SECTION 09650 - RESILIENT BASE
<br />1. MANUFACTURER: PROVIDE EACH TYPE OF RESILIENT BASE AND
<br />ACCESSORIES AS PRODUCED BY A SINGLE MANUFACTURER, INCLUDING
<br />RECOMMENDED PRIMERS, ADHESIVES, SEALANTS, AND LEVELING
<br />COMPOUNDS.
<br />2. SUBMIT TO THE ARCHITECT THE FOLLOWING:
<br />a. SAMPLES OF EACH TYPE, AND COLOR OF RESILIENT BASE REQUIRED,
<br />SHOWING FULL -RANGE OR COLOR AND PATTERN VARIATIONS AS
<br />SPECIFIED.
<br />b. PRODUCT DATA FOR PRIMERS, ADHESIVES, SEALANTS AND LEVELING
<br />COMPOUNDS.
<br />4. PROJECT CONDITIONS: MAINTAIN AMBIENT TEMPERATURES WITHIN RANGE
<br />RECOMMENDED BY MANUFACTURER, BUT NOT LESS THAT 70 DEG F OR MORE
<br />THAN 95 DEG F, IN SPACES TO RECEIVE FLOOR TILE 48 HOURS BEFORE THE
<br />INSTALLATION, DURING INSTALLATION AND 48 HOURS AFTER INSTALLATION.
<br />6. WALL BASE: PROVIDE RUBBER BASE COMPLYING WITH ASTM F1861, TYPE TP,
<br />GROUP 1 (SOLID), WITH MATCHING END STOPS AND PREFORMED OR MOLDED
<br />CORNER UNITS, AND AS FOLLOWS:
<br />A. HEIGHT: 4IN.
<br />B. THICKNESS: 1/8 IN. NOMINAL
<br />C. FINISH: MATTE SHEEN
<br />D. PROFILE: STRAIGHT AND COVED, AS SCHEDULED
<br />E. ADHESIVES (CEMENTS): WATERPROOF, STABILIZED TYPE AS
<br />RECOMMENDED BY MANUFACTURER TO SUIT MATERIAL AND
<br />SUBSTRATE CONDITIONS
<br />7. INSTALL RESILIENT BASE USING METHOD INDICATED IN STRICT COMPLIANCE
<br />WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. EXTEND RESILIENT
<br />FLOORING INTO TOE SPACES, DOOR REVEALS AND INTO CLOSETS AND
<br />SIMILAR OPENINGS.
<br />8. APPLY WALL BASE TO WALLS, COLUMNS, PILASTERS AND OTHER PERMANENT
<br />FIXTURES IN ROOMS OR AREAS WHERE BASE IS REQUIRED. INSTALL BASE IN
<br />LENGTHS AS LONG AS PRACTICABLE, WITH PREFORMED CORNER UNITS, OR
<br />FABRICATED FORM BASE MATERIALS WITH MITERED OR COPED INSIDE
<br />CORNERS. TIGHTLY BOND BASE TO SUBSTRATE THROUGHOUT LENGTH OF
<br />EACH PIECE, WITH CONTINUOUS CONTACT AT HORIZONTAL AND VERTICAL
<br />SURFACES. ON MASONRY SURFACES, OR OTHER SIMILAR IRREGULAR
<br />SUBSTRATES, FILL VOIDS ALONG TOP EDGE OF RESILIENT WALL BASE WITH
<br />MANUFACTURER'S RECOMMENDED ADHESIVE FILLER MATERIAL. PROVIDE
<br />COVE BASE AT RESILIENT FLOORING, U.N.O.
<br />9. EXTRA STOCK FURNISHED TO THE TENANT: NOT LESS THAN 1-BOX FOR EACH
<br />50-BOXES, OR FRACTION THEREOF, FOR EACH TYPE, COLOR, PATTERN AND
<br />SIZE INSTALLED.
<br />10. CLEANING: COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR
<br />CLEANING AND PROTECTION.
<br />SECTION 09672 - RESINOUS FLOORING
<br />1. SUBMITTALS: SUBMIT PRODUCT DATA FOR EACH TYPE OF PRODUCT
<br />INDICATED. SUBMIT SAMPLES FOR VERIFICATION, 6 INCHES (150 MM)
<br />SQUARE, APPLIED TO A RIGID BACKING BY INSTALLER FOR THIS PROJECT.
<br />2. INSTALLER QUALIFICATIONS: ENGAGE AN INSTALLER WHO IS CERTIFIED IN
<br />WRITING BY RESINOUS FLOORING MANUFACTURER AS QUALIFIED TO APPLY
<br />RESINOUS FLOORING SYSTEMS INDICATED.
<br />3. SOURCE LIMITATIONS: OBTAIN PRIMARY RESINOUS FLOORING MATERIALS,
<br />INCLUDING PRIMERS, RESINS, HARDENING AGENTS, GROUTING COATS, AND
<br />TOPCOATS, THROUGH ONE SOURCE FROM A SINGLE MANUFACTURER.
<br />PROVIDE SECONDARY MATERIALS, INCLUDING PATCHING AND FILL MATERIAL,
<br />JOINT SEALANT, AND REPAIR MATERIALS, OF TYPE AND FROM SOURCE
<br />RECOMMENDED BY MANUFACTURER OF PRIMARY MATERIALS FOR SYSTEM
<br />INDICATED.
<br />SECTION 09672 - RESINOUS FLOORING (CONT'D) SECTION 09900 - PAINTING (CONT'D)
<br />5. FIELD TECHNICAL SERVICES REPRESENTATIVES SHALL BE EMPLOYED BY THE 5. UNLESS OTHERWISE INDICATED, ALL SURFACES FOR PAINT FINISH SHALL
<br />SYSTEM MANUFACTURER TO ASSIST IN THE QUALITY ASSURANCE AND RECEIVE 1-COAT OF PRIMER AND 2-COATS OF FINISH PAINT, AS NECESSARY:
<br />QUALITY CONTROL PROCESS OF THE INSTALLATION AND SHALL BE AVAILABLE a. ALL GYPSUM BOARD SURFACES:
<br />TO PERFORM FIELD PROBLEM SOLVING ISSUES WITH THE INSTALLER.
<br />1-COAT LOW-VOC LATEX WALL PRIMER
<br />6. DELIVER MATERIALS IN ORIGINAL PACKAGES AND CONTAINERS, WITH SEALS MINIMUM 2-COATS LOW-VOC LATEX SEMI -GLOSS FINISH COATS
<br />UNBROKEN, BEARING MANUFACTURER'S LABELS INDICATING BRAND NAME b. ALL METAL WORK NOT OTHERWISE SPECIFIED INCLUDING
<br />AND DIRECTIONS FOR STORAGE AND MIXING WITH OTHER COMPONENTS. MISCELLANEOUS METALS, AND OTHER FERROUS METAL WORK:
<br />STORE MATERIALS TO PREVENT DETERIORATION FROM MOISTURE, HEAT, 1-COAT RUST INHIBITIVE LOW-VOC LATEX PRIMER
<br />COLD, DIRECT SUNLIGHT, OR OTHER DETRIMENTAL EFFECTS. 1-FINISH COAT ALKYD LOW-VOC SEMI -GLOSS ENAMEL
<br />7. ENVIRONMENTAL LIMITATIONS: COMPLY WITH RESINOUS FLOORING c PREVIOUSLY PAINTED SURFACES
<br />MANUFACTURER'S WRITTEN INSTRUCTIONS FOR SUBSTRATE TEMPERATURE,
<br />AMBIENT TEMPERATURE, MOISTURE, VENTILATION, AND OTHER CONDITIONS
<br />AFFECTING RESINOUS FLOORING APPLICATION.
<br />8. LIGHTING: PROVIDE PERMANENT LIGHTING OR, IF PERMANENT LIGHTING IS
<br />NOT IN PLACE, SIMULATE PERMANENT LIGHTING CONDITIONS DURING
<br />RESINOUS FLOORING APPLICATION.
<br />9. CLOSE SPACES TO TRAFFIC DURING RESINOUS FLOORING APPLICATION AND
<br />FOR NOT LESS THAN 24 HOURS AFTER APPLICATION, UNLESS
<br />MANUFACTURER RECOMMENDS A LONGER PERIOD.
<br />10. QUALITY CONTROL: MOISTURE TESTING: PERFORM ANHYDROUS CALCIUM
<br />CHLORIDE TEST ACCORDING TO ASTM F 1869. PROCEED WITH INSTALLATION
<br />ONLY AFTER SUBSTRATES HAVE MAXIMUM MOISTURE -VAPOR -EMISSION RATE
<br />PER MANUFACTURER'S RECOMMENDATIONS.
<br />11. MANUFACTURER SHALL FURNISH A SINGLE, WRITTEN WARRANTY COVERING
<br />BOTH MATERIAL AND WORKMANSHIP FOR A PERIOD OF (1) FULL YEARS FROM
<br />DATE OF INSTALLATION, OR PROVIDE A JOINT AND SEVERAL WARRANTY
<br />SIGNED ON A SINGLE DOCUMENT BY MATERIAL MANUFACTURER AND
<br />APPLICATOR JOINTLY AND SEVERALLY WARRANTING THE MATERIALS AND
<br />WORKMANSHIP FOR A PERIOD OF (1) FULL YEAR FROM DATE OF
<br />INSTALLATION. A SAMPLE WARRANTY LETTER MUST BE INCLUDED WITH BID
<br />PACKAGE OR BID MAY BE DISQUALIFIED.
<br />MINIMUM 2-COATS LOW-VOC LATEX SEMI -GLOSS
<br />6. CONTRACTOR TO PROVIDE A 6' x 6' SAMPLE AT EACH WALL SCHEDULED TO
<br />RECEIVE COLOR AS INDICATED ON DRAWINGS. ARCHITECT AND TENANT
<br />APPROVAL REQUIRED TO PROCEED WITH COMPLETION.
<br />7. AT COMPLETION OF WORK, TOUCHUP AND RESTORE FINISH WHERE
<br />DAMAGED, AND LEAVE WORK IN PERFECT CONDITION, SATISFACTORY TO THE
<br />ARCHITECT AND TENANT.
<br />8. REPAIR OR REPLACE, AT CONTRACTOR'S EXPENSE, ANY AND ALL WORK
<br />DAMAGED AS A RESULT OF THE APPLICATION OF THE WORK IN THIS SECTION.
<br />9. ALL COATS OF PAINT SHALL BE THOROUGHLY DRY BEFORE SUCCEEDING
<br />COATS ARE APPLIED. \
<br />10. ALL PAINTS SHALL BE PRODUCTS OF ONE MANUFACTURER, SO AS TO
<br />ENDURE COMPATIBILITY OF UNDERCOATS WITH TOP COATS. FURNISH PAINT
<br />BY MANUFACTURERS AS NOTED ON CONTRACT DOCUMENTS.
<br />11. EXTRA MATERIALS FURNISHED TO THE TENANT: FURNISH AN ADDITIONAL 5
<br />PERCENT, BUT NOT LESS THAN 1 GAL, OF EACH MATERIAL AND COLOR
<br />APPLIED, FROM SAME PRODUCTION RUN (BATCH MIX) AS MATERIALS APPLIED
<br />AND THAT ARE PACKAGED FOR STORAGE AND IDENTIFIED WITH LABELS
<br />DESCRIBING CONTENTS.
<br />12. PREPARATION: PREPARE, PATCH, FILL, AND CLEAN SUBSTRATES ACCORDING 12. SUBMITTALS: SUBMIT PRODUCT SPECIFICATIONS, TECHNICAL DATA,
<br />TO RESINOUS FLOORING MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INCLUDING PAINT ANALYSIS, AND APPLICATION INSTRUCTIONS FOR EACH
<br />SUBSTRATE INDICATED. PRODUCT. SUBMIT 3 DRAWDOWNS OF EACH PRODUCT AND COLOR
<br />COMBINATION. DRAWDOWNS SHALL BE APPLIED USING A 4 MIL WET FILM
<br />13. APPLICATION: APPLY COMPONENTS OF RESINOUS FLOORING SYSTEM
<br />ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS TO PRODUCE A
<br />UNIFORM, MONOLITHIC WEARING SURFACE OF THICKNESS INDICATED. APPLY
<br />JOINT SEALANT TO COMPLY WITH MANUFACTURER'S WRITTEN
<br />RECOMMENDATIONS. APPLY METAL TROWEL SINGLE MORTAR COAT IN
<br />THICKNESS INDICATED FOR FLOORING SYSTEM. HAND OR POWER TROWEL
<br />AND GROUT TO FILL VOIDS. WHEN CURED, SAND TO REMOVE TROWEL MARKS
<br />AND ROUGHNESS. APPLY TOPCOAT(S) IN NUMBER OF COATS INDICATED FOR
<br />FLOORING SYSTEM AND AT SPREADING RATES RECOMMENDED IN WRITING BY
<br />MANUFACTURER.
<br />14. INTEGRAL COVE BASE (WHERE INDICATED): APPLY ACCORDING TO
<br />MANUFACTURER'S WRITTEN INSTRUCTIONS AND DETAILS INCLUDING THOSE
<br />FOR TAPING, MIXING, PRIMING, TROWELING, SANDING, OF COVE BASE.
<br />ROUND INTERNAL AND EXTERNAL CORNERS.
<br />15. TERMINATIONS: CHASE EDGES TO "LOCK" THE FLOORING SYSTEM INTO THE
<br />CONCRETE SUBSTRATE ALONG LINES OF TERMINATION. LAP AND SEAL
<br />RESINOUS SYSTEM ONTO THE PERIMETER OF THE PENETRATING ITEMS BY
<br />BRIDGING OVER COMPATIBLE ELASTOMER AT THE INTERFACE TO
<br />COMPENSATE FOR POSSIBLE MOVEMENT. CONTINUE FLOORING SYSTEM
<br />INTO TRENCHES TO MAINTAIN MONOLITHIC PROTECTION. TREAT COLD
<br />JOINTS TO ASSURE BRIDGING OF POTENTIAL CRACKS. TREAT FLOOR DRAINS
<br />BY CHASING THE FLOORING SYSTEM TO LOCK IN PLACE AT POINT OF
<br />TERMINATION.
<br />16. JOINTS AND CRACKS: TREAT CONTROL JOINTS TO BRIDGE POTENTIAL
<br />CRACKS AND TO MAINTAIN MONOLITHIC PROTECTION. TREAT COLD JOINTS
<br />AND CONSTRUCTION JOINTS TO BRIDGE POTENTIAL CRACKS AND TO
<br />MAINTAIN MONOLITHIC PROTECTION ON HORIZONTAL AND VERTICAL
<br />SURFACES AS WELL AS HORIZONTAL AND VERTICAL INTERFACES.
<br />DISCONTINUE FLOOR COATING SYSTEM AT VERTICAL AND HORIZONTAL
<br />CONTRACTION AND EXPANSION JOINTS BY INSTALLING BACKER ROD AND
<br />COMPATIBLE SEALANT AFTER COATING INSTALLATION IS COMPLETED.
<br />PROVIDE SEALANT TYPE RECOMMENDED BY MANUFACTURER FOR TRAFFIC
<br />CONDITIONS AND CHEMICAL EXPOSURES TO BE ENCOUNTERED.
<br />17. CLEANING, PROTECTING, CURING: CURE RESINOUS FLOORING MATERIALS IN
<br />COMPLIANCE WITH MANUFACTURER'S DIRECTIONS, TAKING CARE TO
<br />PREVENT CONTAMINATION DURING STAGES OF APPLICATION AND PRIOR TO
<br />COMPLETION OF CURING PROCESS. CLOSE AREA OF APPLICATION FOR A
<br />MINIMUM OF 18 HOURS. PROTECT RESINOUS FLOORING MATERIALS FROM
<br />DAMAGE AND WEAR DURING CONSTRUCTION OPERATION. WHERE
<br />TEMPORARY COVERING IS REQUIRED FOR THIS PURPOSE, COMPLY WITH
<br />MANUFACTURER'S RECOMMENDATIONS FOR PROTECTIVE MATERIALS AND
<br />METHOD OF APPLICATION. GENERAL CONTRACTOR IS RESPONSIBLE FOR
<br />PROTECTION AND CLEANING OF SURFACES AFTER FINAL COATS. REMOVE
<br />TEMPORARY COVERING AND CLEAN RESINOUS FLOORING JUST PRIOR TO
<br />FINAL INSPECTION. USE CLEANING MATERIALS AND PROCEDURES
<br />RECOMMENDED BY RESINOUS FLOORING MANUFACTURER.
<br />SECTION 09900 - PAINTING
<br />1. THE EXTENT OF REQUIRED PAINTING IS INDICATED ON THE DRAWINGS.
<br />2. THE CONTRACTOR SHALL INSPECT AND PREPARE THE EXISTING SURFACE
<br />AND SUBSURFACE CONDITIONS PER PAINT MANUFACTURER'S INSTRUCTIONS.
<br />ALL PAINT SHALL BE APPLIED IN ACCORDANCE WITH MANUFACTURER'S
<br />SPECIFICATIONS FOR THE PARTICULAR SURFACE.
<br />3. PREPARATION OF SURFACE FOR PAINTING AND FINISHING:
<br />a. HARDWARE, PLATES AND SIMILAR ITEMS SHALL BE REMOVED OR
<br />PROTECTED AND MARKED AS REQUIRED DURING PAINTING.
<br />b. ALL HOLES AND CRACKS IN PLASTER AND DRYWALL SURFACES SHALL BE
<br />FILLED WITH SPACKLING COMPOUND. PLASTER AND DRYWALL SURFACES
<br />SHALL BE FREE OF DUST, GREASE AND DIRT, AND SHALL BE
<br />SUFFICIENTLY DRY TO ASSURE GOOD ADHESION OF PAINT.
<br />THICKNESS DRAWDOWN BAR ON LENETA FORM WD WHITE COATED CARDS,
<br />SIZE 4" X 6" MINIMUM. LABEL EACH CARD WITH PROJECT NAME, DATE,
<br />PRODUCT NAME AND NUMBER, COLOR NUMBER AS STATED IN SCHEDULE,
<br />AND NAME, ADDRESS AND TELEPHONE NUMBER OF SUPPLYING FACILITY.
<br />RESUBMIT UNTIL ACCEPTABLE COLOR AND SHEEN IS ACHIEVED.
<br />SECTION 12241 - ROLLER WINDOW SHADES
<br />1. SUBMIT PRODUCT DATA FOR EACH TYPE OF PRODUCT. INCLUDE STYLES,
<br />MATERIAL DESCRIPTIONS, CONSTRUCTION DETAILS, DIMENSIONS OF
<br />INDIVIDUAL COMPONENTS AND PROFILES, FEATURES, FINISHES, AND
<br />OPERATING INSTRUCTIONS FOR ROLLER SHADES.
<br />2. SUBMIT SAMPLES FOR EACH EXPOSED PRODUCT AND FOR EACH COLOR AND
<br />TEXTURE SPECIFIED.
<br />3. INSTALL ROLLER SHADES LEVEL, PLUMB, AND ALIGNED WITH ADJACENT
<br />UNITS, ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS. ADJUST
<br />AND BALANCE ROLLER SHADES TO OPERATE SMOOTHLY, EASILY, SAFELY,
<br />AND FREE FROM BINDING OR MALFUNCTION THROUGHOUT ENTIRE
<br />OPERATIONAL RANGE.
<br />4. CLEAN ROLLER -SHADE SURFACES AFTER INSTALLATION, ACCORDING TO
<br />MANUFACTURER'S WRITTEN INSTRUCTIONS.
<br />SECTION 15000 - HEATING, VENTILATION AND AIR
<br />CONDITIONING
<br />1. SEE RELEVANT ENGINEERING DRAWINGS FOR ADDITIONAL INFORMATION,
<br />INCLUDING BUT NOT LIMITED TO PLANS, DIAGRAMS, DETAILS, NOTES AND
<br />SCHEDULES.
<br />2. ALL HVAC WORK SHALL COMPLY WITH LOCAL GOVERNING CODES AND OTHER
<br />APPLICABLE ORDINANCES OR AUTHORITIES HAVING JURISDICTION.
<br />3. THE HVAC CONTRACTOR SHALL INCLUDE ALL CUTTING AND PATCHING OF
<br />BUILDING MATERIALS REQUIRED FOR THE INSTALLATION OF HIS WORK IN HIS
<br />INITIAL COST.
<br />4. THE ENTIRE HVAC DUCTWORK SYSTEM SHALL BE INSTALLED IN ACCORDANCE
<br />WITH THE LATEST EDITION OF THE SMACNA GUIDELINES FOR SHEET METAL
<br />WORK.
<br />5. THE HVAC CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, SAMPLES AND
<br />PRODUCT DATA OF THE SPECIFIED WORK FOR REVIEW BY THE GENERAL
<br />CONTRACTOR, ARCHITECT, CONSULTING ENGINEER AND TENANT AS
<br />SPECIFIED IN SECTION 01340. SUPPLY ONE ADDITIONAL COPY FOR EACH ITEM
<br />SUBMITTED.
<br />6. SEE ADDITIONAL GENERAL NOTES AND SPECIFICATIONS ON THE HVAC
<br />DRAWINGS AND REPORT ANY DISCREPANCIES TO THE ARCHITECT BEFORE
<br />COMMENCING WORK.
<br />7. THE HVAC CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE
<br />CONSTRUCTION OF A COMPLETE HVAC SYSTEM INCLUDING AND IN ADDITION
<br />TO THE HVAC WORK INDICATED HEREIN. THE HVAC CONTRACTOR SHALL
<br />NOTIFY THE ARCHITECT IMMEDIATELY, IN WRITING, OF ANY CONFLICTS
<br />SHOWN BETWEEN HIS WORK AND THE WORK OF ANY OTHER TRADES. ANY
<br />SYSTEM LOCATION OR SPECIAL EQUIPMENT LOCATIONS INDICATED IN THESE
<br />DRAWINGS OR SPECIFICATIONS SHALL BE INCLUDED IN THE CONTRACTOR'S
<br />WORK, AS SHALL ANY EXISTING DEVICES TO REMAIN. SEE RELEVANT
<br />MECHANICAL DRAWINGS.
<br />8. HVAC CONTRACTOR SHALL TEST AND BALANCE THE COMPLETE SYSTEM
<br />SUBSEQUENT TO INSTALLATION AND SHALL PROVIDE A TEST AND BALANCE
<br />REPORT TO THE ARCHITECT AND OWNER.
<br />9. HVAC CONTRACTOR TO ADJUST SYSTEM BASED ON PRELIMINARTY TEST AND
<br />BALANCE REPORT, TO COMPLY WITH THE REQUIREMENTS OF THE CONTRACT
<br />DOCUMENTS, AND SHALL PROVIDE A FINAL TEST AND BALANCE REPORT TO
<br />CONFIRM COMPLIANCE WITH THE CONTRACT DOCUMENTS.
<br />MEP / FP Engineer
<br />EPSTEIN
<br />600 West Fulton
<br />Chicago, IL 60661
<br />312.454.9100
<br />SECTION 15310 - FIRE SUPPRESSION
<br />1. SEE RELEVANT ENGINEERING DRAWINGS FOR ADDITIONAL INFORMATION.
<br />2. COORDINATE DESIGN AND CONSTRUCTION WITH OWNER.
<br />3. ALL SPRINKLER WORK SHALL COMPLY WITH LOCAL GOVERNING BUILDING
<br />CODES AND OTHER APPLICABLE ORDINANCES OR AUTHORITIES HAVING
<br />JURISDICTION.
<br />4. REVIEW ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR FIRE ISSUES AND
<br />ADDITIONAL NOTES AND SPECIFICATIONS. REPORT ANY DISCREPANCIES TO
<br />THE ARCHITECT.
<br />5. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR
<br />RELOCATION OF ANY ADDITIONAL SPRINKLER HEADS OUTSIDE OF THE
<br />DEMISED TENANT SPACE IN ORDER TO MEET CODE REQUIREMENTS.
<br />6. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR
<br />COORDINATING ALL REQUIRED CEILING, DUCT, CLOSET, ETC. DETECTION
<br />SYSTEMS/DEVICES WITH THE GENERAL CONTRACTOR AND OTHER
<br />SUBCONTRACTORS.
<br />7. CENTER SPRINKLER HEADS ON CEILING TILES OR AS INDICATED ON RCP.
<br />WHERE NO DIMENSIONS ARE GIVEN, ASSUME EQUAL SPACING FOR ALIGNED
<br />HEADS.
<br />8. THE FIRE PROTECTION CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE
<br />COMPLETE DESIGN, ENGINEERING AND CONSTRUCTION OF A COMPLETE FIRE
<br />PROTECTION SYSTEM INCLUDING AND IN ADDITION TO THE FIRE PROTECTION
<br />WORK INDICATED HEREIN. THE FIRE PROTECTION CONTRACTOR SHALL
<br />SUBMIT CONSTRUCTION DRAWINGS OF HIS ENGINEERED DESIGN
<br />FOR THE PERMIT APPLICATIONS. THE FIRE
<br />PROTECTION CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY, IN
<br />WRITING, OF ANY CONFLICTS SHOWN BETWEEN HIS WORK AND THE WORK OF
<br />ANY OTHER TRADES. ANY SYSTEM LOCATIONS OR SPECIAL EQUIPMENT
<br />LOCATIONS INDICATED IN THESE DRAWINGS OR SPECIFICATIONS SHALL BE
<br />INCLUDED IN THE CONTRACTOR'S DESIGN AS SHALL ANY EXISTING DEVICES
<br />TO REMAIN. EPSTEIN WILL PROVIDE BACKGROUND CAD DRAWINGS FOR THE
<br />CONTRACTOR'S USE.
<br />SECTION 15400 - PLUMBING
<br />1. SEE ENGINEERING DRAWINGS FOR ADDITIONAL INFORMATION, INCLUDING
<br />BUT NOT LIMITED TO PLUMBING PLANS, NOTES, DETAILS, DIAGRAMS AND
<br />SCHEDULES.
<br />2. ALL WORK SHALL BE IN CONFORMANCE WITH THE LOCAL GOVERNING
<br />PLUMBING CODE REQUIREMENTS.
<br />3. ALL MATERIAL SHALL BE NEW, SHALL BE INSTALLED IN A FIRST CLASS,
<br />WORKMANLIKE MANNER, AND SHALL BE GUARANTEED TO BE FREE OF
<br />DEFECTS FOR A PERIOD OF ONE YEAR FROM THE ESTABLISHED DATE OF
<br />SUBSTANTIAL COMPLETION.
<br />4. ALL FIXTURES SHALL BE INSTALLED PER THE MANUFACTURER'S
<br />RECOMMENDATIONS FOR INSTALLATION.
<br />5. PROVIDE 12 IN. AIR CHAMBERS AT ALL HOT AND COLD WATER SUPPLY LINE
<br />CONNECTIONS TO FIXTURES.
<br />6. REFER TO THE PLUMBING DRAWINGS FOR PLUMBING WORK AND ADDITIONAL
<br />GENERAL NOTES AND SPECIFICATIONS. REPORT ANY DISCREPANCIES TO THE
<br />ARCHITECT BEFORE COMMENCING WORK.
<br />7. THE PLUMBING CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, SAMPLES AND
<br />PRODUCT DATA OF THE SPECIFIED WORK FOR REVIEW BY THE GENERAL
<br />CONTRACTOR, ARCHITECT, CONSULTING ENGINEER AND TENANT AS
<br />SPECIFIED IN SECTION 01340. SUPPLY ONE ADDITIONAL COPY FOR EACH
<br />PLUMBING ITEM SUBMITTED.
<br />8. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE
<br />CONSTRUCTION OF COMPLETE PLUMBING AND SANITARY SYSTEMS. THE
<br />PLUMBING CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY, IN
<br />WRITING, OF ANY CONFLICTS SHOWN BETWEEN HIS WORK AND THE WORK OF
<br />ANY TRADE. ANY SYSTEM LOCATIONS OR SPECIAL FIXTURE LOCATIONS
<br />INDICATED IN THESE DRAWINGS OR SPECIFICATIONS SHALL BE INCLUDED IN
<br />THE CONTRACTOR'S WORK, AS SHALL ANY EXISTING PARTS TO REMAIN. THE
<br />CONTRACTOR IS TO COORDINATE PROJECT REQUIREMENTS WITH THOSE
<br />REQUIREMENTS OF SPECIAL EQUIPMENT INSTALLATIONS. SEE RELEVANT
<br />PLUMBING DRAWINGS.
<br />SECTION 16000 - ELECTRICAL
<br />1. SEE ENGINEERING DRAWINGS FOR ADDITIONAL INFORMATION, INCLUDING
<br />BUT NOT LIMITED TO PLUMBING PLANS, NOTES, DETAILS, DIAGRAMS AND
<br />SCHEDULES.
<br />2. ALL ELECTRICAL WORK SHALL COMPLY WITH LOCAL GOVERNING BUILDING
<br />CODES AND OTHER APPLICABLE ORDINANCES OR AUTHORITIES HAVING
<br />JURISDICTION.
<br />3. ELECTRICAL CIRCUITRY SHALL BE IDENTIFIED AND LABELED IN THE MASTER
<br />ELECTRICAL PANEL.
<br />Design Architect
<br />EPSTEIN
<br />600 West Fulton
<br />Chicago, IL 60661
<br />312.454.9100
<br />Nestle Waters North America
<br />Nestle Waters North America
<br />4330 20th Street
<br />Zephyrhills, Florida 33542-6703
<br />972.462.3663
<br />SECTION 16000 - ELECTRICAL (CONT'D)
<br />5. ELECTRICAL CIRCUITRY SHALL BE IDENTIFIED AND LABELED IN THE MASTER
<br />ELECTRICAL PANEL.
<br />6. ELECTRICAL CONTRACTOR SHALL INCLUDE ALL CUTTING AND PATCHING OF
<br />BUILDING MATERIALS REQUIRED FOR THE INSTALLATION OF HIS WORK IN HIS
<br />INITIAL COST.
<br />7. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ELECTRICAL
<br />POWER, CONDUIT AND CABLE CONNECTING POWER PANELS TO THE BUILDING
<br />POWER CIRCUITS.
<br />8. WHERE EXISTING POWER CIRCUITS HAVE BEEN DISTURBED, ALL COSTS FOR
<br />RECIRCUITING OF SAME SHOULD BE CONSIDERED UPON SUBMISSION OF
<br />INITIAL COST.
<br />9. THE ELECTRICAL CONTRACTOR SHALL VERIFY REQUIREMENTS FOR SPECIAL
<br />EQUIPMENT WITH MANUFACTURER BEFORE INSTALLATION.
<br />10. WALL ELECTRICAL AND/OR TELEPHONE AND DATA BOXES ON OPPOSITE
<br />FACES OF SAME WALL ARE TO BE STAGGERED AND SEPARATED BY WALL
<br />FRAMING MEMBERS AND INSULATION WITHIN THE WALL.
<br />11. ELECTRICAL CONTRACTOR SHALL INCLUDE UNIT PRICES IN THE PROPOSAL
<br />FOR FURNISHING AND INSTALLING WALL MOUNTED DUPLEX AND
<br />QUADRUPLEX OUTLETS, COMMUNICATIONS OUTLETS AND PHONE OUTLETS.
<br />12. WHERE MULTIPLE ELECTRICAL DEVICES OCCUR, I.E. SEVERAL WALL
<br />SWITCHES IN THE SAME LOCATION, A MULTI -GANG COVER PLATE SHALL BE
<br />INSTALLED.
<br />13. ELECTRICAL CONTRACTOR SHALL COORDINATE INSTALLATION OF WORK
<br />REQUIRED BY OTHER TRADES FOR THE COMPLETION OF HIS WORK.
<br />14. SEE THE ARCHITECTURAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
<br />GENERAL NOTES AND SPECIFICATIONS. REPORT ANY DISCREPANCIES TO THE
<br />ARCHITECT BEFORE COMMENCING WORK.
<br />15. ALL ELECTRICAL POWER DEVICES SHALL BE LEVITON DECORA SERIES WITH
<br />SCREWLESS TYPE COVER PLATES, LUTRON DESIGNER STYLE.
<br />16. ALL EXPOSED ELECTRICAL DEVICES AND COVER PLATES SHALL BE EITHER
<br />WHITE OR BLACK, AS SPECIFIED ON THE DRAWINGS. WHITE PLATES SHALL BE
<br />INSTALLED AT ALL WALLS TO RECEIVE PAINT P-1. BLACK PLATES SHALL BE
<br />INSTALLED AT ALL WALLS TO RECEIVE PAINT P-2 OR WALL COVERING WC-1.
<br />17. THE CONTRACTOR IS TO COORDINATE PROJECT REQUIREMENTS WITH
<br />REQUIREMENTS OF SPECIAL EQUIPMENT INSTALLATIONS BY THE TENANT.
<br />18. ALL POWER, DATA AND TELEPHONE RECEPTACLES SHALL BE INSTALLED WITH
<br />THE CENTERLINE AT 18 INCHES A.F.F., UNLESS OTHERWISE NOTED.
<br />19. THE ELECTRICAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, SAMPLES
<br />AND PRODUCT DATA OF THE SPECIFIED WORK FOR REVIEW BY THE GENERAL
<br />CONTRACTOR, ARCHITECT, CONSULTING ENGINEER AND TENANT AS
<br />SPECIFIED IN SECTION 01340. SUPPLY ONE ADDITIONAL COPY FOR EACH ITEM
<br />SUBMITTED.
<br />20. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE
<br />CONSTRUCTION OF A COMPLETE ELECTRICAL POWER AND LIGHTING
<br />SYSTEMS. THE ELECTRICAL CONTRACTOR SHALL NOTIFY THE ARCHITECT
<br />IMMEDIATELY, IN WRITING, OF ANY CONFLICTS SHOWN BETWEEN HIS WORK
<br />AND THE WORK OF ANY OTHER TRADE. ANY SYSTEM LOCATIONS OR SPECIAL
<br />EQUIPMENT LOCATIONS INDICATED IN THESE DRAWINGS OR SPECIFICATIONS
<br />SHALL BE INCLUDED IN THE CONTRACTOR'S WORK, AS SHALL BE ANY
<br />EXISTING DEVICES TO REMAIN.
<br />SECTION 16510 - INTERIOR LIGHTING
<br />1. SEE ENGINEERING DRAWINGS FOR ADDITIONAL INFORMATION, INCLUDING
<br />BUT NOT LIMITED TO ELECTRICAL PLANS, NOTES, DETAILS, DIAGRAMS AND
<br />SCHEDULES.
<br />2. SUBMITTALS: FOR EACH TYPE OF LIGHTING FIXTURE, ARRANGED IN ORDER OF
<br />FIXTURE DESIGNATION, PROVIDE PRODUCT DATA ON FEATURES,
<br />ACCESSORIES, FINISHES, PHYSICAL DIMENSIONS, BALLAST,
<br />ENERGY -EFFICIENT DATA, AIR AND THERMAL PERFORMANCE DATA, SOUND
<br />PERFORMANCE DATA, LIFE, OUTPUT AND ENERGY -EFFICIENCY FOR LAMPS,
<br />AND PHOTOMETRIC DATA.
<br />3. ALL ACOUSTICAL TILE, DRYWALL AND CEILING WORK SHALL BE CLOSELY
<br />COORDINATED WITH OTHER TRADES WHOSE WORK AFFECTS OR IS
<br />AFFECTED BY THESE TRADES.
<br />4. ALL EMERGENCY LIGHTING FIXTURES ARE IN SUGGESTED LOCATIONS,
<br />SUBJECT TO CODE APPROVAL. QUANTITY AND LOCATIONS ARE THE
<br />RESPONSIBILITY OF THE CONTRACTOR, AND AS INDICATED ON THE
<br />ENGINEERING DRAWINGS.
<br />5. THE GENERAL CONTRACTOR SHALL VERIFY ALL RECESS DEPTHS OF
<br />FIXTURES AGAINST DUCTWORK, PIPES, BEAMS, ETC. AND IMMEDIATELY
<br />REPORT ANY DISCREPANCIES TO THE ARCHITECT.
<br />6. NEW LIGHT FIXTURES, LENSES AND ACOUSTIC TILE SHALL BE AS INDICATED
<br />ON THE DRAWINGS, UNLESS OTHERWISE NOTED.
<br />7. ALL SWITCH PLATES TO BE SCREWLESS TYPE, LUTRON DESIGNER STYLE. ALL
<br />SWITCHES, DIMMERS, SENSORS TO BE LUTRON DIVA STYLE.
<br />8. FURNISH EXTRA MATERIALS THAT MATCH PRODUCTS INSTALLED AS
<br />FOLLOWS, UNLESS NOTED OTHERWISE ON THE CONTRACT DOCUMENTS:
<br />a. LAMPS: 10 FOR EVERY 100 OF EACH TYPE AND RATING INSTALLED, BUT
<br />NOT LESS THAN ONE OF EACH TYPE
<br />b. PLASTIC DIFFUSERS AND LENSES: 1 FOR EVERY 100 OF EACH TYPE AND
<br />RATING INSTALLED, BUT NOT LESS THAN ONE OF EACH TYPE
<br />c. BATTERY AND CHARGER DATA: ONE FOR EACH EMERGENCY LIGHTING
<br />UNIT
<br />d. BALLASTS: 1 FOR EVERY 100 OF EACH TYPE AND RATING INSTALLED, BUT
<br />NOT LESS THAN ONE OF EACH TYPE
<br />e. GLOBES AND GUARDS: 1 FOR EVERY 20 OF EACH TYPE AND RATING
<br />INSTALLED, BUT NOTE LESS THAN ONE OF EACH TYPE
<br />10. SEE ARCHITECTURAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL GENERAL
<br />NOTES AND SCHEDULES. REPORT ANY DISCREPANCIES TO THE ARCHITECT
<br />PRIOR TO COMMENCING THE WORK.
<br />11. ALL FIXTURES OF SAME MARKITYPE TO RECEIVE LAMPS OF SAME COLOR
<br />TEMPERATURE/CRI FROM SAME MANUFACTURER.
<br />100
<br />7jN7e-t1mqqers
<br />NORTH AMERICA
<br />4
<br />09.18.2013
<br />ISSUE FOR PERMIT
<br />3
<br />09.11.2013
<br />ISSUE FOR BIDS
<br />2
<br />1
<br />NO.
<br />09.03.2013
<br />08.16.2013
<br />DATE
<br />CD REVIEW PACKAGE
<br />DD REVIEW PACKAGE
<br />REVISIONS/ISSUANCES
<br />�PSTEIN
<br />Architecture
<br />Chicago
<br />Interiors
<br />New York
<br />Engineering
<br />Bucharest
<br />Construction
<br />Warsaw
<br />600 W. Fulton Street
<br />Chicago, IL 60661-1259
<br />T 312.454.9100
<br />www.epsteinglobal.com
<br />PROJECT NUMBER: 12386
<br />PROJECT MANAGER: JK
<br />ARCH/ENG: LK
<br />SCALE: 1/32" = 1'-0"
<br />DRAWN BY: JK
<br />CHECKED BY: LK
<br />v
<br />INTERIOR OUTLINE
<br />SPECIFICATONS
<br />SEALCA-004