It <br />PLUMBING SPECIFICATIONS <br />SCOPE: THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE THE DRAWINGS AND SPECIFICATIONS BEFORE SUBMITTING A PROPOSAL. ALL WORK SHALL BE IN ACCORDANCE <br />WITH THE FLORIDA BUILDING CODES SEVENTH EDITION (2020), WITH AMENDMENTS, AND LOCAL CODES AND ORDINANCES. INSTALLATION SHALL COMPLY WITH THE CODE <br />REFERENCED STANDARDS SET BY NFPA, ASHRAE, ASPE, SMACNA, NEC AND UL. THE SYSTEMS, EQUIPMENT, DEVICES AND ACCESSORIES SHALL BE INSTALLED, FINISHED, <br />TESTED AND ADJUSTED FOR CONTINUOUS AND PROPER OPERATION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR HIS WORK FITTING IN PLACE AND SHALL COORDINATE <br />WITH OTHER TRADES TO AVOID INTERFERENCE WITH THEIR WORK. THE INFORMATION GIVEN HEREIN AND ON THE DRAWINGS IS AS EXACT AS COULD BE SECURED, BUT ITS <br />EXTREME ACCURACY IS NOT GUARANTEED. THE DRAWINGS ARE DIAGRAMMATIC, INTENDED TO SHOW GENERAL ARRANGEMENT, CAPACITY AND LOCATION OF VARIOUS <br />COMPONENTS, EQUIPMENTS, AND DEVICES. IF WORK IS REQUIRED IN A MANNER TO MAKE IT IMPOSSIBLE TO PRODUCE FIRST CLASS WORK, OR SHOULD DISCREPANCIES <br />APPEAR AMOUNG THE CONTRACT DOCUMENTS, OR BETWEEN THE CONTRACT DOCUMENTS AND THE MANUFACTURER'S RECOMMENDATIONS,THE CONTRACTOR SHALL REQUEST <br />INTERPRETATION BEFORE PROCEDING WITH WORK. CONTRACTOR SHALL FURNISH AND INSTALL ALL MINOR ITEMS WHICH ARE OBVIOUSLY AND REASONABLY NECESSARY TO <br />COMPLETE THE INSTALLATION WHETHER OR NOT SPECIFIED IN THE DOCUMENTS. <br />REQUIRED COORDINATION: ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN DUCTS AND PIPING (INCLUDING DIVIDED DUCTS) AND TRANSITIONS <br />AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER. <br />CONSTRUCTION PLANS: IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY AND SHOULD NOT BE SCALED. <br />REQUIRED ACCESS: CONTRACTOR SHALL ENSURE THAT ALL EQUIPMENT AND DEVICES THAT REQUIRE REPLACEMENT, SERVICING, ADJUSTING OR MAINTENANCE SHALL BE <br />LOCATED TO ALLOW EASY ACCESS AND SPACE FOR REMOVAL OF INTERNAL ASSMBLIES, IF REQUIRED. CONTRACTOR SHALL PROVIDE ACCESS PANELS WHERE REQUIRED TO <br />ALLOW ACCESS, EVEN IF NOT INDICATED ON THE DRAWINGS AT NO ADDITIONAL COST TO OWNER. <br />WIND RESISTANCE: ALL EQUIPMENT, APPLIANCE AND SUPPORTS LOCATED EXTERIOR OF THE FACILITY SHALL BE INSTALLED TO RESIST WIND LOADS AS DETAILED IN THE <br />BUILDING CODE. <br />CUTTING AND PATCHING: ALL OPENINGS AROUND DUCT OR PIPE PENETRATIONS THROUGH SMOKE OR FIRE RATED FLOORS, CEILINGS OR WALLS SHALL BE SEALED AIRTIGHT <br />WITH MATERIALS HAVING A RATING EQUAL TO THE MATERIAL OF THE WALL, CEILING OR FLOOR PENETRATED. <br />ALL EQUIPMENT WILL HAVE A PERMANENTLY FIXED TAG CORRESPONDING TO THE EQUIPMENT TAG ON THE ENGINEER'S DRAWINGS. <br />FIRESTOPPING: UL APPROVED MATERIALS AND METHODS SHALL PROTECT THE PENETRATIONS OF FIRE AND/OR SMOKE RATED WALLS, CEILINGS OR FLOORS. THE RATING OF <br />THE FIRESTOPPING SHALL EQUAL THE RATING OF THE RATED ASSEMBLY. ALL INSULATION SHALL HAVE COMPOSITE FIRE AND SMOKE HAZARD RATINGS AS TESTED BY <br />PROCEDURE ASTM E-84, NFPA-225, UL-723 NOT EXCEEDING: <br />FLAME SPREAD 25 <br />SMOKE DEVELOPED 50 <br />FUEL DISTRIBUTED 50 <br />ACCESSORIES SUCH AS ADHESIVE, MASTIC, CEMENTS AND TAPES SHALL HAVE THE SAME COMPONENT RATING AS LISTED ABOVE. <br />SERVICE AND PERMITS: CONTRACTOR SHALL MAKE ALL ARRANGEMENTS WITH UTILITY COMPANIES FOR SERVICE AND CONNECTIONS AND SHALL PAY FOR PERMITS. <br />SHOP DRAWINGS: EACH TRADE SHALL PREPARE AND SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH PROCEDURES OUTLINED IN DIVISION 1. RESPONSIBILITY FOR ERRORS <br />OR OMISSIONS IN THE SUBMITTALS SHALL NOT BE RELIEVED BY THE ARCHITECT'S OR ENGINEER'S REVIEW. ENGINEER'S PROCESSING WILL NOT CONSTITUTE A COMPLETE <br />CHECK BUT WILL INDICATE ONLY THAT A GENERAL METHOD OF CONSTRUCTION AND DETAILING IS SATISFACTORY. AT A MINIMUM SUBMITTALS SHALL INCLUDE FIXTURES, <br />VALVES, PIPING, INSULATION AND ACCESSORIES. <br />START-UP: CONTRACTOR SHALL STARTUP ALL EQUIPMENT AND FOLLOW THE MANUFACTURER'S START-UP PROCEDURES. <br />OPERATING AND MAINTENANCE DATA: SUBMIT THREE COPIES OF MANUFACTURER'S OPERATING AND MAINTENANCE INSTRUCTIONS AND SPARE PARTS LIST FOR EACH PIECE OF <br />EQUIPMENT. <br />SUPPLEMENTARY SUPPORTS: CONTRACTOR SHALL PROVIDE ALL SUPPLEMENTARY STEEL REQUIRED TO SUSPEND MECHANICAL EQUIPMENT AND MATERIALS, IN ORDER TO <br />PROVIDE A "VIBRATION -FREE" RIGID INSTALLATION. <br />DIELECTRIC UNIONS: PROVIDE DIELECTRIC UNIONS OR FLANGES AT CONNECTIONS OR CONTACT BETWEEN PIPES OF DISSIMILAR METALS. <br />WATER PIPING: WATER PIPING SHALL BE CPVC TUBING. TUBING, FITTINGS AND CEMENT SHALL MEET ASTM D-2846, 100 PSI ® 1807 CONTINUOUS RATING. CPVC TUBING <br />AND FITTINGS SHALL MEET 25/50 FLAME SPREAD/SMOKE DEVELOPED REQUIREMENTS FOR PLENUMS. CONTRACTOR SHALL INSTALL CPVC IN ACCORDANCE WITH <br />MANUFACTURER'S INSTRUCTIONS. CONTRACTOR SHALL PROVIDE FOR EXPANSION AND CONTRACTION OF TUBING. TUBING SHALL BE SLEEVED AT PENETRATION OF CONCRETE <br />SLABS OR WALLS. CPVC TUBING SHALL BE BFGOODRICH FLOWGUARD GOLD OR APPROVED EQUAL. INSTALL PIPE SUPPORTS AT 3-FOOT INTERVALS FOR SIZES 1" OR <br />SMALLER; INSTALL PIPE SUPPORTS AT 4-FOOT INTERVALS FOR 1-1/4" AND LARGER. <br />WATER HAMMER ARRESTORS: INSTALL WATER HAMMER ARRESTERS AT EACH HOT AND COLD FIXTURE SUPPLY. <br />EXPOSED PIPING: EXPOSED PIPING SHALL BE POLISHED CHROMIUM ON EITHER BRASS OR BRONZE. PROVIDE ADA INSULATED WATER AND WASTE LINE COVERINGS FOR WALL <br />HUNG SINKS AND LAVATORIES. <br />VALVES: ALL VALVES SHALL HAVE A MINIMUM OF 125 PSIG WORKING PRESSURE. VALVES AND COCKS MAY NOT BE INDICATED IN EVERY INSTANCE ON THE DRAWINGS, BUT <br />WHETHER OR NOT SHOWN, ALL VALVES, COCKS AND CHECK VALVES NECESSARY FOR THE PROPER OPERATION OF THE SYSTEM SHALL BE FURNISHED AND INSTALLED. <br />INSTALL ISOLATION/SHUT-OFF VALVES AT ALL MAIN RISERS, AND MAIN BRANCH TAKEOFFS. INSTALL ISOLATION/SHUT-OFF VALVES ON EACH INLET AND OUTLET OF EACH <br />PIECE OF EQUIPMENT. PROVIDE A FLANGE OR UNION BETWEEN THE VALVE AND THE EQUIPMENT TO PERMIT DISCONNECTION, REMOVAL AND SERVICE. <br />STERILIZATION OF DOMESTIC WATER SYSTEM: THE ENTIRE DOMESTIC WATER DISTRIBUTION SYSTEM SHALL BE THOROUGHLY STERILIZED AS REQUIRED BY THE HEALTH <br />AUTHORITY OR WATER PURVEYOR HAVING JURISDICTION, OR IN THE ABSENCE OF A PRESCRIBED METHOD, THE PROCEDURE DESCRIBED IN EITHER AWWA C651 OR AWWA C652, <br />OR AS DESCRIBED IN SECTION 610 FBC-P. <br />NATURAL GAS SYSTEM: A SERVICE LINE, METER AND PRESSURE REDUCING VALVE HAS BEEN FURNISHED BY THE LOCAL GAS UTILITY COMPANY. THE COMPLETE GAS PIPING <br />SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH SEVENTH EDITION FBC (2020) - FUEL GAS CODE. ABOVE GROUND GAS TO BE SCHEDULE 40 BLACK STEEL PIPING, <br />ASTM A53. BELOW GROUND TO BE POLYETHYLENE GAS PIPING WITH CODE REQUIRED TRACER WIRE (FBC-FG, SECTION 404.17.3), ASTM D 2513. GAS PIPING INSTALLED <br />UNDER SLAB SHALL BE RUN IN STEEL CONDUIT AND SEALED IN ACCORDANCE WITH FBC-FG, SECTION 404.14. PROVIDE UNION AND GAS SHUT-OFF VALVE TO EACH PIECE <br />OF GAS FIRED EQUIPMENT OR APPLIANCE. PIPE INSTALLATION MUST BE TESTED IN ACCORDANCE WITH FCB-FC, SECTION 406. <br />VENTING: THE STACKS SHALL BE EXTENDED THROUGH ROOF OF BUILDING TO POINTS NOT LESS THAN 12" ABOVE ROOF. VENTS SHALL BE OFFSET AS REQUIRED TO <br />PENETRATE ROOFS AT LEAST 3 FEET FROM THE RIDGE OR EDGE OF BUILDING AND 10 FEET FROM ANY FRESH AIR INTAKE OR OPERABLE WINDOW OR DOOR, <br />SANITARY, WASTE. AND VENT PIPING: ALL BURIED AND UNBURIED PIPING AND FITTINGS SHALL BE SCHEDULE 40 PVC-DWV. (SOLID CORE) SLOPE OF SANITARY OR <br />DRAINAGE PIPING 2-1 /2" AND SMALLER SHALL BE A MINIMUM OF 1 /4" PER FOOT; PIPING 3" AND LARGER SHALL BE SLOPED A MINIMUM OF 1 /8" PER FOOT. CLEANOUTS <br />WILL BE LOCATED NOT MORE THAN 100 FEET APART AND AT EACH CHANGE OF DIRECTION GREATER THAN 45' ALONG THE HORIZONTAL DRAIN. CLEANOUTS SHALL BE <br />INSTALLED AT BASE OF EACH STACK. CONCEALED CLEANOUTS SHALL HAVE CAST BRASS CHROMIUM PLATED FLAT ACCESS COVER PLATE. <br />FLOOR DRAINS/SINKS: FLOOR DRAINS SHALL BE CAST IRON AND ADJUSTABLE TO ACCOMMODATE THE FINISHED FLOOR. FLOOR SINKS SHALL HAVE AN ACID -RESISTANT <br />ENAMELED INTERIOR. STRAINERS SHALL BE PROVIDED WITH BARRIER -TYPE TRAP SEAL PROTECTION (ASSE 1072) AND FLASHING FLANGE OR CLAMP, UNLESS OTHERWISE <br />INDICATED. <br />PLUMBING FIXTURES AND TRIM: PLUMBING FIXTURES SHALL BE FURNISHED AND INSTALLED IN A NEAT AND WORKMANLIKE MANNER WITH PROPER CONNECTIONS TO SUPPLY <br />AND DRAINAGE PIPING. ALL FIXTURES SHALL BE FREE OF FLAWS AND DEFECTS OF ANY SORT IN MATERIAL AND WORKMANSHIP AND SHALL OPERATE PERFECTLY WHEN <br />INSTALLED IN ACCORDANCE WITH MANUFACTURER'S DIRECTIONS. CONTRACTOR SHALL PROVIDE ROUGH -IN, AND SHALL CONNECT ALL FIXTURES TO THE PLUMBING SYSTEMS. <br />ALL FIXTURES TO BE PROVIDED WITH CHROME -PLATED SUPPLIES AND STOPS. PROVIDE 17 GAUGE CHROME -PLATED BRASS TRAPS FOR ALL FIXTURES WITHOUT INTEGRAL <br />TRAPS. PROVIDE CONCEALED ARM CARRIERS AND SUPPORTS FOR ALL FIXTURES REQUIRING SAME. <br />PIPE INSULATION: INSTALL INSULATION PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES. SEAL <br />ALL JOINTS, BREAKS, TEARS AND PENETRATIONS WITH FIRE RETARDENT, VAPOR BARRIER MASTIC. COVER VALVES, FITTINGS AND SIMILAR ITEMS IN EACH PIPING SYSTEMS. <br />INSULATE ALL DOMESTIC HOT WATER PIPE WITH 1" THICK FIBERGLASS SECTIONAL PIPE COVERING WITH CANVAS JACKET OR ARMAFLEX AP (ASTM E-84). <br />TESTING: TEST ALL WASTE AND VENT PIPING FOR A PERIOD OF NOT LESS THAN 8 HOURS BY CAPPING OR PLUGGING. ALL JOINTS TO A LEVEL OF THE HIGHEST FIXTURE OR <br />FITTINGS. FILLING THE SYSTEM WITH WATER, AND OBSERVING FOR LEAKS. TEST WATER PIPING AT 100 PSIG FOR A PERIOD OF 8 HOURS, OBSERVING FOR ANY VISIBLE <br />LEAKS. TEST PIPING AGAIN WITH FIXTURES INSTALLED. REPAIR ANY LEAKS FOUND BY REMAKING JOINT. DO NOT USE CAULKING OR SIMILAR METHODS TO CORRECT LEAKS. <br />UPON REPAIRING ANY LEAKS FOUND. AGAIN TEST THAT PORTION OF THE SYSTEM AS DESCRIBED ABOVE. <br />EQUIPMENT FURNISHED BY OTHERS: WHERE SHOWN ON THE DRAWINGS, THE CONTRACTOR SHALL MAKE ALL PIPING CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS. <br />THIS WORK SHALL INCLUDE FURNISHING AND INSTALLATION OF ALL WATER AND DRAIN PIPING. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH RECOMMENDATIONS <br />OF EQUIPMENT MANUFACTURER. <br />GUARANTEE: THE ONE-YEAR GUARANTEE PERIOD SHALL NOT START UNTIL THE PROJECT IS FULLY COMPLETED AND THE CONTRACTOR HAS RECEIVED THE FINAL PAYMENT <br />AND CERTIFICATION OF COMPLETION. ALL EQUIPMENT AND ALL WORK SHALL BE FULLY GUARANTEED, PARTS AND LABOR, FOR ONE YEAR FROM THE DATE OF THE <br />CERTIFICATE OF COMPLETION. REPAIRS MADE DURING THIS PEROID MUST BE FULLY GUARANTEED FOR AN ADDITIONAL ONE YEAR PERIOD FROM THE DATE OF REPAIRS. IN <br />ADDITION, THE CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR ANY DAMAGE TO THE BUILDING, AND ITS CONTENTS OR OTHER EQUIPMENT, CAUSED BY DEFECTS OR <br />IMPROPER INSTALLATION OF EQUIPMENT OR MATERIAL INSTALLED. <br />SUBSTITUTIONS: CONTRACTOR 'SHALL PAY FOR ANY AND ALL ADDED COSTS ASSOCIATED WITH ANY SUBSTITUTION, INCLUDING SUBSTITUTIONS THAT REQUIRE CHANGES TO THE <br />OTHER BUILDING COMPONENTS, SUCH AS ELECTRICAL, STRUCTURAL REINFORCING, CEILINGS, WALLS, ROOFS, ETC. THIS WILL INCLUDE ANY ENGINEERING/ARCHITECTURAL <br />RE -DESIGN COSTS AS A RESULT OF SAID SUBSTITUTION. THESE COSTS SHALL NOT BE BORNE BY THE OWNER, ARCHITECT, NOR ENGINEER, REGARDLESS OF ACCEPTABILITY <br />OF SUBSTITUTION. ENGINEER RESERVES THE RIGHT TO ACCEPT OR DENY ANY SUBSTITUTION THAT HE DOES NOT DEEM TO BE EQUIVALENT, AND CONTRACTOR SHALL <br />PROVIDE SPECIFIED OR EQUIVALENT MATERIALS/EQUIPMENT AT NO ADDITIONAL COST TO OWNER, SHOULD A SUBSTITUTION BE DENIED. <br />PLUMBING LEGEND <br />DESCRIPTION <br />ABBREV. <br />SYMBOL <br />SANITARY PIPING <br />SAN <br />GREASE PIPING <br />GR <br />GR <br />VENT PIPING <br />V <br />DOMESTIC COLD WATER <br />CW <br />--------- <br />DOMESTIC HOT WATER <br />HW <br />---------- <br />GAS PIPING <br />GAS <br />--w---�—�- <br />BALL/ISOLATION VALVE <br />BV <br />-----lei--- <br />DUAL-CHECK BACKFLOW <br />PREVENTER <br />GRADE CLEAN OUT <br />COTG <br />COTG <br />WALL CLEAN OUT <br />WCO <br />WCO I <br />FLOOR CLEAN OUT <br />FCO <br />FCO <br />PIPE TURNING UP <br />0------- <br />PIPE TURNING DOWN <br />------ <br />CAPPED PIPING <br />TYPICALITEM <br />TYP <br />CONNECTION BETWEEN <br />NEW & EXISTING <br />EXISTING <br />(E) <br />NEW <br />(N) <br />BALANCE VALVE <br />BV <br />NOTE ON EXISTING UTILITIES: <br />CONTRACTOR SHALL FIELD VERIFY LOCATIONS & INVERTS <br />OF ALL EXISTING UTILITY MAINS INSIDE BUILDING (I.E. <br />SEWER, GAS, DOMESTIC WATER, ETC.) PRIOR TO ANY <br />DEMOLITION OR CONSTRUCTION. ADVISE ENGINEER OF <br />ANY DISCREPANCIES BEFORE PROCEEDING ANY FURTHER. <br />** CCTV VIDEO CAMERA INVESTIGATION REQUIRED BY PLUMBER <br />(PRIOR TO ANY WORK) TO VERIFY INVERT ADEQUATE AT MOST <br />REMOTE AREA OF NEW SANITARY UNDERGROUND CONNECTION. <br />NOTIFY ENGINEER OF RESULTS OF CAMERA WORK. <br />NOTE TO CONTRACTOR <br />ON EXISTING CONDITIONS: <br />1 CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND <br />SURVEY ALL EXISTING CONDITIONS AND EQUIPMENT <br />PRIOR TO SUBMITTING BID FOR WORK REQUIRED BY <br />THESE DOCUMENTS. THIS INCLUDES ABOVE THE <br />CEILING AND ON TOP OF THE ROOF. <br />2. CONTRACTOR SHALL REFER TO AND READ THROUGH <br />ALL OF THE "CONTRACTOR'S SCOPE OF WORK" AS <br />DEFINED IN THE BID SPECIFICATIONS AND DOCUMENTS <br />AS PART OF THE BID PROCESS. <br />3. IF AT ANY TIME, THERE IS DISCREPANCY BETWEEN THE <br />PLANS & SPECS. OR CONFUSION/CONCERN OVER <br />REQUIRED WORK, CONTRACTOR SHALL IMMEDIATELY <br />NOTIFY ARCHITECT. ENGINEER, &/OR OWNER AND GET <br />DIRECTION BEFORE PROCEEDING WITH WORK IN <br />I#l1j*v `•l.e <br />4. FOR ALL NEW ROOF PENETRATIONS, CONTRACTOR <br />SHALL INCLUDE IN HIS BID THE COST TO HIRE THE <br />ROOFING FIRM HOLDING THE WARRANTY TO PROVIDE <br />ROOF PENETRATIONS. <br />5. FOR ALL EXISTING EQUIPMENT TO BE RE -LOCATED <br />&/OR RE -USED, CONTRACTOR SHALL BE RESPONSIBLE <br />FOR DISCONNECTION, SAFE STORAGE, & <br />RE -CONNECTION OF SAID EQUIPMENT COMPLETELY. <br />6. FOR ALL EXISTING EQUIPMENT TO BE DEMOLISHED (I.E. <br />DEMO) CONTRACTOR SHALL BE RESPONSIBLE FOR <br />DISCONNECTION, REMOVAL, & DISPOSAL OFF -SITE PER <br />CODE, OF SAID EQUIPMENT COMPLETELY. <br />CIYIIII <br />/� M 0) <br />V 0 � � ao <br />I <br />0 <br />F_ t N <br />Q V) U <br />O 3 M <br />w <br />Y V) Yd <br />o <br />V) J <br />W i� <br />Z< Wa�� M <br />aVi <br />CL Q W U M <br />/uj w Z � J � y J <br />w <br />Q <br />u- <br />�9 <br />a� <br />o <br />L <br />r j <br />A <br />a a <br />a R <br />>> <br />R <br />E <br />Vl <br />4 r y <br />+' <br />O <br />N O <br />O <br />(4-- <br />0z <br />(� <br />Q <br />tl) <br />z <br />W <br />< <br />a <br />(a <br />a <br />(.) <br />o <br />O <br />v <br />Q <br />< <br />to <br />O <br />� <br />Z <br />-p <br />Lo <br />(� <br />a_ <br />LIA <br />N <br />e� <br />� <br />W <br />ti <br />O <br />q r~ <br />Al <br />Nu 56189 <br />°. MATE OF <br />s' <br />TONAL <br />Date: 4. 25.22 <br />Checked by: mil <br />Drawn: TJ/KB <br />.lob: 21-042 <br />Sheet <br />POO 1 <br />