAINLESS STEEL WITH 305 STAINLESS STEEL WORM DRIVE <br />SCREWS. THE GASKET MATERIAL SHALL BE NEOPRENE AND CONFORM TO ASTM C-564. THE COUPLING <br />ASSEMBLY SHALL BE TORQUED TO SPECIFIED REQUIREMENTS FOR THE RATED 15 PSIG SYSTEM PRESSURE <br />LIMITATION. THIS PRODUCT IS NOT TO BE USED IN HORIZONTAL PUMPED PRESSURE APPLICATIONS. <br />3. CORROSION RESISTANT, SCHEDULE 40 POLYVINYL CHLORIDE (PVC) PIPE. PVC NOT ALLOWED IN RETURN AIR <br />PLENUM APPLICATIONS. <br />PVC NOT TO BE USED IN RETURN AIR PLENUM APPLICATIONS. <br />a. PIPE AND FITTINGS JOINED WITH SOLVENTS, MEETING REQUIREMENTS OF ASTM D2466 AND ASTM D2855. <br />2.03 CLEANOUTS <br />A. CLEANOUTS SHALL BE PROVIDED AS REQUIRED BY CODE AND LOCAL AMMENDMENTS. <br />B. ACCEPTABLE MANUFACTURERS: <br />1. J. R. SMITH. <br />2. JOSAM <br />3. WADE <br />4. ZURN. <br />C. PIPE SPACE CLEANOUTS SHALL TERMINATE IN A BRASS RAISED HEAD CLEANOUT PLUG BEHIND THE WALL <br />SURFACE WITH A 12 GAGE STAINLESS STEEL PLATE ON THE WALL HELD IN PLACE WITH A COUNTERSUNK <br />SCREW, J. R. SMITH MODEL 4420 WITH MODEL 4725. <br />D. FINISHED FLOORS: LABELED SANITARY OR STORM AS APPLICABLE, CAST IRON CLEANOUT BODY, BRONZE <br />COUNTERSUNK CLOSURE PLUG, ADJUSTABLE SCORIATED SECURED NICKEL BRONZE COVER. <br />PART 3 - EXECUTION <br />3.01 EXAMINATION <br />A. GENERAL: EXAMINE AREAS AND CONDITIONS UNDER WHICH WORK IS TO BE INSTALLED FOR COMPLIANCE WITH <br />REQUIREMENTS OF CONTRACT DOCUMENTS AND TO DETERMINE IF CONDITIONS AFFECTING PERFORMANCE OF <br />WORK ARE SATISFACTORY. DO NOT PROCEED WITH INSTALLATION UNTIL UNSATISFACTORY CONDITIONS HAVE <br />BEEN RESOLVED. COMMENCEMENT OF INSTALLATION SHALL CONSTITUTE ACCEPTANCE OF CONDITIONS. <br />3.02 PRODUCT HANDLING <br />A. STORE PIPE AND TUBE INSIDE AND PROTECTED FROM WEATHER. PROTECT FLANGES AND FITTINGS FROM <br />MOISTURE AND DIRT BY INSIDE STORAGE AND ENCLOSURE, OR BY PACKAGING WITH DURABLE, WATERPROOF <br />WRAPPING. WHERE NECESSARY TO STORE OUTSIDE, ELEVATE WELL ABOVE GRADE AND ENCLOSE WITH <br />DURABLE, WATERPROOF WRAPPING. <br />B. MAINTAIN END CAPS THROUGH SHIPPING, STORAGE AND HANDLING TO PREVENT PIPE END DAMAGE AND <br />ELIMINATE DIRT AND MOISTURE FROM INSIDE OF PIPE AND TUBE. <br />C. PROTECT PIPING WORK DURING CONSTRUCTION PERIOD, TO AVOID CLOGGING WITH CONSTRUCTION <br />MATERIALS AND DEBRIS AND TO PREVENT DAMAGE FROM TRAFFIC AND OTHER CONSTRUCTION MATERIALS. <br />D. CLEAN EXTERIOR SURFACES OF INSTALLED PIPING SYSTEMS OF SUPERFLUOUS MATERIALS. FLUSH OUT PIPING <br />SYSTEMS WITH CLEAN WATER BEFORE PROCEEDING WITH REQUIRED TESTS. INSPECT EACH RUN OF EACH <br />SYSTEMS FOR COMPLETION OF JOINTS, SUPPORTS AND ACCESSORY ITEMS. <br />3.03 PIPING ARRANGEMENT AND ALIGNMENT <br />A. PIPING SHALL BE ARRANGED AS INDICATED ON DRAWINGS AND MEET REQUIREMENTS OF SECTION 01314 - <br />SPECIAL COORDINATION. WHERE SPECIAL CONDITIONS ARE ENCOUNTERED, REARRANGEMENT AND <br />REALIGNMENT OF PIPING SHALL BE AS DIRECTED BY ARCHITECT. <br />B. PIPING SHALL BE INSTALLED IN A UNIFORM MANNER, PARALLEL TO WALL OR CEILINGS. HORIZONTAL PIPING <br />SHALL BE RUN AT RIGHT ANGLES TO WALLS AND L NOT RUN DIAGONALLY ACROSS ROOM OR OTHER PIPING. <br />WHEREVER POSSIBLE PIPING SHALL BE ARRANGED TO PROVIDE MAXIMUM HEADROOM. <br />C. WHERE INTERFERENCE OCCURS WITH ANOTHER TRADE WHOSE WORK IS MORE DIFFICULT TO ROUTE, REROUTE <br />PIPES AS REQUIRED TO AVOID INTERFERENCE. <br />D. PIPING SHALL BE INSTALLED TO PROVIDE ALIGNMENT, SLOPE AND EXPANSION. <br />E. PIPING SHALL BE GROUPED WHEREVER PRACTICAL AND BE INSTALLED UNIFORMLY IN STRAIGHT PARALLEL <br />LINES IN EITHER VERTICAL OR HORIZONTAL POSITIONS. PIPING SHALL RUN PARALLEL WITH OTHER TRADES <br />PIPING AND WHEREVER PRACTICAL ALL PIPING SHALL BE SUPPORTED ON COMMON GROUP HANGERS. PROVIDE <br />GROUP HANGERS TO SUPPORT PIPING AND PIPING WHEN MULTIPLE TRADES ARE INVOLVED. <br />F. EXPANSION AND CONTRACTION: EXAMINE FINAL COORDINATED PIPING LAYOUT AND INSTALL ANCHORS AND <br />EXPANSION GUIDES AS INDICATED ON THE CONTRACT DOCUMENTS, AND NOTIFY ARCHITECT OF ANY <br />ADDITIONAL ANCHOR POINTS REQUIRED TO ADEQUATELY PROTECT SYSTEM FOR CONFIRMATION STRUCTURE <br />CAN ACCOMMODATE THRUST LOADS AT POINTS OF ANCHORAGE. <br />1. PROVIDE STRUCTURAL STEEL WORK REQUIRED FOR CONTROLLED EXPANSION AND CONTRACTION OF THE <br />PIPING SYSTEM, WHICH MAY UTILIZE A COMBINATION OF LOOPS, PIPE OFFSETS, SWING JOINTS AND <br />EXPANSION JOINTS. <br />2. AT ANCHOR POINTS RIGIDLY ATTACH PIPING SYSTEM TO BUILDING STRUCTURE, AND PROVIDE PIPE GUIDES SO <br />THAT MOVEMENT TAKES PLACE ALONG AXIS OF PIPE ONLY. CONTRACTOR SHALL DESIGN ATTACHMENTS AND <br />SUPPORTING STEEL. <br />3. STRESSES ON PIPE LINES SHALL BE GUIDED AND PIPE SHALL BE SUPPORTED IN SUCH A MANNER THAT PIPE <br />LINES SHALL NOT CREEP, SAG OR BUCKLE. ANCHORS AND SUPPORTS SHALL BE PROVIDED WHEREVER <br />NECESSARY TO PREVENT ANY MISALIGNMENT OF PIPING. <br />H. REDUCTIONS IN SIZE OF HORIZONTAL PIPING SHALL BE MADE WITH ECCENTRIC FITTINGS. IN VERTICAL RISERS, <br />CONCENTRIC REDUCERS MAY BE USED. BUSHINGS WILL NOT BE PERMITTED UNDER ANY CIRCUMSTANCES. <br />I. MINIMUM PITCH OF PIPING SHALL BE AS FOLLOWS: <br />1. HOT AND COLD DOMESTIC WATER SHALL PITCH UP 1 INCH IN 40 FEET IN DIRECTION OF FLOW WITH AIR VENTS <br />AT ALL HIGH POINTS AND DRAIN VALVES AT ALL LOW POINTS TO ALLOW FOR COMPLETE DRAINING OF THE <br />SYSTEM. <br />2. ALL HORIZONTAL RUNS OF SANITARY, WASTE AND STORM PIPES SHALL BE PITCHED AS INDICATED ON <br />DRAWINGS. WHERE NO INDICATION IS GIVEN, THE PITCH SHALL BE 1/8 INCH PER FOOT FOR PIPE LARGER THAN <br />3 INCHES, AND 1/4 INCH PER FOOT FOR PIPE 3 INCHES AND SMALLER. <br />3.04 INSTALLATION - PIPING <br />A. WATER DISTRIBUTION PIPING: <br />1. VALVED OUTLETS: PROVIDE VALVED OUTLETS FOR EXTENSION BY OTHER TRADES AS INDICATED ON <br />DRAWINGS. <br />2. BRANCHES SHALL BE PROVIDED WITH SHUT-OFF VALVES. <br />3. PROVIDE UNIONS OR FLANGES AT EACH VALVE TO PERMIT DISMANTLING OF LINE PIPING AND REMOVAL OF <br />FIXTURES OR EQUIPMENT. <br />4. ELECTRIC EQUIPMENT SPACES: DO NOT RUN ANY PIPING THROUGH TRANSFORMER VAULTS AND OTHER <br />ELECTRICAL, TELEPHONE/ DATA OR ELECTRONIC EQUIPMENT SPACES AND ENCLOSURES. <br />B. DRAINAGE PIPING: <br />1. HORIZONTAL RUNS OF SOIL, WASTE AND STORM PIPES SHALL BE PITCHED AS REQUIRED. WHERE NO <br />NOTATION IS GIVEN, THE PITCH SHALL BE 1/8 INCH PER FOOT FOR PIPE LARGER THAN 3 INCHES, AND 1/4 INCH <br />PER FOOT FOR PIPE 3 INCHES AND SMALLER. <br />2. CLEANOUTS: INSTALL CLEANOUT PLUGS AT EACH 90 DEGREE CHANGE IN DIRECTION IN SUSPENDED <br />HORIZONTAL PIPING. COMPLIANCE WITH LOCAL CODE SHALL BE MINIMUM REQUIREMENTS WITH REGARD TO <br />CLEANOUTS. INSTALL FLOOR AND WALL CLEANOUTS AT LOCATIONS INDICATED. MAINTAIN INTEGRITY OF <br />WATERPROOF MEMBRANES WHERE PENETRATING SUCH FLOORS. <br />a. ALL PARTS OF THE PLUMBING SYSTEM SHALL BE MADE ACCESSIBLE FOR RODDING. <br />b. PROVIDE CLEANOUT TEES WITH BRASS PLUGS AT THE BASE OF ALL DOWNSPOUTS AND SOIL AND WASTE <br />STACKS. <br />3.05 PIPE JOINTS <br />A. THREADED JOINTS: THREAD PIPE IN ACCORDANCE WITH ANSI B2.1, CUT THREADS FULL AND CLEAN USING <br />SHARP DIES. REAM THREADED ENDS TO REMOVE BURRS AND RESTORE FULL INSIDE DIAMETER. APPLY PIPE <br />JOINT COMPOUND, OR PIPE JOINT TAPE (TEFLON) WHERE RECOMMENDED BY PIPE/FITTING MANUFACTURER, ON <br />MALE THREADS AT EACH JOINT AND TIGHTEN JOINT TO LEAVE NOT MORE THAN 3 THREADS EXPOSED. <br />B. SOLDERED JOINTS: <br />1. COPPER PIPE JOINTS SHALL BE MADE UP WITH LEAD FREE SOLDER. <br />2. FITTINGS AND PIPE SHALL BE CLEANED TO FULL DEPTH OF FITTING USING MEDIUM SAND CLOTH OR STEEL <br />WOOL AND A SUITABLE FLUX CLEANING FLUID. <br />3. SWEATING SHALL BE DONE USING TORCH FLAME. JOINTS SHALL BE WIPED CLEAN OF FLUX WHEN COMPLETED. <br />4. WHERE COPPER PIPE OR FITTINGS ARE CONNECTED TO ANY FERROUS PIPE OR FITTINGS OR WHERE THERE IS <br />ANY CONTACT BETWEEN DISSIMILAR METALS, A DIELECTRIC UNION OR COUPLING SHALL BE INSTALLED. <br />C. HUBLESS CAST IRON JOINTS: <br />1. COUPLINGS SHALL BE 24 GAGE, TYPE 304 STAINLESS STEEL WITH HI -TORQUE CLAMPS TIGHTENED TO 100-125 <br />INCH POUNDS TORQUE. COUPLINGS SHALL HAVE NEOPRENE GASKETS AND INTERLOCK WITH THE HOUSING <br />ASSEMBLY TO MAKE A SLIP -FREE JOINT. <br />2. ACCEPTABLE MANUFACTURERS: <br />a. CLAMP -ALL. <br />b. HUSKEY. <br />D. CAST IRON BELL AND SPIGOT JOINTS: <br />1. RUBBER GASKET, SLIP TYPE JOINT MEETING REQUIREMENTS OF ASTM C564. <br />3.06 FLASHINGS <br />A. GENERAL: COORDINATE FLASHING FOR VENT PIPES PASSING THROUGH ROOF, ROOF DRAINS WITH ROOFING <br />MEMBRANE SYSTEM AND FLOOR DRAINS WITH WATERPROOFING MEMBRANE. IF SHEET LEAD IS REQUIRED, <br />PROVIDE 4 POUND SHEET LEAD. <br />B. VENT PIPES: FLASHING SHALL EXTEND 12 INCHES MINIMUM FROM VENT PIPES AND BE EXTENDED UP 3 INCHES <br />MINIMUM ABOVE INCREASER AND TURNED DOWN ON THE INSIDE. <br />3.07 SLEEVES <br />A. M WHERE PIPES PASS THROUGH PARTITIONS IN FINISHED ROOMS EXPOSED TO VIEW, INSTALL NICKEL PLATED <br />METAL ESCUTCHEON PLATES, SPLIT TYPE WITH HEAVY SPRING SECURING PLATES TO PIPE. <br />B. WHERE PIPES ARE COVERED, SLEEVES SHALL BE LARGE ENOUGH TO ALLOW AMPLE CLEARANCE FOR <br />COVERING AND WHERE PIPES PASS THROUGH. <br />C. CENTER OF PIPES SHALL BE IN CENTER OF THE SLEEVES. <br />D. WHERE SLEEVES PASS THROUGH A ROOF FLASH MEETING REQUIREMENTS OF ARTICLE - FLASHINGS, OF THIS <br />SECTION. <br />3.08 HANGERS AND SUPPORTS <br />A. HANGERS AND SUPPORTS SHALL BE PROVIDED FOR ALL PIPING AND TUBING, AND BE MADE OF STEEL OR <br />OTHER DURABLE AND NON-COMBUSTIBLE MATERIALS. WOOD, WIRE OR PERFORATED STRAP IRON SHALL NOT <br />BE USED AS PERMANENT HANGERS OR SUPPORTS. <br />B. INSTALL SO AS NOT TO INTERFERE WITH THE FREE EXPANSION AND CONTRACTION OF PIPING. <br />C. EXCEPT WHERE INDICATED OTHERWISE, HANGERS FOR PIPES SUPPORTED WITH WELDING SADDLES SHALL BE <br />ROLLER TYPE SUPPORTS OF TYPES SPECIFIED HEREINAFTER AND HANGERS FOR ALL OTHER PIPES SHALL BE <br />ADJUSTABLE WROUGHT STEEL, CLEVIS TYPE, GRINNELL FIGURE 260, B - LINE FIGURE B 3100, OR CRAWFORD <br />FIGURE 11. <br />D. HANGERS SHALL BE COMPLETE WITH BOLTS, RODS, AND TWO NUTS FOR EACH BOLT. HANGERS SHALL BE <br />LARGE ENOUGH TO PASS FULL THICKNESS OF INSULATION THROUGH HANGER. THE HANGER ROD DIAMETER <br />AND HANGER SPACING SHALL BE AS FOLLOWS: <br />MAX. VERTICAL <br />PIPE SIZE <br />DIAMETER OF <br />MAX. HORIZONTAL <br />ON CENTER <br />INCHES <br />ROD(INCHES) <br />SPACING (FEET) <br />SPACING (FEET) <br />Y TO 2 <br />% <br />8 <br />10 <br />TO 3 <br />Y <br />10 <br />10 <br />4AND5 <br />% <br />13 <br />10 <br />6 <br />' <br />15 <br />10 <br />8 TO 12 <br />Y8 <br />15 <br />10 <br />E. HANGERS OF GROUPS OF PIPES SHALL BE FABRICATED FROM UNISTRUT SECTIONS OR STRUCTURAL STEEL <br />SHAPES SUPPORTED FROM CEILING HANGERS. RODS SHALL BE THREADED AND A NUT AND WASHER SHALL BE <br />PROVIDED FOR EACH SIDE OF ANGLES FOR EACH ROD WITH A DOUBLE LOCKING NUT ON TOP OF EACH ANGLE. <br />F. PIPING SHALL BE FIRMLY SUPPORTED BY RISER CLAMPS PROPERLY INSTALLED TO RELIEVE WEIGHT FROM <br />FITTINGS AND PIPING AT BASE OF RISERS. <br />G. PIPING SHALL BE FIRMLY SUPPORTED AT INTERVALS NOT GREATER THAN SPECIFIED IN THIS ARTICLE ON <br />STRAIGHT RUNS AND AT ALL CHANGES IN DIRECTION BY MEANS OF CEILING HANGERS. WHEN PIPING IS CLOSE <br />TO FLOOR, IT SHALL BE MOUNTED ON FLOOR STANDS OR ON MASONRY PIERS IF PIPE IS NOT MORE THAN 18 <br />INCHES ABOVE FLOOR. <br />H. BARE COPPER PIPING SHALL HAVE COPPER PLATED HANGERS OR CLAMPS. <br />I. INSULATED PIPING: <br />1. ALL PIPE INSULATION SHALL BE PROTECTED TO PREVENT CRUSHING AT SUPPORT POINTS. <br />2. FURNISH AND WELD TO THE PIPE AT EACH HANGER A CRAWFORD FIGURE 22, B - LINE FIGURE B 3160 OR <br />GRINNELL FIGURE 160 WELDED PIPE COVERING PROTECTION SADDLE OF PROPER DEPTH EXCEPT FOLLOWING: <br />a. ALL PIPING IN SIZES OF 2 INCHES AND SMALLER. <br />b. ALL COLD WATER AND ALL OTHER PIPING HAVING INTERNAL TEMPERATURES BELOW 60 F. <br />1. FOR INSULATED PIPING NOT SUPPORTED BY WELDING SADDLES, PROVIDE TEMPORARY SUPPORT AND A <br />COVERING SHIELD TO FIT AROUND BOTTOM HALF OF INSULATION FOR PERMANENT SUPPORT. SHIELDS SHALL <br />BE 16 GAGE GALVANIZED STEEL MANUFACTURED BY GRINNELL FIGURE 167, B - LINE FIGURE B-3151 OR <br />CRAWFORD FIGURE 265-P. <br />3.09 PRESSURE TESTS <br />A. CONDUCT PRESSURE TESTS ON ALL PIPING SYSTEMS IN PRESENCE OF AUTHORITIES BEARING ON <br />PERFORMANCE OF THE WORK. <br />B. PROVIDE TEMPORARY EQUIPMENT FOR TESTING INCLUDING PUMP AND GAUGES. TEST PIPING SYSTEM BEFORE <br />INSULATION IS INSTALLED WHEREVER FEASIBLE. TEST EACH NATURAL SECTION OF EACH PIPING SYSTEM <br />INDEPENDENTLY. FILL EACH SECTION WITH WATER AND PRESSURIZE FOR THE INDICATED PRESSURE AND TIME. <br />C. REPAIR PIPING SYSTEMS SECTIONS WHICH FAIL REQUIRED TEST BY DISASSEMBLY AND REINSTALLATION, USING <br />NEW MATERIALS TO EXTENT REQUIRED TO OVERCOME LEAKAGE. DO NOT USE CHEMICALS, STOP LEAK <br />COMPOUNDS, MASTIC, OR OTHER TEMPORARY REPAIR METHODS. <br />D. THOROUGHLY FLUSH SYSTEM AFTER TESTS AND DISINFECT SYSTEM AS REQUIRED BY AUTHORITIES BEARING <br />ON PERFORMANCE OF THE WORK. <br />3.10 VALVE TAGS <br />A. EACH VALVE IN THE PIPING SYSTEM SHALL HAVE A BRASS IDENTIFICATION TAG WITH STAMPED NUMBER <br />AFFIXED TO VALVE BY CHAIN OR S-HOOK. <br />END OF SECTION <br />4 <br />09.18.2013 <br />ISSUE FOR PERMIT <br />3 <br />2 <br />09.11.2013 <br />09.03.2013 <br />ISSUE FOR BIDS <br />CD REVIEW PACKAGE <br />1 <br />NO. <br />08.16.2013 <br />DATE <br />DO REVIEW PACKAGE <br />REVISIONS/ISSUANCES <br />��PSTEIN <br />Architecture <br />Chicago <br />Interiors <br />New York <br />Engineering <br />Bucharest <br />Construction <br />Warsaw <br />600 W. Fulton Street <br />Chicago, IL 60661-1259 <br />T 312.454.9100 <br />www.epsteinglobal.com <br />PROJECT NUMBER: <br />12386 <br />PROJECT MANAGER: <br />JK <br />ARCH/ENG: <br />VD <br />SCALE: <br />NTS <br />DRAWN BY: <br />PV <br />CHECKED BY: <br />VD <br />,.•• A ;� g PLUMBING <br />MEP / FP Engineer Design Architect Nestle Waters North America _ TM ; • ` �� A SPECIFICATIONS <br />EPSTEIN <br />600 West Fulton <br />Chicago, IL 60661 <br />312.454.9100 <br />EPSTEIN <br />600 West Fulton <br />Chicago, IL 60661 <br />312.454.9100 <br />Nestle Waters North America <br />4330 20th Street <br />Zephyrhills, Florida 33542-6703 <br />972.462.3663 <br />Waters <br />NORTH AMERICA <br />10' STATE OF <br />sus .• � ® K ,• � w <br />2 .L7 • / <br />P-004 <br />A. Epstein and Sons Intem clonal, Inc. AA rights reserved. <br />